background image

The W7620 Single  Zone Control System is Honeywell’s
new  line of single zone   control  products. The W7620,
can conveniently monitor and control  individual HVAC
zone equipment.

System features include CNAP (Control Network

Automation Protocol) communication, application

flexibility, DDC (Direct Digital Control), network
integration, easy installation and programming, and
increased  equipment reliability.

The basic  W7620  Single  Zone  Controller has built-in
capability to process I/O  (Input/Output) data, run DDC
programs, and communicate along with other devices  on
the CNAP  network.  See  W7620 family photo.

The  W7620  Single   Zone Controller is a DDC device.
DDC has a control loop which periodically updates the
outputs as a  function  of a  set of measured inputs and a
given set of algorithms.  The  advantages of DDC  are:

Control

The W7620 Single  Zone  Controller provides sophisticated

control loops for accurate control of single zone equipment 
that prevents  temperature  droop and provides greater
comfort  in the zone.

Maintainability

Use of a single programmed computer reduces
requirements for calibration checks because there are
fewer interconnected analog components. Periodic

recalibration is automatically performed.

Reliability

EEPROM (Electrically Erasable  Programmable Read
Only Memory) and EPROM  (Erasable   Programmable
Read Only Memory) hold the control  program  and
parameters eliminating the need  for a battery.

Communlcatlon

Networking controllers together on  a   RS-485   network
using  CNAP software  provides information for integration
of control functions, monitoring, trending, alarming, and
report generation.

The  W7620 Single  Zone  Controller can be applied in a
stand-alone environment with distributed zone control
and hard-wired time-of-day functionality  It can also be

applied as part of a networked  system via connection to

the RS-485 CNAP network. The CNAP network  enables

communication to multiple W7620  Zone  Controllers as

well as to other controllers,  such as the W7600  Control

Module, 47640 NIU  or a Q7650  PC Interface  Card in

a PC with ZM7603 Remote Monitoring software.  Refer
to the  ZM7601 Configuration  Tool/ZM7603 Remote

Monitoring software specification sheet,  Form  63-4272,
for a more detailed description.

Through the  CNAP  network, the controller can be
provided with information specific  to its controlled zone

only,  or with information necessary for a  group of zone

controllers.  ZM7601/ZM7603   software  can,  in  turn,  be
provided  with periodic information on  any controller data
for monitoring, data gathering, or report generating. See
Figure 1.

The  W7620  Zone Control System was designed for
application flexibility. Simply  by changing the  algorithm
which is stored in EBPROM and by determining  the  input

and output requirements, the same 

 

 

be applied in a variety of applications.

‘Ike W7620 Baseboard provides input dedicated to the
T7660 Space Temperature Sensor (space temperature,

remote setpoint,  bypass switch with LED feedback, and

CNAP communication connections). The baseboard  only
provides four SPST  (Single Pole, Single Throw)  relays.
A variety of small point, single zone  or heat pump
applications can be met by using only the W7620.

The  W7621 Input  Board  adds two resistive, one digital,
one AC input, and two voltage inputs that can be used

for a variety of inputs depending on application. One

W7621 input board can be  added  to the W7620  Zone

controller.

3

63-4224

Содержание W7620

Страница 1: ...e ad ditional input point expansion on one board of up to two resistive inputs two digital inputs two voltage inputs one dry contact one extended 24 Vac input q W7622 Expansion Output Point Boards provide ad ditional output point expansion on one board of up to three analog outputs three digital outputs 0 T7660 Space Temperature Sensor provides up to one space temperature input one space temperatu...

Страница 2: ... LIKE To COMMENT ON OUR PRODUCTS OR SERVICES PLEASE WRITEOR PHONE 1 YOUR LOCAL H O N E Y W E L L SALES OFFICE CHECK WHITE PAGES OF YOUR PHONE DIRECTORY ASK FOR THE RESIDENTIAL ANDBUILDING CONTROLSSALES REPRESENTATIVE 2 RESIDENTIAL AND BUILDING CONROLS CUSTOMER SERVICE HONEYWELL INC 1885 DOUGLAS DRIVE NORTH MINNEAPOLIS MINNESOTA 55422 612 542 7500 IN CANADA HONEYWELLLIMITED HONEYWELL LIMITEE 740 EL...

Страница 3: ...generation The W7620 Single Zone Controller can be applied in a stand alone environment with distributed zone control and hard wired time of day functionality It can also be applied as part of a networked system via connection to the RS 485 CNAP network The CNAP network enables communication to multiple W7620 Zone Controllers as well as to other controllers such as the W7600 Control Module 47640 N...

Страница 4: ...Figure 1 CNAP Network Diagram ...

Страница 5: ...oliig system to an occupied mode when the control system is in an unoccupied mode Also it can be used to initiate a continuous unoccupied period The LED indicates the override status These zone sensors arefurnishedwithanRJ11connectorforlocaloperation of an S7610 POT Portable Operator s Terminal See the T7660A D Space Temperature Sensors Information and Installation sheet Form 63 4219 for m o r e d...

Страница 6: ...Figure 3 POT Portable Operator s Terminal ...

Страница 7: ... is likely to cause interference in which case the user at his own expense will be required to take whatever measures necessary to correct the interference I surface before removing the W7621 or W7622 expansion board from the antistatic bag Failure to do so might damage the board I Mount the controller in a location that allows clearance for wiring servicing and removal of the cover 1 Remove the c...

Страница 8: ... Knockout for l 2 in conduit fittings h Double knockout for l 2 or 3 4 in conduit fittings Figure 4 W7620 Mounting STANDOFF HOLE PLASTIC STANDOFF 10 PIN CONNECTOR Figure 5 Mounting Additional Board 8 ...

Страница 9: ...ll controller models are furnished with a terminal arrangement similar to that shown in this figure Pull the pair of CNAP communication cables to each controller on the network and connect to the screw terminals marked CNAP Figure 6 I N O T E I Power Wire Lengths 1 Power requircmcnts limit 24 Vac power transmission distance The following data can be used in calculating load versus wire length Devi...

Страница 10: ... override on an output point to a desired value with the S7610 POT or ZM7601 ZM7603 software 2 Measure or observe the output condition e g fan turns on 3 If the output does not follow the command override condition isolate the problem by checking connections and measurements at the output destination as well as at the W7620 4 Clear the override condition Example The following procedure is for Fan ...

Страница 11: ...round Testing physical points requires either the actual sensor be at a known v a l u eor digital state or that a simulated known value or digital state be applied to the input point terminals In the case of physical output points the output condition of the controlled equipment must be known or the output terminals of the W7620 can be measured with an indicating device or meter The Hardware Confi...

Страница 12: ...arily provide a good ground The following provides grounding details 1 Earth ground one W7620 within a group of W7620s connected to a given transformer Connect the ground wire to the green ground screw on the W7620 chassis See Figure 7 connect the same side of the transformer secondary to the same terminal number on each W7620 2 Grounded Transformer Secondaries If the Transformer has a grounded se...

Страница 13: ...ee 24 Vac source indicating digital response to call from same transformer All three Inputs can be used separately or together to determine the final state of input Outputs Analog O IO Vdc 20 mA maximum Relay expansion 2 0 amp maximum running 7 5 amp In rush at 30 Vac 50 or 60 Hz Relay base 1 6 amp maximum running 7 5 amp In rush at 30 Vac 50 or 60 Hz Temperature Ratings Ambient 40 to 110 F 4 to 4...

Страница 14: ...bl Knockout for l 2 in conduit fittings Q Double knockout for 1 2 or 3 4 in conduit fittings Figure 8 W7620 Dimensions 14 63 4224 ...

Страница 15: ...Base Unit with cover Input Expansion Boards Use with W7459 Economizer Logic Module modulating spring Damper Actuator ...

Страница 16: ...td aar 18 mlnlstBr des Communlcstions du Canada Dear Customer Please send your comments and suggestions to We welcome your comments and suggestions for Improving Honeywell Inc this publication 8500 Bluewater N W Your assistance is greatly appreciated and will enable us to Albuquerque NM 87121 1958 provide better technical information for you ATTN Technical Editor HONEYWELL MINNEAPOLIS MN 55408 INT...