DRAIN JOINT INSTALLATION
NOTE:
The drain joint may differ slightly from the
diagram. For the drain joint with the seal, Fig. A,
first fit the seal onto the drain joint, then, insert the
drain joint into the base pan hole of outdoor unit.
Rotate it 90 degrees to secure it in place.
To install drain joint as shown in Fig. B, insert the
drain joint into the base pan hole of outdoor unit
until it remains fixed with a clicking sound. Connect
the drain joint with an extension drain hose (Locally
purchased), in case of water draining off the
outdoor unit during the heating or cooling mode.
REFRIGERANT PIPE CONNECTION
Flaring
1. Cut a pipe with a pipe cutter.
2.Remove flare nuts attached to the indoor and
out door units. Slide them over the end of the
pipes after removing burs from the pipes, and
flare the pipe.
3.Firmly hold copper pipe in a die in the
dimensions shown in the table below.
Tightening connection
Align pipes to be connected. Sufficiently tighten
the flare nut with fingers, and then tighten it
with a torque wrench as shown. Be careful -
excessive torque can break or damage the nut.
Use proper torque to ensure a good seal.
Do not over-tighten.
13
Outer
diam.
A(mm)
Max.
Min.
6.35mm
or 1/4 “
1.3
0.7
12.7mm
or 1/2 “
1.8
1.0
Outer diam.
Tightening
torque(N.cm)
Additional tightening
torque(N.cm)
6.35mm
or 1/4”
1500(153kgf.cm)
1600(163kgf.cm)
12.7mm
or 1/2”
3500(357kgf.cm
3600(367kgf.cm)