VISTA-128FBPN Installation and Setup Guide
5-12
FIELD
TITLE and DATA ENTRIES
EXPLANATION
1*76
Control Relay (partition-specific)
01-96 = relay number
00 = relay not used.
If enabled, the assigned relay closes for 2 seconds when the user enters his
code and presses 0.
Must be set to “00” for Commercial Fire and Burglary installations.
NOTE: See
SECTION 3: Installing the Control
for enhanced access control
capabilities.
1*77
Log 1
st
Main Signal
0 = disable
1 = enable
If enabled, the system logs the first maintenance signal from each smoke
detector. If disabled, no logging occurs.
1*78
Extended Home Control Events
0 = limited
1 = extended
If extended, there are 255 commands to the home control command set. If
limited, there are 32 commands to the home control command set.
Home Control Automation is not allowed in UL installations.
1*79
Home Control Events
0 = disable
1 = enable
Select the type of events (status reports) transmitted via the RS232 output.
Home Control Automation is not allowed in UL installations.
1*80
Log Faults & Restores
0 = disable
1 = enable
When enabled automatically transfers data of the RS232 output.
Home Control Automation is not allowed in UL installations.
2*00
Number of Partitions
Enter 1-8.
Enter the number of partitions used in the system.
2*01
Daylight Saving Time Start/End
Month
0 = disable
1 = enable
Enter the months (00-12) in which daylight saving time starts and ends.
Enter 00, 00 if daylight saving time does not apply to the user’s region.
Standard setting for U.S. is 03, 11.
2*02
Daylight Saving Time Start/End
Weekend
0 = disable
1 = enable
Enter the start and end weekends for daylight saving time as follows: 1=first;
2=second; 3=third; 4=fourth; 5=last; 6=next to last; 7=third from last.
Standard setting for U.S. is 2, 1.
2*05
Auto-Arm Delay (partition-
specific)
00 = no delay.
01-14 times 4 minutes (04-56) delay.
15 = no auto arming.
This is the time between the end of the arming window and the start of auto-
arm warning time (field 2*06).
NOTE: This field must be set to “00” for UL installations.
2*06
Auto-Arm Warning Period
(partition-specific)
01-15 times 1-minute warning.
00 = no warning period.
This is the time that the user is warned by a keypad sounding and display to
exit the premises prior to auto arming of the system.
NOTE: This field must be set to “00” for UL installations.
2*07
Auto-Disarm Delay (partition-
specific)
00 = no delay.
01-14 times 4 minutes (04-56) delay.
15 = no auto disarming.
This is the time between the end of the disarming window and the start of auto
disarming of the system.
NOTE: This field must be set to “15” for UL864 compliance.
2*08
Force Arm Enable for Auto-Arm
(partition-specific)
0 = disable
1 = enable
If enabled, the system automatically bypasses any faulted zones when it
attempts to auto-arm.
If disabled, the system does not auto-arm.
NOTE: Force arm is not approved for ULC applications.
NOTE: This field must be set to “0” for UL installations.
Содержание VISTA-128FBP
Страница 2: ......
Страница 8: ...viii ...
Страница 62: ...VISTA 128FBPN Installation and Setup Guide 4 10 ...
Страница 98: ...VISTA 128FBPN Installation and Setup Guide 8 2 ...
Страница 108: ...VISTA 128FBPN Installation and Setup Guide 10 6 ...
Страница 114: ...VISTA 128FBPN Installation and Setup Guide B 2 Relay Control Commands Activate Relay for Current Partition User Code 0 ...
Страница 116: ...VISTA 128FBPN Installation and Setup Guide C 2 ...
Страница 120: ...VISTA 128FBPN Installation and Setup Guide D 4 ...