Section 3 - Installing the Control
3-5
You may use a Commercial Fire Listed 24VDC Power Supply to convert one or both Vista-128FBPN 12VDC,
1.7A style-Y supervised Special Application Notification Appliance Circuits to 24V, style-Y supervised, Special
Application Notification Appliance Circuits.
UL
•
Burglary Notification Appliance Circuits must be programmed for a timeout of 16 minutes or longer.
•
Commercial fire alarm systems require Notification Appliance Circuits to be supervised.
Notification Appliance Circuit Supervision
The VISTA-128FBPN monitors the Notification Appliance Circuits wiring for open and short circuit faults while the
output is inactive. The system provides a trouble indication (Zone 970 Bell 1; 971 Bell 2) when an open occurs. When a
short occurs between the Bell (+) and Bell (-) terminal wiring, or between the Bell (+) terminal wiring and earth ground
the system provides a trouble indication (972 Earth Ground).
The VISTA-128FBPN indicates the trouble condition regardless of whether the system is armed or disarmed. The zone
displays on the keypads, reports to the event log, and transmits to the central station (if programmed) on Partition 1.
The trouble is cleared from the display by entering the user code + OFF.
UL
•
Use only UL Listed sounding devices for UL installations.
•
In Commercial Fire installations, the 4204CF cannot be used to drive sounders in the same audible area as
sounders connected to the alarm outputs of the control panel.
Synchronization Requirements for Commercial Fire
Notification Appliance Circuit outputs must be wired to a Sync Module if more than one device is used. Follow
instructions provided with Sync Module. Be sure to use the compatible Sync Module for the Alarm Indicating Device
selected.
MANUFACTURER
SYNC MODULE MODEL NUMBER
GENTEX AVSM
SYSTEM SENSOR
MDL
WHEELOCK DSM
UL
•
All visual notification appliances within the same physical area must be synchronized.
•
The bell outputs are listed as Special Application Notification Appliance Circuits.
Compatible Alarm Indicating Devices
ALARM INDICATING DEVICE TYPE
MANUFACTURER
MODEL #
UL listed Grade A Bell in Housing
Honeywell/ADEMCO
AB12M
Indoor/Outdoor Bell in Steel Bell Box (not evaluated by UL)
Amseco/Potter
ABB-1012
Motorized Burglar Bell 10 Inch 12 VDC (not evaluated by UL)
Amseco/Potter
MBA-10G12PV2
RX7 UL Indoor Sounder, 12V
ADT
875936B
Horn Strobe 2w
GENTEX
GEC3-12, GES3-12, GEH-12
Horn Strobe 2w
GENTEX
GEC3-12, GES3-12, GEH-12
Horn Strobe 4w
GENTEX
GEC3-12, GES3-12, GEH-12
Horn Strobe 4w
GENTEX
GEC3-12, GES3-12, GEH-12
Chime, 12/24V, Selectable Tone & Volume, Red
SYSTEM SENSOR
CHR
Chime, 12/24V, Selectable Tone & Volume, White
SYSTEM SENSOR
CHW
Chime/Strobe, 12/24V, Selectable Candela, Tone & Volume, Red
SYSTEM SENSOR
CHSR
Chime/Strobe, 12/24V, Selectable Candela, Tone & Volume, White
SYSTEM SENSOR
CHSW
Horn, 12/24V, Red
SYSTEM SENSOR
HR
Horn, 12/24V, White
SYSTEM SENSOR
HW
Horn, 12/24V, Outdoor, Red
SYSTEM SENSOR
HRK
2-Wire Wall Mount Horn/Strobe, 12/24V, Standard Candela, Red
SYSTEM SENSOR
P2R
2-Wire Wall Mount Horn/Strobe, 12/24V, High Candela, Red
SYSTEM SENSOR
P2RH
2-Wire Wall Mount Horn/Strobe, 12/24V, Standard Candela, Red, Outdoor
SYSTEM SENSOR
P2RK
2-Wire Wall Mount Horn/Strobe, 12/24V, High Candela, Red, Outdoor
SYSTEM SENSOR
P2RHK
2-Wire Wall Mount Horn/Strobe, 12/24V, Standard Candela, White
SYSTEM SENSOR
P2W
Содержание VISTA-128FBP
Страница 2: ......
Страница 8: ...viii ...
Страница 62: ...VISTA 128FBPN Installation and Setup Guide 4 10 ...
Страница 98: ...VISTA 128FBPN Installation and Setup Guide 8 2 ...
Страница 108: ...VISTA 128FBPN Installation and Setup Guide 10 6 ...
Страница 114: ...VISTA 128FBPN Installation and Setup Guide B 2 Relay Control Commands Activate Relay for Current Partition User Code 0 ...
Страница 116: ...VISTA 128FBPN Installation and Setup Guide C 2 ...
Страница 120: ...VISTA 128FBPN Installation and Setup Guide D 4 ...