7. REMOVAL AND REPLACEMENT OF CONDENSING PRESSURE
REGULATOR (C.P.R.) - REMOTE AIR-COOLED MODELS ONLY
IMPORTANT
Always install a new Drier every time the sealed refrigeration system is
opened. Do not replace the Drier until after all other repairs or replacements
have been made.
1) Turn off the power supply.
2) Remove the panels from the remote condenser unit.
3) Recover the refrigerant and store it in an approved container.
4) Remove the C.P.R. using brazing equipment.
6) Braze the new C.P.R. with nitrogen gas flowing at the pressure of 3 - 4 PSIG.
WARNING
Always protect the valve body by using a damp cloth to prevent the valve
from overheating. Do not braze with the valve body exceeding 250°F.
7) Install the new Drier in the icemaker.
8) Check for leaks using nitrogen gas (140 PSIG) and soap bubbles.
9) Evacuate the system. Charge
it with refrigerant. See the
label on the Control Box in
the icemaker.
9) Replace the panels in their
correct position.
10) Turn on the power supply
Содержание F-2000MLH
Страница 13: ...13 2 CONDENSER UNIT URC 20F...
Страница 15: ...15 II GENERAL INFORMATION 1 CONSTRUCTION F 2000MWH C...
Страница 16: ...16 F 2000MRH C F 2000MRH3 C...
Страница 17: ...17 F 2000MLH C...
Страница 19: ...19 F 2000MRH3 C...
Страница 20: ...20 F 2000MLH C...
Страница 21: ...21 III TECHNICAL INFORMATION 1 WATER CIRCUIT AND REFRIGERATION CIRCUIT F 2000MWH C...
Страница 22: ...22 F 2000MRH C F 2000MRH3 C...
Страница 23: ...23 F 2000MLH C...
Страница 24: ...24 2 WIRING DIAGRAMS F 2000MWH C...
Страница 25: ...25 F 2000MRH C...
Страница 26: ...26 F 2000MRH3 C...
Страница 27: ...27 F 2000MLH C...
Страница 29: ...29 b When Reservoir has been filled Gear Motor starts immediately...
Страница 30: ...30 c Compressor starts F 2000MLH C only two solenoid valves open about 60 sec after Gear Motor starts...
Страница 32: ...32 e Low Water Except Water cooled Model where Compressor will operate intermittently...
Страница 38: ...38...
Страница 68: ...68...