5

4 205 503 / 14

DESCRIPTION OF FUNCTIONS

2.7 

Short description of the functions of the BIC 960 automatic firing device

Since the automatic firing device can only perform in connection with the heating controller, many common functions 

are already given via this. The list below contains only those characteristics which are integrated in the automatic 

firing device:

-  Modulating operating mode

-  Combined electrode for ignition and flame monitoring (Ionisation) 

-  Main gas valve (possibly LPG-valve) and/or heating room fan acitvatable

-  Inputs for Flow sensor 1

   

 

Flow sensor 2

   

 

Flue gas sensor

   

 

Water pressure sensor

   

 

Safety and limit value thermostat (external exhaust gas temperature switch possible)

   

 

Air pressure switch (not used)

   

 

Gas pressure switch

-  “Alarm” and “Flame monitoring” status outputs

-  Additional (external) ignition can be attached

-  RS 485- connection to heating controller

-  RS 232-connection to PC

-  Number of start-up attempts: maximum 4

-  Safety time: 5 secs

-  Pre-ignition: 5 secs

-  Pre-venting: 50 secs

-  Pump after-run time (230V AC): 5 min after heating demand

Faults:

If there is a fault, an error code will appear on the display of the heating controller. Pressing the reset button, located 

under the hinged cover on the front of the unit, will release the automatic burner, and the boiler will resume opera-

tion, if the fault has been rectified. For more detailed information, see section 7.

Fuses:

The BIC 960 has 3 safety fuses:  

 

2AT 

Mains

 

 

   

 

 

4AT 

Pump

 

 

   

 

 

4AT 

Burner fan

What happens when the fuses blow 

4AT (Pump) 

Pump fails to start.

4AT (Burner fan) 

Burner fan fails to start. If a rotation set value has been allocated for the burner fan, 

an error message E:18 (“Fan rotation speed below limit”) will appear after a short 

period of time, indicating that the fuse has blown.

2AT (Mains) 

there is no communication between the automatic firing unit and the heating control-

ler. As a result an error message is displayed on the heating controller.

Содержание BIC 960

Страница 1: ...40 41 UltraGas 50 10 20 30 41 UltraGas 70 10 20 30 UltraGas 90 30 41 UltraGas 100 10 11 20 21 30 41 UltraGas 125 10 11 20 21 30 41 UltraGas 150 10 11 20 21 30 41 UltraGas 200 10 11 20 21 30 41 UltraG...

Страница 2: ...the parameters 6 4 Sensor characteristic curves 12 5 Display of information via the automatic firing device 13 6 Monitoring of warnings and or faults 14 7 Operation using a laptop 16 8 Interfaces to B...

Страница 3: ...nection to TopTronic T TopTronic E 1 Gas pressure regulator 2 3 Gas valve 4 Fan 5 6 Boiler sensor with two sensor elements 7 Flue gas sensor only with UltraGas 8 Ionisation electrode ignition 9 Igniti...

Страница 4: ...operation is ended automatically and the boiler reverts to the prior operation mode It is important to ensure that the heat produced during emission testing can also be discharged When setting boiler...

Страница 5: ...ng controller RS 232 connection to PC Number of start up attempts maximum 4 Safety time 5 secs Pre ignition 5 secs Pre venting 50 secs Pump after run time 230V AC 5 min after heating demand Faults If...

Страница 6: ...n the bus connection between the heating controller and the automatic firing device the automatic firing device begins to operate in emergency mode which means that a set value of 75 C parameter 8 is...

Страница 7: ...ber of rotations to the minimum rotation number Parameter 10 2AK 32778 Max temperature rise at high flow temperature The temperature gradient defined here is deemed to be exceeded if it rises above th...

Страница 8: ...hown on the display Parameter 20 2DE 32788 Blocking pressure min hysteresis Blocking caused by insufficient water pressure is only lifted when the water pressure rises back to Parameter 19 Parameter 2...

Страница 9: ...r 28 2FG 32796 Fan speed at start In the second period of the pre venting phase which also lasts 25 seconds the fan operates at the speed set here and at the end of this period the burner ignites See...

Страница 10: ...eration or blocking After a heat demand and or after blocking of the boiler the fan operates for the period of time defined here and at the speed set under Parameter 36 Parameter 38 2FU 32806 Fan spee...

Страница 11: ...ult Parameter 46 2NA 32814 Setting water pressure sensor ADC 4 value at 0 bar The set values of the water pressure sensor are used to indicate the actual water pressure via the voltage delivered from...

Страница 12: ...12K NTC Sensor screw in sen sor The characteristic curve of the pressure sensor module MCTH 1 0 10 bar is linear The signal voltage of the sen sor at 0 bar is always 0 5V and at 10 bar is always 4 5V...

Страница 13: ...re ignition 5 ON Ignition 6 ON Burning 7 OFF Post venting Using the heating controller parameter tree it is possible to access both the parameter and information levels of the automatic firing device...

Страница 14: ...ing level set under Parameter 17 boiler capacity is reduced to the capacity set under Parameter 24 W 02 Ionisation too low Appears if the ionisation warning limit set under Parameter 25 is under run B...

Страница 15: ...After a parameter set is loaded on the automatic firing device the boiler is locked automatically After pressing re set boiler operation can be resumed E 14 Parameter loading error A connection error...

Страница 16: ...available Printing parameter settings Saving parameter settings in a text file Downloading parameter settings from the connected automatic firing device Loading parameter settings to the connected au...

Страница 17: ...lve Fan 5 Not occupied 6 L Main gas valve 7 N Main gas valve X5 4 pin Molex Header White 5 08 mm 0 2 Pitch 1 Flame monitoring 2 Flame monitoring 3 Error reporting 4 Not occupied 5 Error reporting X6 4...

Страница 18: ...oiler sensor 2 Sensor short circuit 125 C Lock out Sensor not connected 25 C Lock out Lock out temperature 110 C Lock out Maximum temperature difference between sensor 1 and sensor 2 10 C Lock out Blo...

Страница 19: ...Switch on temperature with active boiler frost protection 3 C Switch off temperature with active boiler frost protection 10 C 12 Water pressure Pressure warning 1 bar Warning Blocking pressure min 0 5...

Страница 20: ...r Duplex material aluFer Diameter 71mm thin wall thicknesses housing red orange sheet steel x yes RG128 Duplex material aluFer Diameter 71mm thin wall thicknesses housing red sheet steel new design x...

Страница 21: ...ameter change in relation to generation 40 UltraGas 15 Duplex material aluFer Diameter 71mm thin wall thicknesses housing red sheet steel new design new TopTronic E controller sliding logo removed x n...

Страница 22: ...per revolution Software version FOAA P120320 and higher label with V 3 lettering x Parameter 47 Water pressure sensor setting UltraGas 20 x x x UltraGas 27 x x x UltraGas 35 x x x UltraGas 50 x x x U...

Страница 23: ...ed OEM ON 16 2DA Water pressure sensor attached OEM ON 17 2DB Water pressure warning bar OEM 1 18 2DC Water pressure hysteresis bar OEM 0 2 19 2DD Blocking pressure min bar OEM 0 5 20 2DE Blocking pre...

Страница 24: ...ation summer kick sec OEM 10 43 2IA Ignition 0 Internal 1 Internal External 2 External OEM 2 0 0 0 0 0 0 0 44 2KM Step modulation 0 off 1 increasing 2 increasing and decreasing HF 1 45 2LA Effect of t...

Страница 25: ...110 14 2BD Blocking flue gas temperature C OEM 100 15 2CA Gas pressure switch attached OEM ON 16 2DA Water pressure sensor attached OEM ON 17 2DB Water pressure warning bar OEM 1 18 2DC Water pressur...

Страница 26: ...EM ON 41 2HA Afterrun heating pump or shut off valve min HF 5 42 2HD Summer operation summer kick sec OEM 10 43 2IA Ignition 0 Internal 1 Internal External 2 External OEM 2 0 0 0 0 0 44 2KM Step modul...

Страница 27: ...king flue gas temperature C OEM 100 15 2CA Gas pressure switch attached OEM ON 16 2DA Water pressure sensor attached OEM ON 17 2DB Water pressure warning bar OEM 1 18 2DC Water pressure hysteresis bar...

Страница 28: ...p or shut off valve min HF 5 42 2HD Summer operation summer kick sec OEM 10 43 2IA Ignition 0 Internal 1 Internal External 2 External OEM 2 0 0 0 0 0 0 0 0 44 2KM Step modulation 0 off 1 increasing 2...

Страница 29: ...ing flue gas temperature C OEM 100 15 2CA 32783 Gas pressure switch attached OEM ON 16 2DA 32784 Water pressure sensor attached OEM ON 17 2DB 32785 Water pressure warning bar OEM 1 18 2DC 32786 Water...

Страница 30: ...eating pump or shut off valve min HF 5 42 2HD 32810 Summer operation summer kick sec OEM 10 43 2IA 32811 Ignition 0 Internal 1 Internal External 2 External OEM 2 44 2KM 32812 Step modulation 0 off 1 i...

Страница 31: ...ed OEM ON 16 2DA Water pressure sensor attached OEM ON 17 2DB Water pressure warning bar OEM 1 18 2DC Water pressure hysteresis bar OEM 0 2 19 2DD Blocking pressure min bar OEM 0 5 20 2DE Blocking pre...

Страница 32: ...r operation summer kick sec OEM 10 43 2IA Ignition 0 Internal 1 Internal External 2 External OEM 2 2 2 2 2 2 44 2KM Step modulation 0 off 1 increasing 2 increasing and decreasing HF 1 45 2LA Effect of...

Страница 33: ...nsor attached OEM ON 17 2DB Water pressure warning bar OEM 1 18 2DC Water pressure hysteresis bar OEM 0 2 19 2DD Blocking pressure min bar OEM 0 5 20 2DE Blocking pressure min hysteresis bar OEM 0 2 2...

Страница 34: ...Summer operation summer kick sec OEM 10 43 2IA Ignition 0 Internal 1 Internal External 2 External OEM 2 44 2KM Step modulation 0 off 1 increasing 2 increasing and decreasing HF 1 45 2LA Effect of the...

Страница 35: ...ter pressure sensor attached OEM ON 17 2DB 32785 Water pressure warning bar OEM 1 18 2DC 32786 Water pressure hysteresis bar OEM 0 2 19 2DD 32787 Blocking pressure min bar OEM 0 5 20 2DE 32788 Blockin...

Страница 36: ...n HF 5 42 2HD 32810 Summer operation summer kick sec OEM 10 43 2IA 32811 Ignition 0 Internal 1 Internal External 2 External OEM 2 44 2KM 32812 Step modulation 0 off 1 increasing 2 increasing and decre...

Страница 37: ...4 Water pressure sensor attached OEM ON 17 2DB 32785 Water pressure warning bar OEM 1 18 2DC 32786 Water pressure hysteresis bar OEM 0 2 19 2DD 32787 Blocking pressure min bar OEM 0 5 20 2DE 32788 Blo...

Страница 38: ...ailable OEM ON 41 2HA 32809 Afterrun heating pump or shut off valve min HF 5 42 2HD 32810 Summer operation summer kick sec OEM 10 43 2IA 32811 Ignition 0 Internal 1 Internal External 2 External OEM 2...

Страница 39: ...OEM 100 15 2CA Gas pressure switch attached OEM ON 16 2DA Water pressure sensor attached OEM ON 17 2DB Water pressure warning bar OEM 1 18 2DC Water pressure hysteresis bar OEM 0 2 19 2DD Blocking pr...

Страница 40: ...OEM 3 38 2FU Fan speed at boiler freeze protection min 1 OEM 3700 3100 4200 39 2GA Waiting time after opening main gas valve or activation of heating room fan min OEM 0 40 2GB External main gas valve...

Страница 41: ...41 4 205 503 14...

Страница 42: ...Conservation of Energy Protection of the Environment...

Отзывы: