XNX Universal Transmitter
Section 5 - Warnings/Faults
117
Fault
Description
Appli-
cable
Sensors
Latching / Non-
Latching
Frequency of
Diagnostic
Event History Data
Action For Resolution
F149
Internal 4-20 mA
monitoring circuit
communication
failure
All
Non-latching
3�366 seconds
0
Contact Honeywell Analytics’ Service Department�
F150
mA Output Monitor
Communications
Watchdog Error
All
Non-latching
138 us
Communication error
count
Contact Honeywell Analytics’ Service Department�
F151
Sensor Module
Type Changed
ECC
Non-latching
2 seconds
Module type: 0=None,
1=ECC, 2=mV,
3=Excel, 4=Optima,
5=Generic mA
For ECC: Perform Accept New Sensor function, if problem persists
contact Honeywell Analytics’ Service Department� For others, contact
Honeywell Analytics’ Service Department�
F152
Option Module
Configuration Error
All
Latching
Only at powerup
or every 125 ms
when no option
board detected
Option module ID:
0=None, 1=Founda-
tion Fieldbus, 2=Mod-
bus, 3=Relay
Confirm option properly installed, reconfigure unit�
F153
Signal/Data mis-
match error on IR
personality
Optima,
Excel
Non-latching
2 seconds
Digital sensor reading
Check wiring to Optima/Excel� In particular, check the white wire be-
tween XnX and Optima/Excel� Note: power must be cycled to reset F153
after correcting the cause�
F154
mA Input Diagnos-
tic Failure
Optima,
Excel
Latching
5 minutes after
power up and
then every 8
hours
Input mA
Contact Honeywell Analytics’ Service Department�
F155
Generic mA Sensor
Type Error
Generic
mA
Non-latching
2 seconds
Input mA
Indicates that mA input from sensor is less than 3 mA� Check wiring
between XNX and sensor� Also check the switches S3 and S4 are set
correctly� If the switch settings need to be change, power down the XNX
before changing the switch settings� If wiring and switches are okay,
replace sensor�
F156
mV Current Control
Failure
mV
Non-latching
Main loop x16
constant current A/D
input mV
Check that correct mV sensor type is selected� Check wiring between
XNX and sensor� If sensor type and wiring are okay, replace sensor�
F157
Sensor Drift Fault
ECC, mV
Non-latching
2 seconds
Current baseline
Perform zero calibration� If problem persists, replace sensor�
F158
Sensor/Personal
-
ity Part Number
mismatch
All
Non-latching
"ECC & mV: main
loop x2;
Optima & Excel: 2
seconds"
Entire personality
part #
Check that installed option matches the option indicated in the XNX part
number, check wiring to Optima/Excel�
Содержание XNX
Страница 1: ...Technical Manual XNXTM Universal Transmitter ...
Страница 2: ......
Страница 6: ...XNX Universal Transmitter Table of Contents 4 Table of Contents ...
Страница 11: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 9 1 Introduction ...
Страница 29: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 27 2 Installation and Operation ...
Страница 91: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 89 3 Calibration ...
Страница 104: ...XNX Universal Transmitter Section 3 Calibration 102 ...
Страница 105: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 103 4 Maintenance ...
Страница 109: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 107 5 Warnings and Faults ...
Страница 128: ...XNX Universal Transmitter Section 5 Warnings Faults 126 ...
Страница 129: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 127 6 Specifications ...
Страница 152: ...XNX Universal Transmitter Section 6 Specifications 150 Figure 232 XNX BT Configuration ...
Страница 161: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 159 7 Control Drawings ...
Страница 162: ...XNX Universal Transmitter Section 7 Control Drawings 160 7 1 XNX UL INMETRO ...
Страница 163: ...XNX Universal Transmitter Section 7 Control Drawings 161 ...
Страница 164: ...XNX Universal Transmitter Section 7 Control Drawings 162 ...
Страница 165: ...XNX Universal Transmitter Section 7 Control Drawings 163 7 2 XNX UL CSA FM ...
Страница 166: ...XNX Universal Transmitter Section 7 Control Drawings 164 ...
Страница 167: ...XNX Universal Transmitter Section 7 Control Drawings 165 ...
Страница 169: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 167 Appendix A HART Protocol ...
Страница 185: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 183 Appendix B Modbus Protocol ...
Страница 192: ...XNX Universal Transmitter Appendix B Modbus Protocol 190 ...
Страница 193: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 191 Appendix C Warranty ...
Страница 195: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 193 Index ...
Страница 199: ......