![Honeywell VISTA-128FBP Скачать руководство пользователя страница 106](http://html.mh-extra.com/html/honeywell/vista-128fbp/vista-128fbp_installation-and-setup-manual_153414106.webp)
VISTA-128FBPN Installation and Setup Guide
10-4
Trouble Conditions
Supervisory Messages
Display Description
SUPV +
Zone
Number
This indicates that a fire supervisory
condition exists on the zone number
displayed. This means that the operation
of the fire alarm system may be
compromised.
Check or Trouble Messages
Display Description
CHECK or
TRBL
(as per field
3
✳
00)
This indicates that a problem exists on
the zone number displayed. Zone trouble
may be caused by one of the following
conditions:
•
A hardwired fire zone is open
(broken wire).
•
A Day/Night zone (zone type 5) is
faulted.
•
A polling loop zone is not seen by
the control panel.
•
A polling loop zone has been
tampered (cover removed on a
4190SN).
•
A wireless zone has not checked in
during the time programmed in field
1
✳
31.
•
A 5800 Series transmitter has been
tampered (cover removed).
CHECK 6XX
XX = 01-32
This indicates a trouble on a 4204CF
Supervised Notification Appliance Circuit
(corresponding relay number 01-32).
CHECK 8XX
XX = 00-30
This indicates a trouble on a peripheral
device (connected to the panel’s keypad
terminals) of the corresponding device
address (00-30).
CHECK 9XX
XX = 70-77,
88,90,97
This indicates that a system trouble
exists (RF receiver, Notification
Appliance Circuit, etc.).
If the problem has been corrected, enter an
OFF sequence (Security Code + OFF) twice
to clear the display.
Power Failure
Display Description
AC LOSS
POWER
LED is off
This indicates that the system is
operating on battery power only. Check
to see that the circuit breaker for the
branch circuit that your system’s
transformer is wired to has not been
accidentally turned off. Instruct the
user to call a service representative
immediately if AC power cannot be
restored.
Other System Messages
Display Description
COMM
FAILURE
Indicates a failure occurred in the
telephone communication portion of your
system.
LO BAT
Indicates a low-battery condition exists in
the wireless transmitter displayed.
Pressing any key silences the audible
warning sound.
SYSTEM
LO BAT
This indicates that a low-battery condition
exists with the system’s backup battery.
HSENS
Indicates a smoke detector with a high
sensitivity level, which may cause a false
alarm. The detector should be cleaned or
replaced.
LSENS
Indicates a smoke detector with a low
sensitivity level. The detector may not
detect a smoke condition. The detector
should be cleaned or replaced.
RCVR
SETUP
ERROR
Indicates the system has more wireless
zones programmed than the RF receiver
can support. If this is not corrected, none
of the zones in the system will be
protected. If additional wireless zones are
desired, use an appropriate receiver.
MODEM
COMM
This indicates that the control is on-line
with a remote computer.
System Off-Normal Report
If programmed, an Off-Normal report is generated
instead of the periodic test report if any of the following
conditions are present at the time of the report:
•
Fire trouble on any zone (zone types 9, 16, 17, 18)
•
Fire supervisory present (zone type 18)
•
Unrestored fire alarm on any zone
•
Bypass of any fire zone
•
A fault for any supervised fire Notification
Appliance Circuit
•
Bypass/disable of any supervised fire Notification
Appliance Circuit
•
Telco fault of either dialer line
•
Bypass/disable of either dialer line
•
Earth ground fault
•
Bypass of earth ground supervisory zone
•
Fault on LORRA “XMIT OK” signal (if enabled)
•
LORRA trigger bypassed
•
AC failure
•
Low system battery
•
Keypad supervision fault
The Off-Normal report is sent as follows:
•
Contact ID: Code 608
•
High Speed: Channel 3 of system report used
(channel 9=6)
•
Low Speed: Digits programmed in System Group
#4 report codes
Содержание VISTA-128FBP
Страница 2: ......
Страница 8: ...viii ...
Страница 62: ...VISTA 128FBPN Installation and Setup Guide 4 10 ...
Страница 98: ...VISTA 128FBPN Installation and Setup Guide 8 2 ...
Страница 108: ...VISTA 128FBPN Installation and Setup Guide 10 6 ...
Страница 114: ...VISTA 128FBPN Installation and Setup Guide B 2 Relay Control Commands Activate Relay for Current Partition User Code 0 ...
Страница 116: ...VISTA 128FBPN Installation and Setup Guide C 2 ...
Страница 120: ...VISTA 128FBPN Installation and Setup Guide D 4 ...