background image

LMAN0073-01-EN

Hazardous Location Series

02/2021

 

 

Page 1 

 

ETG-HHR

HazLoc High Bay Round User Manual

 

GENERAL SAFETY INFORMATION

• To reduce the risk of death, personal injury or property damage from fire,

     electric shock, falling parts, cuts/abrasions and other hazards, please read     

     all warnings and instruc�ons included with and on the fixture box and all  

     fixture labels.

• Before installing, servicing, or performing rou�ne maintenance upon this  

     equipment, please follow these general precau�ons.

• Commercial installa�on, service and maintenance of luminaires should be 

     performed by a qualified, licensed electrician.

• 

DO NOT INSTALL DAMAGED PRODUCT!

• Make sure that the supply voltage is the same as the luminaire voltage.

• DO NOT install where the marked opera�ng temperatures exceed the 

     igni�on temperatures of the hazardous atmosphere.

• DO NOT operate in ambient temperatures above those indicated on the luminaire nameplate.

• All gasket seals must be clean and undamaged.

WARNING:

RISK OF ELECTRICAL SHOCK

• Luminaire shall have provision for connec�on to threaded rigid metal conduit or other wiring methods in

     accordance with Ar�cle 502 in the Na�onal Electrical Code, NFPA 70.

• Turn off electrical power at fuse or circuit breaker box before wiring fixture to the power supply.

• Turn off the power when you perform any maintenance.

• Verify that supply voltage is correct by comparing it with the luminaire label informa�on. 

• Make all electrical and grounded connec�ons in accordance with the Na�onal Electrical Code and 

     any applicable local code requirements and Hazloc requirements and make sure they are suitable for wiring system.

• All wiring connec�ons should be capped with UL approved wire connectors.

• Luminaire must be supplied by a wiring system with an equipment grounding conductor.

CAUTION:

RISK OF INJURY

• Tightly close when energized for safety

• Do not open the luminarie a�er installa�on

• Wear gloves and safety glasses at all �mes when removing luminaire from carton, installing, servicing or performing   

    maintenance.

• Avoid direct eye exposure to the light source while it is on.

• Properly handle small parts and destroy packing material, as these may be hazardous to children.

RISK OF FIRE

• Keep combus�ble and other materials that can burn away from 

     luminaire and lamp/lens. 

• MIN 90ºC SUPPLY CONDUCTORS.

Image is for iillustra�on purposes only. 

Your model may vary.

Содержание ETG-HHR

Страница 1: ...her wiring methods in accordance with Ar cle 502 in the Na onal Electrical Code NFPA 70 Turn off electrical power at fuse or circuit breaker box before wiring fixture to the power supply Turn off the power when you perform any maintenance Verify that supply voltage is correct by comparing it with the luminaire label informa on Make all electrical and grounded connec ons in accordance with the Na onal...

Страница 2: ...o suitable conduit 3 Inset the wire from outside through the conduit and the entry hole of Tank then connect to Terminal Block 4 Introduce the wires of branch circuit as following Black wiring connects to Line White wiring connects to Neutral Green wiring connects to Ground 5 Re a ach the Tank Cover and ghten it by eight M6 hexagon bolts of Tank Cover with torque value 6 N m 6 Check the ghtness of...

Страница 3: ...ket Step 1 Secure the bracket and hood with 4 M10 expansion bolts not provided directly to a structural member make sure the hinge is located as marked See Figure 1a Adjust the angle 6x15 of the bracket and fix the posi on with M5 screws provided Step 2 Hang the fixture onto the hinge hook of the hood Connect supply wires to luminaire wire leads or Wago connectors Step 3 Close driver housing making ...

Страница 4: ...he M5 set screw Make sure the gasket of the adapter is properly inserted into the slot Step 2 Hang the hood onto the adapter align as marked Step 3 Rotate the hood clockwise and secure the adapter with M5 screws provided to 5 N m Step 4 Hang the fixture onto the hinge hook of the hood Connect supply wires to luminaire wire leads or Wago connectors Step 5 Close driver housing making sure that all wi...

Страница 5: ...ot Step 3 Hang the hood onto the adapter align as marked Step 4 Rotate the hood clockwise and secure the adapter with M5 screws provided to 5 N m Step 5 Hang the fixture onto the hinge hook of the hood and Connect supply wires to luminaire wire leads or Wago connectors Step 6 Close driver housing making sure that all wires are safely inside driver Tighten three cap ve closing screw M6 to 6 N m Note...

Страница 6: ...all parts are properly assembled Electrically check to make sure that all connec ons are clean and ght NPT Assembly Instruc ons Step 1 Inspect port and fi ng to ensure that both are free of contaminants and excessive burrs and nicks Step 2 Apply a stripe of an anaerobic liquid pipe sealant around the male threads leaving the first two threads uncovered If no liquid sealant is available wrap Teflon ta...