VI. REMOVAL AND REPLACEMENT OF COMPONENTS
1. SERVICE FOR REFRIGERANT LINES
[a] REFRIGERANT RECOVERY [EXCEPT F-2000MLH/-C]
The icemaker unit is provided with two Refrigerant Access Valves - one on the low-side
and one on the high-side line. Using proper refrigerant practices recover the refrigerant
from the Access Valves and store it in an approved container. Do not discharge the refrig-
erant into the atmosphere.
[b] REFRIGERANT RECOVERY [F-2000MLH/-C ONLY]
The refrigerant charge on the F-2000MLH/-C is provided from the external Compressor Rack
Assembly. In the event that service is required on the F-2000MLH/-C, close the Suction and
Liquid Line Shut-off Valves located at the rear of the unit. Attach the Service Manifold
Hoses to the high side, low side and Evaporator Pressure Regulator (E.P.R.) access ports
to purge or evacuate the unit. To recharge the system, simply open the Suction and Liquid
Line Shut-off Valves after evacuating the F-2000MLH/-C.
[c] EVACUATION AND RECHARGE [R-404A]
1) Attach Charging Hoses, a Service Manifold and a Vacuum Pump to the system. Be
sure to connect Charging Hoses to both High-side and Low-side Access Valves.
IMPORTANT
Ensure all components, fasteners and thumbscrews are securely in place
after the equipment is serviced.
IMPORTANT
1. The Polyolester (POE) oils used in R-404A units can absorb moisture
quickly. Therefore it is important to prevent moisture from entering the
system when replacing or servicing parts.
2. Always install a new filter drier every time the sealed refrigeration system
is opened.
3. Do not leave the system open for longer than 15 minutes when replacing or
servicing parts.
Содержание F-2000MLH
Страница 13: ...13 2 CONDENSER UNIT URC 20F...
Страница 15: ...15 II GENERAL INFORMATION 1 CONSTRUCTION F 2000MWH C...
Страница 16: ...16 F 2000MRH C F 2000MRH3 C...
Страница 17: ...17 F 2000MLH C...
Страница 19: ...19 F 2000MRH3 C...
Страница 20: ...20 F 2000MLH C...
Страница 21: ...21 III TECHNICAL INFORMATION 1 WATER CIRCUIT AND REFRIGERATION CIRCUIT F 2000MWH C...
Страница 22: ...22 F 2000MRH C F 2000MRH3 C...
Страница 23: ...23 F 2000MLH C...
Страница 24: ...24 2 WIRING DIAGRAMS F 2000MWH C...
Страница 25: ...25 F 2000MRH C...
Страница 26: ...26 F 2000MRH3 C...
Страница 27: ...27 F 2000MLH C...
Страница 29: ...29 b When Reservoir has been filled Gear Motor starts immediately...
Страница 30: ...30 c Compressor starts F 2000MLH C only two solenoid valves open about 60 sec after Gear Motor starts...
Страница 32: ...32 e Low Water Except Water cooled Model where Compressor will operate intermittently...
Страница 38: ...38...
Страница 68: ...68...