3. Cabinet Temperature Correction (calibration factor)
In cases where there is a discrepancy between the actual cabinet center temperature
and the displayed temperature for a particular model, a calibration factor is used to
correct the displayed temperature.
WARNING
This unit has been factory tested with the default settings listed. Avoid using
this function except to confirm that the setting is correct. If set incorrectly, the
display could show an acceptable temperature even though the temperature is
out of the proper range. This value should only be changed after consulting with
the factory.
To view the current value, follow the steps below.
1) Turn the power on while pressing the
up button. The current correction calibration
factor will be shown. If "18" is displayed, the value is 1.8°F (1.0°C). See the table below
for the default values.
Setting Range
Default
Refrigerator
Freezer
Cabinet Temperature Correction
(calibration factor)
-9.0 to 9.0°F in 0.9°F increments
(-5.0 to 5.0°C in 0.5°C increments)
18 (1.8°F)
(10 (1.0°C))
36 (3.6°F)
(20 (2.0°C))
2) If it is determined through discussion with the factory that the setting needs to be
changed, press the
up or
down button to increase or decrease the value.
3) Press the
button to save the new value.
4) Turn the power off and then back on. The unit will start running with the new value.
[Example]
When the average cabinet temperature is
approximately 5.4°F (3.0°C) higher than the thermistor
detected temperature, change the correction
calibration factor to 5.4°F (3.0°C).
E. Perimeter Frame Heater
This unit is equipped with a perimeter frame heater. This helps prevent the formation of
condensate on the front frame of the unit under high humidity conditions. Draw is 0.3A.
A backup perimeter frame heater has been prerouted in the unit.