Program feature or option
Permitted in
UL864? Y/N
Possible settings
Settings permitted in UL 864
27 TEST REPORT
INTERVAL
Y
Enter 0001-9999 for the test
report interval in hours.
Enter 0000 for test reporting.
Must be set to “0024”
(Maximum 24 hours)
28 POWERUP IN
PREVIOUS STATE
Y
0 = disable
1 = enable
Must be set to “1” (enable).
37 DOWNLOAD
COMMAND ENABLES
N
0 = disable
1 = enable
Must be set to “0” for all
entries (disable).
41 NORMALLY
CLOSED OR EOLR
(ZONES 3-8)
N
0 = EOLR supervision
1 = N.C. loops
Must be set to “0” (EOLR
Supervision).
42 DIAL TONE PAUSE
Y
Enter the wait time for dial
tone detection:
0 = 5 seconds; 1 = 11 seconds;
2 = 30 seconds.
Must be set to “0” (5 seconds).
44 RING DETECTION
COUNT
N
Enter 00 to disable ring
detection.
Enter 01-14 for ring counts of
1-14.
Enter 15 to select Answering
Machine Defeat Mode
Must be set to “00” (disable).
54 UNATTENDED
MODE
N
0 = disable
1 = enable
Must be set to “0” (disable).
56 DYNAMIC
SIGNALING DELAY
Y
Enter 00-15 times 15 seconds.
Must be set to “6” (90
seconds).
77 AUTO TROUBLE
RESTORE
Y
0 = disable
1 = enable
Must be set to “1” (enable).
80 ZONE TYPE
RESTORES FOR TYPES
9, 10 & 14
N
0 = disable
1 = enable
Must be set to “1” (enable) for
zone type 9.
1 12 PROGRAM
NOTIFICATION SIGNAL
Y
0 = no
1 = yes
Must be set to “1” (yes).
1 13
SYSTEM SENSOR
REVERSING RELAY
N
0=use neither Zone 1 or Zone
2 inputs
1=use Zone 1 input;
2=use Zone 2 input;
3=use Zone 1 and Zone 2
inputs.
Not Used. Must be set to “0”.
1 18
AFFECTS LOBBY
N
0 = disable
1 = enable
Must be set to “0” (disabled)
for partition 1.
1 19
ARMS LOBBY
N
0 = disable
1 = enable
Must be set to “0” (disabled)
for partition 1.
1 22 thru 1 25 CROSS-
ZONING PAIRS (1 – 4)
N
Enter 001-128
Enter 000,000 to disable
Must be set to “000,000”
(disabled) for fire zones.
1 28 RF TRANSMITTER
LOW BATTERY SOUND
N
0 = disarmed state only
1 = both armed and disarmed
states
Must be set to “1” (both
armed and disarmed states).
1 29 RF TRANSMITTER
LOW BATTERY
REPORTING
N
0 = disable
1 = enable
Must be set to “1” (enable).
Содержание VISTA-128FBP
Страница 2: ......
Страница 8: ...viii ...
Страница 62: ...VISTA 128FBPN Installation and Setup Guide 4 10 ...
Страница 98: ...VISTA 128FBPN Installation and Setup Guide 8 2 ...
Страница 108: ...VISTA 128FBPN Installation and Setup Guide 10 6 ...
Страница 114: ...VISTA 128FBPN Installation and Setup Guide B 2 Relay Control Commands Activate Relay for Current Partition User Code 0 ...
Страница 116: ...VISTA 128FBPN Installation and Setup Guide C 2 ...
Страница 120: ...VISTA 128FBPN Installation and Setup Guide D 4 ...