Copyright 2013 HotSpot Energy
SELECT THE BEST LOCATION
Indoor unit
There should not be any heat source or steam near the
unit. There should not be any obstacles blocking the air
circulation. Choose a location where air flow is good.
Choose a location where condensate drainage can be
easily done and where noise prevention is taken into
consideration. Do not install the unit near the en trance
or exit of the room. Ensure the clearances indicated by
arrows, from the wall, ceiling, fence or other obstacles.
See figure 1. There should not be any direct sunlight on
the indoor unit. If unavoidable, sunlight prevention
should be taken into consideration.
Outdoor unit
If an awning is built over the unit to prevent direct
sunlight or rain, be careful that heat radiation from the
condenser is not obstructed. There should not be any
animals or plants near the unit which could be affected
by hot air discharged. Ensure the clearances indicated
by arrows, from the wall, ceiling, fence or other
obstacles. See figure 2
Do not place any obstacles on the unit that may
interfere with the discharged air flow.
Placement of the
outdoor unit
Anchor the outdoor unit with a bolt and nut 10 or 8
tightly and horizontally on a concrete or rigid mount.
NOTE:
Install the outdoor unit according to the
dimension as indicated below:
Outdoor Unit Dimensions
(760 x 590 x 285) mm
Figure 2
1
Installation Plate
1
2
Clip Anchor
5-8
Depending
on the model
3
Self-tapping Screw AST 3.9 x 25
5-8
Depending
on the model
4
Seal
1
5
Drain Joint(For cooling & heating models
only
)
1
6
Line Set
Liquid
side
6.35 mm
1/4 “
Parts you must
purchase.
Gas Side
9.52 mm
1/2 “
Parts you must
purchase.
7
Control
Cable
Refer to page 11 for
control cable details
Parts you must
purchase.
8
Remote controller
1
9
Self-tapping Screw B ST2.9x10
2
Optional Parts
1
0
Remote controller holder
1
Optional Parts
6