53
PROBLEM
POSSIBLE CAUSE
REMEDY
c) Gear Motor Protector
(Circuit Breaker)
1. Tripped.
1. Find out the cause, get rid
of it, and press Reset
Button on Circuit Breaker.
d) Gear Motor Relay
1. Coil winding opened.
1. Replace.
2. Bad contacts.
2. Check for continuity and
replace.
e) Control Timer
(Printed Circuit Board)
1. Broken.
1. Replace.
f) Gear Motor Protect
Relay
1. Coil winding opened.
1. Replace.
2. Bad contacts.
2. Check for continuity and
replace.
[4] Gear Motor starts,
but Compressor (for
Solenoid Valves) will
not start (open) or
operates (opens)
intermittently
a) Pressure Switch
[Except
F-2000MLH/-C]
1. Dirty Air Filter or
Condenser.
1. Clean.
2. Ambient or condenser
water temperature too
warm.
2. Get cooler.
3. Condenser water
pressure too low or
off. (Water-cooled
model only)
3. Check and get
recommended pressure.
4. Water Regulating
Valve set too high.
(Water-cooled model
only)
4. Adjust it lower.
5. Fan not rotating.
5. See "3. [1] a) Fan Motor."
6. Refrigerant
overcharged.
6. Recharge.
7. Refrigerant line or
components plugged.
7. Clean and replace drier.
8. Bad contacts.
8. Check for continuity and
replace.
9. Loose connections.
9. Tighten.
b)
1. Bad contacts.
1. Replace. Check for
continuity and replace.
2. Coil winding opened.
2. Replace Timer.
c)
1. Bad contacts.
1. Check for continuity and
replace.
2. Coil winding opened.
2. Replace.
3. Loose Connections.
3. Tighten.
d) Start Capacitor or Run
Capacitor [Except
three phase model and
F-2000MLH/-C]
1. Defective.
1. Replace.
X2 Relay on Control
Timer
Starter [Except three
phase model and
F-2000MLH/-C]
Содержание F-2000MLH
Страница 13: ...13 2 CONDENSER UNIT URC 20F...
Страница 15: ...15 II GENERAL INFORMATION 1 CONSTRUCTION F 2000MWH C...
Страница 16: ...16 F 2000MRH C F 2000MRH3 C...
Страница 17: ...17 F 2000MLH C...
Страница 19: ...19 F 2000MRH3 C...
Страница 20: ...20 F 2000MLH C...
Страница 21: ...21 III TECHNICAL INFORMATION 1 WATER CIRCUIT AND REFRIGERATION CIRCUIT F 2000MWH C...
Страница 22: ...22 F 2000MRH C F 2000MRH3 C...
Страница 23: ...23 F 2000MLH C...
Страница 24: ...24 2 WIRING DIAGRAMS F 2000MWH C...
Страница 25: ...25 F 2000MRH C...
Страница 26: ...26 F 2000MRH3 C...
Страница 27: ...27 F 2000MLH C...
Страница 29: ...29 b When Reservoir has been filled Gear Motor starts immediately...
Страница 30: ...30 c Compressor starts F 2000MLH C only two solenoid valves open about 60 sec after Gear Motor starts...
Страница 32: ...32 e Low Water Except Water cooled Model where Compressor will operate intermittently...
Страница 38: ...38...
Страница 68: ...68...