2. To disable a controller, remove both legs of I

or removing connections from Terminals TR

and TR earth-ground.

the AC power. Removing  only  one leg may

prevent other controllers on the same
transformer from communicating on the
CNAP network.

I

L

The  W7620  Zone Control System must be  earth-grounded
at each cluster of  W7620   controllers  (one  or  mote  W7620
controllers  powered by  a single 24  Vac  transformer). Use
No. 18 AWG or larger  copper  conductor  run  to a  known
earth-ground,  such  as  a  water  pipe driven into the earth

or the ground connection found within the power
distribution panel. The power distribution panel must  be
earth-grounded  per  National Electric Codes. Do not “se
the ductwork  or  the wiring conduit since these do not
necessarily provide  a good ground. The following
provides grounding  details:

1. Earth-ground one  W7620  within  a group of

W7620s   connected  to a given transformer.

Connect the ground  wire  to the green ground
screw  on the  W7620  chassis. See Figure 7.

connect the same side of the

transformer secondary to the same terminal

number on each  W7620.

2. Grounded   Transformer  Secondaries:  If the

Transformer  has  a grounded secondary,  it is
necessary  to identify the grounded  side. Use an
ohm  meter  to test for conductivity  between  one

side of the  transformer  and the suspected
grounding   plane  (usually the controller chassis).

If one side of the transformer is  grounded,

connect  the  grounded secondary  to the

earth-ground  connection on the  W7620   (TR
earth-ground).

to connect grounded secondary to

will cause damage to the

Tie each W7620  (using ground

screw) together in the cluster.

Earth-ground each cluster at some
accessible point that is a good
distribution ground.

Содержание W7620

Страница 1: ...e ad ditional input point expansion on one board of up to two resistive inputs two digital inputs two voltage inputs one dry contact one extended 24 Vac input q W7622 Expansion Output Point Boards provide ad ditional output point expansion on one board of up to three analog outputs three digital outputs 0 T7660 Space Temperature Sensor provides up to one space temperature input one space temperatu...

Страница 2: ... LIKE To COMMENT ON OUR PRODUCTS OR SERVICES PLEASE WRITEOR PHONE 1 YOUR LOCAL H O N E Y W E L L SALES OFFICE CHECK WHITE PAGES OF YOUR PHONE DIRECTORY ASK FOR THE RESIDENTIAL ANDBUILDING CONTROLSSALES REPRESENTATIVE 2 RESIDENTIAL AND BUILDING CONROLS CUSTOMER SERVICE HONEYWELL INC 1885 DOUGLAS DRIVE NORTH MINNEAPOLIS MINNESOTA 55422 612 542 7500 IN CANADA HONEYWELLLIMITED HONEYWELL LIMITEE 740 EL...

Страница 3: ...generation The W7620 Single Zone Controller can be applied in a stand alone environment with distributed zone control and hard wired time of day functionality It can also be applied as part of a networked system via connection to the RS 485 CNAP network The CNAP network enables communication to multiple W7620 Zone Controllers as well as to other controllers such as the W7600 Control Module 47640 N...

Страница 4: ...Figure 1 CNAP Network Diagram ...

Страница 5: ...oliig system to an occupied mode when the control system is in an unoccupied mode Also it can be used to initiate a continuous unoccupied period The LED indicates the override status These zone sensors arefurnishedwithanRJ11connectorforlocaloperation of an S7610 POT Portable Operator s Terminal See the T7660A D Space Temperature Sensors Information and Installation sheet Form 63 4219 for m o r e d...

Страница 6: ...Figure 3 POT Portable Operator s Terminal ...

Страница 7: ... is likely to cause interference in which case the user at his own expense will be required to take whatever measures necessary to correct the interference I surface before removing the W7621 or W7622 expansion board from the antistatic bag Failure to do so might damage the board I Mount the controller in a location that allows clearance for wiring servicing and removal of the cover 1 Remove the c...

Страница 8: ... Knockout for l 2 in conduit fittings h Double knockout for l 2 or 3 4 in conduit fittings Figure 4 W7620 Mounting STANDOFF HOLE PLASTIC STANDOFF 10 PIN CONNECTOR Figure 5 Mounting Additional Board 8 ...

Страница 9: ...ll controller models are furnished with a terminal arrangement similar to that shown in this figure Pull the pair of CNAP communication cables to each controller on the network and connect to the screw terminals marked CNAP Figure 6 I N O T E I Power Wire Lengths 1 Power requircmcnts limit 24 Vac power transmission distance The following data can be used in calculating load versus wire length Devi...

Страница 10: ... override on an output point to a desired value with the S7610 POT or ZM7601 ZM7603 software 2 Measure or observe the output condition e g fan turns on 3 If the output does not follow the command override condition isolate the problem by checking connections and measurements at the output destination as well as at the W7620 4 Clear the override condition Example The following procedure is for Fan ...

Страница 11: ...round Testing physical points requires either the actual sensor be at a known v a l u eor digital state or that a simulated known value or digital state be applied to the input point terminals In the case of physical output points the output condition of the controlled equipment must be known or the output terminals of the W7620 can be measured with an indicating device or meter The Hardware Confi...

Страница 12: ...arily provide a good ground The following provides grounding details 1 Earth ground one W7620 within a group of W7620s connected to a given transformer Connect the ground wire to the green ground screw on the W7620 chassis See Figure 7 connect the same side of the transformer secondary to the same terminal number on each W7620 2 Grounded Transformer Secondaries If the Transformer has a grounded se...

Страница 13: ...ee 24 Vac source indicating digital response to call from same transformer All three Inputs can be used separately or together to determine the final state of input Outputs Analog O IO Vdc 20 mA maximum Relay expansion 2 0 amp maximum running 7 5 amp In rush at 30 Vac 50 or 60 Hz Relay base 1 6 amp maximum running 7 5 amp In rush at 30 Vac 50 or 60 Hz Temperature Ratings Ambient 40 to 110 F 4 to 4...

Страница 14: ...bl Knockout for l 2 in conduit fittings Q Double knockout for 1 2 or 3 4 in conduit fittings Figure 8 W7620 Dimensions 14 63 4224 ...

Страница 15: ...Base Unit with cover Input Expansion Boards Use with W7459 Economizer Logic Module modulating spring Damper Actuator ...

Страница 16: ...td aar 18 mlnlstBr des Communlcstions du Canada Dear Customer Please send your comments and suggestions to We welcome your comments and suggestions for Improving Honeywell Inc this publication 8500 Bluewater N W Your assistance is greatly appreciated and will enable us to Albuquerque NM 87121 1958 provide better technical information for you ATTN Technical Editor HONEYWELL MINNEAPOLIS MN 55408 INT...

Отзывы: