Table 6.3
–
%SR Registers
–
Master %SR Table
Register
Default I/O
Name
Description
Min-Max
Values
Program
(Read/Write)
Display
(Read/Write)
%SR149-150
Free-running 10kHz count: 1 count =
0.1ms (32-Bit DINT)
Read Only
Read Only
%SR151
Reserved
%SR152
RS-485 Termination
Read / Write
Read / Write
%SR152.1
MJ2 Termination
Enable
*Excludes RCC972
Read / Write
Read / Write
%SR152.2
MJ3 Termination Enable
*XL+ Only
RS485 Termination Enable
* X4 & X7 Only
Read / Write
Read / Write
%SR152.3*
MJ1 Termination Enable
*XL+, XLE, XLT, RCC2414 Only
Read / Write
Read / Write
%SR152.4*
MJ1 Biasing
*XL+ Only
CAN Termination Enable
*X4 & X7 Only
Read / Write
Read / Write
%SR153-163
Reserved
%SR164
FailSafe / Clone
%SR164.1
RS485 Port Biasing #1 (MJ1 or MJ2)
Read / Write
Read / Write
%SR164.2
RS485 Port Biasing #2 (MJ2 or MJ3)
Read / Write
Read / Write
%SR164.3
AUTO_RESTRD
Indicates Automatic Restore Operation
has been performed
Read Only
Read Only
%SR164.4
BCKUP_TAKN
Indicates Backup of Registers has been
taken
Read Only
Read Only
%SR164.5
EN_AUTO_RN
Enable AUTORUN
–
Sets “Enable
AutoRun” to “Yes” or “No”
Read / Write
Read / Write
%SR164.6
EN_AUTO_LD
Enable AUTOLOAD
–
Sets “Enable
AutoLoad” to “Yes” or “Not”
Read / Write
Read / Write
%SR164.7
STRT_BCKUP
Start Backup trigger bit
–
Setting TRUE
starts backup of all register data
Read / Write
Read / Write
%SR164.8
CLR_BACKUP
Clear Backup trigger bit
–
Setting TRUE
clears backup of all register data (if a
backup was done previously)
Read / Write
Read / Write
%SR164.9
MAKE_CLONE
MAKE_CLONE trigger bit = Setting
TRUE does a Load Clone (if a media
card is present)
Read / Write
Read / Write
%SR164.10
LOAD_CLONE
LOAD_CLONE trigger bit
–
Setting TRUE
does a LOAD CLONE (if a media card is
present that contains clone files)
Read / Write
Read / Write
%SR164.11
MK_CLN_FL
Make Clone Fail (This bit goes high
when Make/Create Clone fails)
Read / Write
Read / Write
%SR164.12
LD_CLN_FL
Load Clone Fail (This big goes high
when Load Clone fails)
Read / Write
Read / Write
%SR164.14
Set to 1 to restore data manually, and
this in turn sets %SR164.15 to 1.
Set to 0 to abort restore operation.
*RCC Units Only
Read / Write
Read / Write
%SR164.15
Set to 1 for manual restore of data.
Read / Write
Read / Write