background image

                 

26 

 

HOSHIZAKI EUROPE 
B.V.

 

 

 

  

PREMIER 

K W80 

PREMIER 

KG W80 

PREMIER 

M W80 

PREMIER  

F W80 

P. 

CODE 

DESCRIPTION 

VALUE 

VALUE 

VALUE 

VALUE 

SP  

Set point 

-20 

CA1 

cabinet probe offset  

CA2 

evaporator probe offset 

CA3 

Auxillary probe offset 

P0 

probe type  

P1 

enable °C decimal point 

P2 

temperature unit of measurement 

P3 

Evaporator probe function 

P4 

configurable input function 

P5 

value displayed 

P7 

inlet air weight for calculated product temperature 

50 

50 

50 

50 

P8 

display refresh time 

r0 

setpoint differential  

r1 

minimum setpoint 

-5 

-25 

r2 

maximum setpoint 

12 

12 

12 

-5 

r3 

enable setpoint block 

r4 

setpoint offset in energy saving 

r5 

cooling or heating operation  

r6 

setpoint offset in overcooling/overheating 

r7 

Overcooling/overheating duration 

r12 

position of the r0 differential  

C0 

compressor on delay after power-on 

C1 

delay between 2 compressor switch-ons 

C2 

compressor off minimum time 

C3 

compressor on minimum time  

C4 

compressor off time during cabinet probe alarm 

C5 

compressor on time during cabinet probe alarm 

C6 

threshold for high condensation warning 

60 

60 

60 

60 

C7 

threshold for high condensation alarm 

65 

65 

65 

100 

C8 

high condensation alarm delay 

C10 

compressor hours for service 

C11 

compressor 2 on delay 

10 

10 

10 

10 

d00 

enable double defrost 

d01 

temperature for defrost B activation 

d0 

automatic defrost interval 

d0b 

automatic defrost interval for B 

d1 

defrost type 

d1b 

defrost type for B 

d2 

threshold for defrost end 

d2b 

threshold for defrost end for B 

d3 

defrost duration 

60 

60 

60 

60 

d3b 

defrost duration for B 

60 

60 

60 

60 

Содержание PREMIER 60

Страница 1: ...HOSHIZAKI SERVICE MANUAL PREMIER 70 PREMIER W80 PREMIER 60 As the user please use the operating instructions This service manual does not include operating instructions It is only intended for the se...

Страница 2: ...Electrical Connection 9 8 Instructions for Daily Use 9 9 Cleaning and Maintenance 10 10 Control Elements 12 11 Switching the Door Hinge Side 29 12 Removing and Reattaching the Evaporator Cover 32 13 M...

Страница 3: ...e Class Ambient Temperatures andHumidity 4 30 C with 55 RH 5 40 C with 40 RH The cabinet must be installed in a dry well ventilated room away from direct sunlight at a sufficient distance from radiato...

Страница 4: ...KI EUROPE B V Distance from walls and ceiling A gap of at least 500 mm must be kept between the top edge of the machine compartment and the ceiling and of at least 50 mm from walls furniture and other...

Страница 5: ...er air quantity can circulate between the cabinets As a result a minimum distance of 30 to 50mm must be kept between the cabinets depending on the temperature and airhumidity These gaps must not be se...

Страница 6: ...to allow the oil to collect inthe compressor Once the cabinet is on its back the transport pallet must be removed by the following order 1 2 3 2 pieces of long wooden pieces at the bottom of the palle...

Страница 7: ...e pallet are removed it means the cabinet is no longer connected to the pallet 10 11 12 With the help of a pallet truck or by means of 2 people the cabinet is first tilted to one side from the pallet...

Страница 8: ...his equipment is intended for the amount of condensation water that accumulates on average witha maximum of 72 door openings per day according toISO 22041 The actual amount of condensation water may v...

Страница 9: ...In order to achieve the necessary air circulation in the interior only store goods within the corresponding markings loading marks and on the shelves never on the floor or in front of the air outlets...

Страница 10: ...n the machine compartment Chemical agents other than neutral cleaner might cause damage to the interior and exterior surfaces Any remaining detergent will damage metal or plastic surfaces Use a soft c...

Страница 11: ...ters at least twice a month When clogged or when the temperature controller shows cH use warm water and a neutral cleaner to wash the filters Don t operate the unit with the air filters removed or the...

Страница 12: ...active Cabinet light on Cabinet light off cabinet light on by digital input Auxiliary function 1 on Auxiliary function 1 off auxiliary function 1 on by digital input auxiliary function 1 delay active...

Страница 13: ...Touch the DEFROST key for 2 sec If P3 1 default defrost is activated provided that the evaporator temperature is lower than the d2 threshold Cabinet light on off if u1c u5c 5 1 Touch the CABINET LIGH...

Страница 14: ...he compressor is on rhH High humidity function evaporator fan on 4 Touch the ON STAND BY key to exit the procedure or don t operate for 60 sec View delete HACCP alarm information not available in EVJ2...

Страница 15: ...urs if u1c u5c 1 rCH Delete compressor and second compressor functioning hours 3 Touch the SET key 4 Touch the UP and DOWN to set 149 to select rCH 5 Touch the SET key 6 Touch the ON STAND BY key to e...

Страница 16: ...SET key 4 Touch the ON STAND BY key to exit the procedure or don t operate for 60 sec SETTINGS Setting configuration parameters 1 Touch the SET key for 4 sec the display will show the label PA 2 Touch...

Страница 17: ...N key for 1 sec 2 Touch the UP or DOWN key within 15 sec to select a label rtc 3 Touch the SET key The display will show the label y followed by the last two figures of the year 4 Touch the UP or DOWN...

Страница 18: ...e label PA 2 Touch the SET key 3 Touch the UP or DOWN key within 15 sec to set 149 4 Touch the SET key or don t operate for 15 sec The display will show label dEF 5 Touch the SET key 6 Touch the UP or...

Страница 19: ...h a key check electrical connection COH High Condensation Warning automatic Check C6 CSd High Condensation Alarm manual switch the device off and on check C7 iA Multi Purpose input Alarm automatic Che...

Страница 20: ...offset in overcooling overheating 0 0 0 0 r7 Overcooling overheating duration 0 0 0 0 r12 position of the r0 differential 1 1 1 1 C0 compressor on delay after power on 0 0 0 0 C1 delay between 2 comp...

Страница 21: ...rature 2 2 2 2 d25 enable air out probe for defrost during evaporator probe alarm 0 0 0 0 d26 defrost interval during evaporator probe alarm 6 6 6 6 A0 select value for high low temperature alarms 0 0...

Страница 22: ...10 10 i5 multi purpose input function 8 8 8 8 i6 multi purpose input activation 0 0 0 0 i7 multi purpose input alarm delay 0 0 0 0 i8 number of multi purpose input activations for high pressure alarm...

Страница 23: ...heating 0 0 0 0 r7 Overcooling overheating duration 0 0 0 0 r12 position of the r0 differential 1 1 1 1 C0 compressor on delay after power on 0 0 0 0 C1 delay between 2 compressor switch ons 5 5 5 5 C...

Страница 24: ...enable air out probe for defrost during evaporator probe alarm 0 0 0 0 d26 defrost interval during evaporator probe alarm 6 6 6 6 A0 select value for high low temperature alarms 0 0 0 0 A1 threshold f...

Страница 25: ...10 10 i5 multi purpose input function 8 8 8 8 i6 multi purpose input activation 0 0 0 0 i7 multi purpose input alarm delay 0 0 0 0 i8 number of multi purpose input activations for high pressure alarm...

Страница 26: ...verheating 0 0 0 0 r7 Overcooling overheating duration 0 0 0 0 r12 position of the r0 differential 1 1 1 1 C0 compressor on delay after power on 0 0 0 0 C1 delay between 2 compressor switch ons 5 5 5...

Страница 27: ...or defrost during evaporator probe alarm 0 0 0 0 d26 defrost interval during evaporator probe alarm 6 6 6 6 A0 select value for high low temperature alarms 0 0 0 0 A1 threshold for low temperature ala...

Страница 28: ...function 8 8 8 8 i6 multi purpose input activation 0 0 0 0 i7 multi purpose input alarm delay 0 0 0 0 i8 number of multi purpose input activations for high pressure alarm 0 0 0 0 i9 reset counter time...

Страница 29: ...easons Otherwise there is a risk of injury and damage tothe cabinet Change from right to left The door is turned by 180 then the hinge brackets are moved diagonally rotated by 180 The door closer is m...

Страница 30: ...ge of the canopy 2 Fold the canopy upwards and secure it against folding back down using adhesive tape or similar Risk of injury 3 Open the door at an angle of around 120 4 Remove the screw from the d...

Страница 31: ...e former top edge to the intended top edge of the door 11 Place the door closer at the bottom left at an opening angle of 180 and put the bottom left corner of the door over the door closer with the r...

Страница 32: ...the belts that secure the evaporator box and carefully remove to avoid damage The Evaporator Box needs to be lifted carefully not damaging box Checking and Reattaching the Evaporator Box 2 O ring must...

Страница 33: ...Heater to prevent plastic surface from melting 7 Make sure the sensor is correctly positioned and drain path is checked 8 After fitting the evaporator box secure the belts and do not overtighten Make...

Страница 34: ...at could pose a threat to humans and the environment if proper disposal WEEE is not observed Products labelled with a crossed out bin symbol belong to this group of electrical and electronic component...

Страница 35: ...Hoshizaki Italia Italia TEL 39 348 3022156 commerciale hoshizaki it Hoshizaki Europe B V All other countries in Europe and Africa TEL 31 0 20 691 84 99 sales hoshizaki nl http hoshizaki europe com In...

Страница 36: ...nergy Consumption AEC kWh 341 27 451 51 341 27 1771 34 Net Volume for Compartment 1 Vn or Vn1 litre 475 475 475 475 Net Volume for Compartment 2 Vn2 litre Net Volume for Compartment 3 Vn3 litre Net Vo...

Страница 37: ...ergy Consumption AEC kWh 337 63 439 46 337 63 1777 55 Net Volume for Compartment 1 Vn or Vn1 litre 475 475 475 475 Net Volume for Compartment 2 Vn2 litre Net Volume for Compartment 3 Vn3 litre Net Vol...

Страница 38: ...rgy Consumption AEC kW h 286 53 373 4 286 53 1506 36 Net Volume for Compartment 1 Vn or Vn1 litre 335 335 335 335 Net Volume for Compartment 2 Vn2 litre Net Volume for Compartment 3 Vn3 litre Net Volu...

Страница 39: ...39 HOSHIZAKI EUROPE B V PREMIER K 70 PREMIER M 70 PREMIER F 70 17 Dimensions...

Страница 40: ...40 HOSHIZAKI EUROPE B V PREMIER KG 70...

Страница 41: ...41 HOSHIZAKI EUROPE B V PREMIER K W80 PREMIER M W80 PREMIER F W80...

Страница 42: ...42 HOSHIZAKI EUROPE B V PREMIER KG W80...

Страница 43: ...43 HOSHIZAKI EUROPE B V PREMIER K 60 PREMIER M 60 PREMIER F 60...

Страница 44: ...44 HOSHIZAKI EUROPE B V PREMIER KG 60...

Страница 45: ...45 HOSHIZAKI EUROPE B V ELECTRICAL WIRING DIAGRAM FOR CABINET REFRIGERATOR MODELS 18 Wiring Diagram...

Страница 46: ...46 HOSHIZAKI EUROPE B V ELECTRICAL WIRING DIAGRAM FOR CABINET FREEZER MODELS...

Страница 47: ...47 HOSHIZAKI EUROPE B V 19 Cooling Diagram...

Отзывы: