background image

When 

installing  

this product . . .

1. Read these instructions  carefully. Failure to follo

them could damage  the product  or cause  a

hazardous  condition.

2.

Check 

the ratings  given in the  SPECIFICATION:

section and on the  product to make sure that the

product is suitable for the  application.

3. The installer must  be  a  trained, experienced

service  or installation  technician.

4. After installation is complete, check system

operation  as provided in these instructions.

5. Verify that the  W7620s  are installed in accordan

with the job drawings  and these installation

procedures.

6.  Verify   that  the   T7660  Space  Temperature   Sensor

installed in  accordance with job  drawings  and  the

T7660 Specification Sheet (63-4219).

Disconnect power supply before beginning

installation  to prevent electrical shock and
equipment damage.

radiate radio  frequency energy.

not installed

and used in accordance with the instruction
manual, it may cause interference to radio
communications. Pursuant to FCC Rules,
Subpart J of Part 15, this equipment has
been tested and found to comply with the
limits for a Class  A computing device. These
limits are designed to provide reasonable
protection  against  interference when operating
in a commercial environment. Operating this

equipment in a residential environment is
likely to cause interference, in which case the
user at his own expense will be required to
take whatever measures necessary to correct

the interference.

I

surface-before removing  the W7621

or W7622

expansion board from the antistatic bag.
Failure to do so might damage the board.

I

Mount  the   controller   in a location that allows clearance

for wiring,  servicing  and removal of the  cover.

1. Remove the cover by loosening the two side

screws (Figure  4) and mount the  controller  in a

location appropriate to the equipment being

controlled.

2. Use No. 8 sheet metal screws  (obtain locally) to

secure the  controller  to the mounting  surface

through  the four  key holes  inside the 

3. Test  the   controller and equipment  operation.

4. Replace and  secure  the  controller  cover after

wiring  is complete.

Mountlng Additional Boards

To  install  additional input  or output expansion boards

(W7621  or W7622) which are not manufacturer  installed

on  the base board assembly (Figure 5) complete the

following:

1. Align the IO-pin connector (J4) or (J5)  on  the

baseboard with the  10-pin inverse connector  on

the input  board   (J15)  or output board (13).

2. Align  the white plastic standoff tab with the hole

located near the lo-pin  connector.

3. Lean the input  or output board in at  the base to

catch  the metal tab located  on  the bottom of the

controller.

4. Snap the board into place
5. Secure the board into place by applying and

tightening  the two board  screws   provided   with

each expansion  board.

7

63-4224

Содержание W7620

Страница 1: ...e ad ditional input point expansion on one board of up to two resistive inputs two digital inputs two voltage inputs one dry contact one extended 24 Vac input q W7622 Expansion Output Point Boards provide ad ditional output point expansion on one board of up to three analog outputs three digital outputs 0 T7660 Space Temperature Sensor provides up to one space temperature input one space temperatu...

Страница 2: ... LIKE To COMMENT ON OUR PRODUCTS OR SERVICES PLEASE WRITEOR PHONE 1 YOUR LOCAL H O N E Y W E L L SALES OFFICE CHECK WHITE PAGES OF YOUR PHONE DIRECTORY ASK FOR THE RESIDENTIAL ANDBUILDING CONTROLSSALES REPRESENTATIVE 2 RESIDENTIAL AND BUILDING CONROLS CUSTOMER SERVICE HONEYWELL INC 1885 DOUGLAS DRIVE NORTH MINNEAPOLIS MINNESOTA 55422 612 542 7500 IN CANADA HONEYWELLLIMITED HONEYWELL LIMITEE 740 EL...

Страница 3: ...generation The W7620 Single Zone Controller can be applied in a stand alone environment with distributed zone control and hard wired time of day functionality It can also be applied as part of a networked system via connection to the RS 485 CNAP network The CNAP network enables communication to multiple W7620 Zone Controllers as well as to other controllers such as the W7600 Control Module 47640 N...

Страница 4: ...Figure 1 CNAP Network Diagram ...

Страница 5: ...oliig system to an occupied mode when the control system is in an unoccupied mode Also it can be used to initiate a continuous unoccupied period The LED indicates the override status These zone sensors arefurnishedwithanRJ11connectorforlocaloperation of an S7610 POT Portable Operator s Terminal See the T7660A D Space Temperature Sensors Information and Installation sheet Form 63 4219 for m o r e d...

Страница 6: ...Figure 3 POT Portable Operator s Terminal ...

Страница 7: ... is likely to cause interference in which case the user at his own expense will be required to take whatever measures necessary to correct the interference I surface before removing the W7621 or W7622 expansion board from the antistatic bag Failure to do so might damage the board I Mount the controller in a location that allows clearance for wiring servicing and removal of the cover 1 Remove the c...

Страница 8: ... Knockout for l 2 in conduit fittings h Double knockout for l 2 or 3 4 in conduit fittings Figure 4 W7620 Mounting STANDOFF HOLE PLASTIC STANDOFF 10 PIN CONNECTOR Figure 5 Mounting Additional Board 8 ...

Страница 9: ...ll controller models are furnished with a terminal arrangement similar to that shown in this figure Pull the pair of CNAP communication cables to each controller on the network and connect to the screw terminals marked CNAP Figure 6 I N O T E I Power Wire Lengths 1 Power requircmcnts limit 24 Vac power transmission distance The following data can be used in calculating load versus wire length Devi...

Страница 10: ... override on an output point to a desired value with the S7610 POT or ZM7601 ZM7603 software 2 Measure or observe the output condition e g fan turns on 3 If the output does not follow the command override condition isolate the problem by checking connections and measurements at the output destination as well as at the W7620 4 Clear the override condition Example The following procedure is for Fan ...

Страница 11: ...round Testing physical points requires either the actual sensor be at a known v a l u eor digital state or that a simulated known value or digital state be applied to the input point terminals In the case of physical output points the output condition of the controlled equipment must be known or the output terminals of the W7620 can be measured with an indicating device or meter The Hardware Confi...

Страница 12: ...arily provide a good ground The following provides grounding details 1 Earth ground one W7620 within a group of W7620s connected to a given transformer Connect the ground wire to the green ground screw on the W7620 chassis See Figure 7 connect the same side of the transformer secondary to the same terminal number on each W7620 2 Grounded Transformer Secondaries If the Transformer has a grounded se...

Страница 13: ...ee 24 Vac source indicating digital response to call from same transformer All three Inputs can be used separately or together to determine the final state of input Outputs Analog O IO Vdc 20 mA maximum Relay expansion 2 0 amp maximum running 7 5 amp In rush at 30 Vac 50 or 60 Hz Relay base 1 6 amp maximum running 7 5 amp In rush at 30 Vac 50 or 60 Hz Temperature Ratings Ambient 40 to 110 F 4 to 4...

Страница 14: ...bl Knockout for l 2 in conduit fittings Q Double knockout for 1 2 or 3 4 in conduit fittings Figure 8 W7620 Dimensions 14 63 4224 ...

Страница 15: ...Base Unit with cover Input Expansion Boards Use with W7459 Economizer Logic Module modulating spring Damper Actuator ...

Страница 16: ...td aar 18 mlnlstBr des Communlcstions du Canada Dear Customer Please send your comments and suggestions to We welcome your comments and suggestions for Improving Honeywell Inc this publication 8500 Bluewater N W Your assistance is greatly appreciated and will enable us to Albuquerque NM 87121 1958 provide better technical information for you ATTN Technical Editor HONEYWELL MINNEAPOLIS MN 55408 INT...

Отзывы: