4. CONTROLLER
[a] SERVICING CONTROLLER
1) When receiving a service call, ask the user to turn off the power supply and turn it back
on after 30 seconds, while watching the unit. This will reset the controller, and in some
cases normal operation will resume.
2) Keep the following in mind when servicing the controller:
* Check that the unit has been earthed properly. If not, the controller will not work properly.
* To get static free, always touch the cabinet (earth) before servicing. Electrostatic
discharge will cause severe damage to the controller.
* The controller and thermistor can be replaced separately.
* Do not drop the controller on the floor.
* The thermistor and pressure switch leads have a thin coating and are potentially
breakable. Do not tension the leads.
* The connectors must not be subjected to tension to prevent disconnection or breakage.
After servicing the controller, check for disconnected connectors.
* The thermistor is provided with single-wire leads. Do not bend or stretch them.
* Do not pinch or weigh down the thermistor and thermistor leads. The coatings may be
broken, resulting in a short circuit.
Содержание HFE-127MA-CHD
Страница 7: ...3 2 DIMENSIONS SPECIFICATIONS Representative standard models only a HRE 77MA CHD Model Code R262 C501 ...
Страница 8: ...4 b HRE 127MA CHD Model Code R263 C501 参考図 ホシザキ電機 2013 09 16 ...
Страница 9: ...5 c HRE 147MA CHD Model Code R264 C501 ...
Страница 10: ...6 d HRE 187MA CHD Model Code R265 C501 ...
Страница 11: ...7 e HFE 77MA CHD Model Code R266 C501 ...
Страница 12: ...8 f HFE 127MA CHD Model Code R267 C501 ...
Страница 13: ...9 g HFE 147MA CHD Model Code R268 C501 ...
Страница 14: ...10 h HFE 187MA CHD Model Code R269 501 ...
Страница 15: ...11 i HRFE 77MA CHD Model Code R281 C501 ...
Страница 16: ...12 j HRFE 127MAF CHD Model Code R282 C501 ...
Страница 17: ...13 k HRFE 147MAF CHD Model Code R283 C501 ...
Страница 18: ...14 l HRFE 187MAF CHD Model Code R284 C501 ...
Страница 20: ...16 d HFE 77MA CHD Model Code R266 C501 c HRE 187MA CHD Model Code R265 C501 ...
Страница 21: ...17 e HFE 127MA CHD Model Code R267 C501 HFE 147MA CHD Model Code R268 C501 f HFE 187MA CHD Model Code R269 501 ...
Страница 22: ...18 g HRFE 77MA CHD Model Code R281 C501 ...
Страница 23: ...19 h HRFE 127MAF CHD Model Code R282 C501 HRFE 147MAF CHD Model Code R283 C501 ...
Страница 24: ...20 i HRFE 187MAF CHD Model Code R284 C501 ...
Страница 26: ...22 k HRE 127MA CHD Model Code R263 C571 HRE 147MA CHD Model Code R264 C571 ...
Страница 27: ...23 l HRE 187MA CHD Model Code R265 C571 ...
Страница 28: ...24 m HFE 77MA CHD Model Code R266 C571 ...
Страница 29: ...25 n HFE 127MA CHD Model Code R267 C571 HFE 147MA CHD Model Code R268 C571 ...
Страница 30: ...26 o HFE 187MA CHD Model Code R269 C571 ...
Страница 57: ...53 HRFE 77MA refrigerator Defrost Thermistor Interior Thermistor ...