XNX Universal Transmitter
Section 3 - Calibration
94
3.2.4 Zero and Span Calibration of XNX EC Hydrogen
Sulfide (
H
2
S) Sensors
Caution:
Before initial calibration, allow the sensor to stabilize for 30 minutes
after applying power. When in zero and span calibration modes, the current
output from the sensor is inhibited (default 2mA) to avoid false alarms.
Caution:
Recalibrate if the temperature of local environment has varied by
more than ±15°C from the temperature of calibration.
Hydrogen Sulfide sensors can be affected by extreme humidity
changes� A sudden increase in ambient humidity can result in a
short-term positive drift in the instrument’s reading� A sudden
decrease in ambient humidity can result in a short-term negative
drift in the instrument’s reading� These are most likely to be
noticed during calibration with dry or cylinder gas�
When calibrating hydrogen sulfide cartridges, the following
should be taken into account while following the procedure in
Section 3�2�2
�
1� To zero the sensor, use a compressed gas cylinder of
20�9%Vol oxygen (not nitrogen)� Do not use background
air�
If a span calibration is to be performed, the span calibration gas
should be applied to the sensor immediately after the zeroing
procedure� Do not allow the sensor to return to ambient air
conditions�
Warning:
Long-term exposure (> 20 minutes) to concentrations exceediing the
full-scale range of the sensor can cause it to lose sensitivity. The ouput of the
sensor may then decrease in value even though high levels of toxic gas are still
present. Before re-calibrating the transmitter, verify the absence of gas.
3.2.5 705/705HT Calibrating
For complete calibration and configuration information, see the
Type 705 Operating Instructions (P/N: 00705M5002)�
3.2.6 Sensepoint/Sensepoint HT Calibrating
For complete calibration and configuration information, see the
Sieger Sensepoint Technical Handbook (P/N: 2106M0502)�
3.2.7 Calibrating the Searchpoint Optima Plus
Complete calibration and configuration information can be
found in the Searchpoint Optima Plus Operating Instructions
(P/N:2108M0501)� If properly installed and maintained, the
Searchpoint Optima Plus sensor will not require routine
calibration� This is due to the inherent stability of the IR
absorption process and the unit’s fully compensated optical
configuration�
1� From the Calibration menu, select the Gas Calibration option�
Figure 204. Calibration menu
Содержание XNX
Страница 1: ...Technical Manual XNXTM Universal Transmitter ...
Страница 2: ......
Страница 6: ...XNX Universal Transmitter Table of Contents 4 Table of Contents ...
Страница 11: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 9 1 Introduction ...
Страница 29: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 27 2 Installation and Operation ...
Страница 91: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 89 3 Calibration ...
Страница 104: ...XNX Universal Transmitter Section 3 Calibration 102 ...
Страница 105: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 103 4 Maintenance ...
Страница 109: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 107 5 Warnings and Faults ...
Страница 128: ...XNX Universal Transmitter Section 5 Warnings Faults 126 ...
Страница 129: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 127 6 Specifications ...
Страница 152: ...XNX Universal Transmitter Section 6 Specifications 150 Figure 232 XNX BT Configuration ...
Страница 161: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 159 7 Control Drawings ...
Страница 162: ...XNX Universal Transmitter Section 7 Control Drawings 160 7 1 XNX UL INMETRO ...
Страница 163: ...XNX Universal Transmitter Section 7 Control Drawings 161 ...
Страница 164: ...XNX Universal Transmitter Section 7 Control Drawings 162 ...
Страница 165: ...XNX Universal Transmitter Section 7 Control Drawings 163 7 2 XNX UL CSA FM ...
Страница 166: ...XNX Universal Transmitter Section 7 Control Drawings 164 ...
Страница 167: ...XNX Universal Transmitter Section 7 Control Drawings 165 ...
Страница 169: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 167 Appendix A HART Protocol ...
Страница 185: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 183 Appendix B Modbus Protocol ...
Страница 192: ...XNX Universal Transmitter Appendix B Modbus Protocol 190 ...
Страница 193: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 191 Appendix C Warranty ...
Страница 195: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 193 Index ...
Страница 199: ......