VISTA-128FBPN Installation and Setup Guide
4-4
MAIN MENU
OPTIONS
SCHEDULED CHK-IN
1 = YES 0 = NO
0
For defining the schedule for the system to automatically call the downloader.
Following is a list of commands used while in the Menu Mode:
#93 Menu Mode Programming Commands
#93
Enters Menu Mode.
[
✳
]
Serves as [ENTER] key. Press to have keypad accept entry.
[#]
Backs up to previous screen.
0
Press to answer NO.
1
Press to answer YES.
00, or 000+[
✳
]
Quits Menu Mode and goes back to Data Field Programming Mode, if entered at first prompt of each main menu option.
Zone Number Designations
The VISTA-128FBPN supports up to 128 zones of
hardwire, polling loop and/or wireless protection,
distributed among up to 8 partitions. The following
table lists the zone numbers and the types of sensors
that can be used with each, and some alternate
functions of the zones.
Zone
Function
1 & 2
2-wire Smoke Detectors (if used)
6
Cabinet Tamper/Ground Fault (if used)
7
Keyswitch (if used)
8
Latching-Type Glassbreak Detectors (if used)
1-8
Traditional Hardwired Zones
1-128
5800 Series Wireless Devices
9-128
Polling Loop Devices
995
✳
+ 1 Panic (Do not use in Fire Alarm applications)
996
# + 3 Panic (Do not use in Fire Alarm applications)
999
✳
+ # Panic (Do not use in Fire Alarm applications)
Zone Defaults
Zone #
Zone Type
Zone #
Zone Type
001 09
800-830
00
002 09 970 19
003 03
971-974
19
004 03 975 00
005
03
988 & 990
00
006 03 992*
N/A
007 03 995 00
008 03 996 00
009–128
00 997 19
601-632
00 999 06
NOTES:
*
Zone 992 is the Duress zone. Programming of the zone
response type is not applicable. This zone requires only the
report code programming.
Zone Index
The zones are designated as follows:
ZONE #
RANGE
ZONE
FUNCTION
ACTUAL ZONE
001 – 128
Protection
zones
As indicated
601 – 632
Relay
Supervision
Zones
6 + 2-digit Relay Number; e.g.,
Relay Number 03, if supervised,
is zone 603.
NOTE: Relay supervision
should be used only for
relays on 4204CF modules.
800 – 830
ECP Device
Supervision
Zones
8 + 2-digit Device Address; e.g.,
Device Address 01, if
supervised, is zone 801.
970-977,
988, 990, &
997
System
Supervision
Zones
970: Bell
1Output
971
Bell 2 Output
972 Earth
Ground
973 J2
Input
1
(
communications
device
)
974 Dialer
1
975 Dialer
2
976 Auxiliary
Relay
977
J2 Trigger Outputs
988: 2
nd
Wireless Receiver –
not receiving signals
990: 1
st
Wireless Receiver –
not receiving signals
997:
Polling Loop (short
circuit)
992, 995 –
999
Duress and
Keypad Panics
992: Duress
995:
1 +
✳
panic (A key)
996:
3 + # panic (C key)
999:
✳
+ # panic (B key)
Supervision zones should be given a response type of either 05
(Trouble by Day, Alarm by Night) or 19 (24-Hour Trouble).
Содержание VISTA-128FBP
Страница 2: ......
Страница 8: ...viii ...
Страница 62: ...VISTA 128FBPN Installation and Setup Guide 4 10 ...
Страница 98: ...VISTA 128FBPN Installation and Setup Guide 8 2 ...
Страница 108: ...VISTA 128FBPN Installation and Setup Guide 10 6 ...
Страница 114: ...VISTA 128FBPN Installation and Setup Guide B 2 Relay Control Commands Activate Relay for Current Partition User Code 0 ...
Страница 116: ...VISTA 128FBPN Installation and Setup Guide C 2 ...
Страница 120: ...VISTA 128FBPN Installation and Setup Guide D 4 ...