30
Problem
Possible Cause
Remedy
d) Compressor Relay
1. Defective; contacts
welded.
1. Replace.
e) Control Board
1. Defective.
1. Replace.
[8] Evaporator does
not defrost
completely.
a) Defrost Thermistor
1. Defective.
1. Check and replace.
b) Defrost
1. Not enough defrosts
occurring per day.
Operation in humid
conditions.
1. Factory default is once
every 6 hours. If coil is
frosting too much, can
shorten defrost interval.
c) Defrost Heaters
1. Defective.
1. Replace heaters.
d) Safety Defrost
Thermostat
1. Defective, turning off
heaters prematurely,
or open.
1. Replace safety defrost
thermostat.
e) Defrost Heater Thermal
Fuse
1. Blown.
1. Determine why fuse blew.
Replace fuse.
f) Evaporator Shroud
Heater
1. Defective and causing
freeze-up of drain to
drain tank.
1. Replace evaporator
shroud.
[9] Defrost cycle
lasts too long.
a) Defrost Thermistor
1. Defective.
1. Replace.
b) Control Board
1. Defective.
1. Replace.
c) Defrost
1. Not enough defrosts
occurring per day.
Operation in humid
conditions.
1. Factory default is once
every 6 hours. If coil is
frosting too much, can
shorten defrost interval.
d) Defrost Heaters
1. Defective.
1. Replace heaters.
e) Safety Defrost
Thermostat
1. Defective, turning off
heaters prematurely,
or open.
1. Replace safety defrost
thermostat.
[10]Condensate
water overflow.
a) Cabinet Contents
1. Loading of large
volumes of warm,
moist, uncovered
product.
1. Cover product with plastic
wrap.
b) Location of Unit
1. Unit located near high
humidity source such
as fryer, steamer, etc.
1. Relocate.
c) Seals
1. Poor sealing around
evaporator, door
gaskets.
1. Adjust or replace.
d) Environment
1. Extreme environment
and door-opening
conditions.
1. Adjust conditions.
e) Primary Drain Tank
Thermostat
1. Defective, turning off
heater prematurely, or
open.
1. Replace primary drain
tank thermostat.
f) Safety Drain Tank
Thermostat
1. Defective, turning off
heater prematurely, or
open.
1. Replace safety drain tank
thermostat.
g) Drain Tank Thermal
Fuse
1. Blown.
1. Determine why fuse blew.
Replace fuse.
h) Drain Tank Heater
1. Defective.
1. Replace heater.