XNX Universal Transmitter
Section 6 - Specifications
132
6.2.3 EC Sensor Performance Data, DEKRA EXAM verified (see Section 6.3)
Gas
Cartridge P/N
Selectable Full
Scale Range (Dis-
play and 4-20mA
Full Scale)
Default
Range
Range
Incre-
ments
Lower
Alarm
Limit
Lower
Detection
Limit
Zero
Variation
Selectable
Cal Gas
Range
Default Cal
Point
Response
Time (T50)
(sec)
T90 Response
T10 Recovery
Time (sec)
Accuracy1
Operating Temperature
Operating Humidity
Min
Max
Min
Max
O
2
Oxygen
XNXXSO1SS
n/a
25.0 %Vol
n/a
5.0%Vol
3.5 %Vol
n/a
20.9 %Vol
(fixed)
20.9 %Vol
T20 <10
<30
<+/-0.6 %Vol
-30°C / -34°F
55°C /131°F
15% RH
90% RH
H
2
S
Hydrogen
Sulfide
XNXXSH1SS
10.0 to 50.0 ppm
15.0 ppm
0.1ppm
3.0 ppm
1.0 ppm
2.0 ppm
30 to 70%
of the
selected full
scale range
10 ppm
<20
<30
<+/-0.3 ppm
-40°C / -40°F
55°C / 131°F
15% RH
90% RH
H
2
S (High)
Hydrogen
Sulfide
XNXXSH2SS
50 to 500 ppm
100 ppm
10 ppm
5 ppm
1 ppm
2 ppm
50 ppm
<20
<30
<+/-5 ppm
-40°C / -40°F
55°C / 131°F
15% RH
90% RH
CO
Carbon
Monoxide
XNXXSC1SS
100 to 500 ppm
300 ppm
100 ppm
15 ppm
5 ppm
10 ppm
100 ppm
<15
<30
<+/-2 ppm
-40°C / -40°F
55°C / 131°F
15% RH
90% RH
FOOTNOTE:
1� Accuracy of reading at default Alarm 1 concentration (typically 10% FS or defined minimum alarm level setting, whichever is greater) when operated at default full scale�
NOTES:
• Sensor drift between LDL and negative drift fault limits (typcially > negative zero variation) appear as 0 on the display and outputs of the device�
• Long-term drift: XNXXSC1SS <5%/year, XNXXSO1SS <4%/year, XNXXSH1SS and XNXXSH2SS <2%/month�
• Performance figures are measured by test units calibrated at 50% of full scale, at ambient conditions of 20°C, 50% RH, with the EC weatherproof cover attached�
• Operating the XNX EC sensor at extended temperature ranges for a prolonged time period exceeding 12 hours may cause deterioration in sensor performance and shorten
sensor life� Extended temperature ranges for XNX EC sensor cartridges are -40°C to -20°C�
• Barometric pressure effects on the O
2
sensor: The output from the O
2
sensor has pressure effects of <0�1% change of output per % change in pressure� When the barometric
pressure changes by ±20%, the output from the O
2
sensor changes <±0�4%Vol� However, the oxygen sensor shows transient behavior when subjected to a rapid change in
ambient pressure due to either weather or altitude� For example, a 10KPa instantaneous positive pressure step change may cause an overscale alarm condition for a period
of about 12 seconds�
• Response times may increase at lower temperatures�
• Contact Honeywell Analytics for any additional data or details�
Содержание XNX
Страница 1: ...Technical Manual XNXTM Universal Transmitter ...
Страница 2: ......
Страница 6: ...XNX Universal Transmitter Table of Contents 4 Table of Contents ...
Страница 11: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 9 1 Introduction ...
Страница 29: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 27 2 Installation and Operation ...
Страница 91: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 89 3 Calibration ...
Страница 104: ...XNX Universal Transmitter Section 3 Calibration 102 ...
Страница 105: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 103 4 Maintenance ...
Страница 109: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 107 5 Warnings and Faults ...
Страница 128: ...XNX Universal Transmitter Section 5 Warnings Faults 126 ...
Страница 129: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 127 6 Specifications ...
Страница 152: ...XNX Universal Transmitter Section 6 Specifications 150 Figure 232 XNX BT Configuration ...
Страница 161: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 159 7 Control Drawings ...
Страница 162: ...XNX Universal Transmitter Section 7 Control Drawings 160 7 1 XNX UL INMETRO ...
Страница 163: ...XNX Universal Transmitter Section 7 Control Drawings 161 ...
Страница 164: ...XNX Universal Transmitter Section 7 Control Drawings 162 ...
Страница 165: ...XNX Universal Transmitter Section 7 Control Drawings 163 7 2 XNX UL CSA FM ...
Страница 166: ...XNX Universal Transmitter Section 7 Control Drawings 164 ...
Страница 167: ...XNX Universal Transmitter Section 7 Control Drawings 165 ...
Страница 169: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 167 Appendix A HART Protocol ...
Страница 185: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 183 Appendix B Modbus Protocol ...
Страница 192: ...XNX Universal Transmitter Appendix B Modbus Protocol 190 ...
Страница 193: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 191 Appendix C Warranty ...
Страница 195: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 193 Index ...
Страница 199: ......