VISTA-128FBPN Installation and Setup Guide
5-10
FIELD
TITLE and DATA ENTRIES
EXPLANATION
1*31
RF Transmitter Check-in Interval
Enter 02-15 times 2 hours (4-30 hours).
00 = disable transmitter supervision.
Select the check-in monitoring interval for the RF transmitters.
Failure of an individual transmitter to send a supervision signal within the time
entered will result in a trouble response and related communication report.
Maximum is 2 (4 hr) for Commercial Fire and UL Commercial Burglary
installations.
1*33
TouchTone with Rotary Backup
0 = disable
1 = enable
If enabled, the system reverts to rotary dialing if communicator is not
successful in dialing using TouchTone DTMF on first attempt.
1*34
Communicator Split Reporting
0 = Split Reporting disabled
1 = Alarm, Alarm Restore, and Cancel
reports to primary, all others to secondary
2 = Open/Close and Test reports to
secondary, all other reports to primary
3 = Fire Alarms and Fire Restores to primary
and secondary, all others to secondary
Select the type of split reporting for system communication.
NOTE: See *51 for split/dual reporting combinations.
NOTE: Split reporting should not be used with Dynamic Signaling.
1*35
Access Control Dialer Enables
0 = disable
1 = enable
There are six entries for this field as follows: Trace, Trouble, Not Used,
Bypass, System, and Alarm.
If Trace is enabled, access grant/denial events sent to the central station.
For the other events, if enabled, a report is sent to the central station.
Not Used.
1*42
Call Waiting Defeat
0 = disable
1 = enable
If enabled, the system defeats Call Waiting on the first outgoing call attempt to
both the primary and secondary numbers.
NOTES:
After the panel's initial call to report the alarm, the panel may attempt to make
an additional call, perhaps for a cancel or a zone restoral. If Call Waiting is
not defeated, an operator at the central station attempting to contact the
premises (to verify whether the alarm is valid) hears the phone ringing
indefinitely and must to dispatch on the call.
DO NOT enable this feature unless Call Waiting is being used.
1*43
Permanent Keypad Display
Backlighting (partition-specific)
0 = disable
1 = enable
If enabled, backlighting for the keypad display remains on at all times.
Otherwise the backlighting comes on when a key is pressed.
NOTE: When a key is pressed, display backlighting turns on for all keypads in
that partition.
1*44
Wireless Keypad Tamper Detect
0 = disable
1 = enable
If enabled, when more than 40 key depressions are received without a valid
sequence (arm, disarm, etc.), the control panel disables the wireless keypad.
The inhibit is removed once a valid key sequence is received from a wired
keypad.
Not Used. Must be disabled (“0”).
1*47
Chime on Bell 1 (partition-
specific)
0 = disable
1 = enable
If enabled, the system produces chime annunciation on the Bell 1 output.
1*48
Wireless Keypad Assignment
0 = none
1-8 = partition number
Select the partition in which RF keypad is used.
Not Used. Must be set to “0”.
1*49
Suppress Transmitter
Supervision Sound
0 = disable
1 = enable
If enabled, no trouble soundings occur on the keypad for transmitter check-in
failures.
Must be 0 for UL installations.
Содержание VISTA-128FBP
Страница 2: ......
Страница 8: ...viii ...
Страница 62: ...VISTA 128FBPN Installation and Setup Guide 4 10 ...
Страница 98: ...VISTA 128FBPN Installation and Setup Guide 8 2 ...
Страница 108: ...VISTA 128FBPN Installation and Setup Guide 10 6 ...
Страница 114: ...VISTA 128FBPN Installation and Setup Guide B 2 Relay Control Commands Activate Relay for Current Partition User Code 0 ...
Страница 116: ...VISTA 128FBPN Installation and Setup Guide C 2 ...
Страница 120: ...VISTA 128FBPN Installation and Setup Guide D 4 ...