background image

SV9501/SV9502/SV9601/SV9602 SMARTVALVE

TM 

SYSTEM CONTROL

9

69-1270—3

Standard Pressure Regulator (M Models), 

Slow Open (H models), Step Open (P 

Models)

1.

Check the full rate manifold pressure listed on the 
appliance nameplate. The ignition system control 
outlet pressure must match the full rate pressure 
listed on the nameplate. Adjust the pressure if they 
do not match.

NOTE: Slow opening (H models) and step opening 

(P models) may take several seconds to reach 
full flow rate. M models will take 2 to 3 seconds 
to reach full flow rate.

2.

With the main burner ON, check the ignition system 
control flow rate using the meter clocking method, 
or check the pressure using a manometer 
connected to the outlet pressure tap on the ignition 
system control.

3.

Adjust the pressure regulator to match the 
appliance rating if necessary. See Table 2 and 3 for 
factory set nominal outlet pressure and adjustment 
range.
a. Remove the pressure regulator adjustment cap 

screw.

b. Using a screwdriver, turn the inner adjustment 

screw clockwise to increase or counter 
clockwise to decrease gas pressure to the 
burner.

c. Replace the cap screw and tighten it firmly to 

prevent gas leakage.

4.

If the desired outlet pressure or flow rate cannot be 
achieved by adjusting the ignition system control, 
check the ignition system control inlet pressure 
using a manometer at the ignition system control 
inlet pressure tap.

5.

If the inlet pressure is in the factory specified 
nominal range, as shown in Table 2 and 3, replace 
the ignition system control. Otherwise, take the 
necessary steps to provide proper gas pressure to 
the control.

NOTE: If the burner firing rate is above the maximum 

capacity as shown in Table 3, it might not be pos-
sible to deliver the desired outlet pressure. This 
is an application issue, not a control failure. Take 
whatever steps are necessary to correct the situ-
ation.

MAINTENANCE

WARNING

Fire or Explosion Hazard.
Can cause severe injury, death or property 
damage.

Do not attempt to take the control apart or clean it. 
Improper cleaning or reassembly may cause gas 
leakage.

Regular preventive maintenance is important in 
applications that place a heavy load on system controls. 
This include applications in commercial cooking, 
agricultural, and industrial industries where these 
conditions often exist:

• Heavy cycling. In commercial cooking, the operation, 

the equipment operates 100,000 to 200,000 cycles per 
year. This can wear out a gas control in one to two 
years.

• Exposure to water, dirt, chemicals, and heat can 

damage the gas control and shut down the control 
system.

Table 2. SV9501/SV9502/SV9602/SV9601 Pressure Regulator Specification Pressures.

Table 3. Capacity of SV9501/SV9502/SV9602/SV9601.

The maintenance program should include regular 
checkout of the control as described in the Startup and 
Checkout section, and the control system as described in 
the application manufacturer’s literature.

Maintenance frequency must be determined individually 
for each application. Some considerations follow:

• Cycling frequency. Appliances that cycle 20,000 times 

annually should be checked each month.

• Intermittent use. Appliances that are used seasonally 

should be checked before shutdown and before each 
use.

• Consequence of unexpected shutdown. Where the 

cost of an unexpected shutdown would be high, check 
the system frequently. 

• Dusty, wet, or corrosive environment. Since these 

environments can cause the gas control to deteriorate 
more rapidly, check the system frequently.

Model 

Type

Type of 

Gas

Nominal Inlet 

Pressure Range

Factory Set Nominal Outlet 

Pressure

Setting Range

Step

Full Rate

Step

Full Rate

in. wc

kPa

in. wc

kPa

in. wc

kPa

in. wc

kPa

in. wc

kPa

Standard, 
Slow

NAT

5.0-7.0

1.2-1.7

3.5

0.9

3-5

0.7-1.2

LP

12.0-14.0 2.9-3.9

10.0

2.5

8-12

2-3

Step

NAT

5.0-7.0

1.2-1.7

0.9

0.2

3.5

0.9

None

None

3-5

0.7-1.2

LP

12.0-14.0 2.9-3.9

2.2

0.2

10.0

2.5

None

None

8-12

2.0-3.0

Model

Size

(Inlet x Outlet) (in.)

Capacity (at 1 inch 

wc pressure drop)

Minimum Regulated 

Capacity

Maximum Regulated 

Capacity

SV9501/SV9502

1/2 x 1/2

150 ft

3

/hr (3.7m

3

/hr)

20 ft

3

/hr (0.6m

3

/hr)

200 ft

3

/hr 95.7m

3

/hr)

SV9602/SV9601

3/4 x 3/4

300 ft

3

/hr (8.5m

3

/hr)

30 ft

3

/hr (0.8 m

3

/hr)

415 ft

3

/hr (11.8m

3

/hr)

Содержание TRADELINE SV9501

Страница 1: ...ed step outlet pressure at the start of each heating cycle to allow main burner ignition at reduced outlet pressure Reducer bushings are provided with the SV9602 and SV9601 models for adapting to smaller pipe sizes IMPORTANT Carefully determine the full Honeywell model number of the existing control Use Table 4 or Table 5 to make sure the replacement control model is suitable for replacing the ori...

Страница 2: ...ge the control Make sure the ambient temperature at the control does not exceed the control rating If the appliance operates at very high temperatures use insulation shielding and proper air circulation as necessary to protect the control The appliance manufacturer should provide proper insulation or shielding Make sure there is proper air circulation when installing the appliance Installation WAR...

Страница 3: ...ine in place of the gas control by following the same precautions and instructions that are used for installing the gas control After the pipe adapter is installed attach the gas control to the adapter NOTE Using a pipe adapter increases the overall length of the gas control Install Pipe Adapter to Gas Control Install adapter to gas control as follows Bushings 1 Remove seal over gas control inlet ...

Страница 4: ...system control connect the pipe to the ignition system control inlet and outlet Fig 3 Sediment trap installation Fig 4 Mount so gas flows in the direction of the arrows NOTE If the control has a flange place the wrench on the flange instead of on the ignition system con trol as shown in Fig 6 Table 1 Threading the Pipe M17142 VALVE OUTLET FLANGE 9 64 INCH HEX SCREWS 4 Pipe Size Thread Pipe this Am...

Страница 5: ...50 or Q3480 pilot hardware Wiring Follow the wiring instructions supplied by the appliance manufacturer if available Otherwise use the following general instructions NOTE 1 In most cases connect the wiring by plugging the appliance wiring harness connector into the SmartValveTM Use the supplied exten sion harness if necessary 2 Where the general instructions are different from the appliance manufa...

Страница 6: ...ERMOSTAT OR PRESSURE SWITCH PILOT BURNER GROUND THROUGH PILOT TUBING L1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 1 1 M7935C UNUSED M7937D G W C Y R FUSE AIR CLEANER LO ML MH HI CIRCULATING FAN STARTING CAP ROLL OUT SWITCH LIMIT CONTROL PRESSURE SWITCH TRANS FORMER 115 230 VAC 24 VAC DENOTES STANDARD TERMINAL DENOTES OPTIONAL TERMINAL THERMOSTAT L2 N L1 H TO 115 230...

Страница 7: ...ccurs normally ON Allows gas to flow through the control valve The thermostat controls the gas flow to the pilot and main burners Fig 11 SV9501 SV9502 SV9602 SV9601 typical wiring diagram in induced draft boiler application THERMOSTAT L2 L1 120 VAC POWER SUPPLY W G C R Y COIL RED BLACK RED D892 VENT DAMPER 4 3 2 1 BLACK CIRCULATOR PUMP AQUASTAT CONTROL ROLLOUT SWITCH SPILL SWITCH M7936C BLACK PILO...

Страница 8: ... gas leakage NOTE Controls are provided with adjustment screws set at the maximum pilot flow position Fig 12 Proper flame adjustment Check and Adjust Gas Input and Burner Ignition IMPORTANT Many replacement valves require outlet pressure adjustment Do not exceed the input rating stamped on the appliance nameplate Do not exceed the manufacturer s recommended burner orifice pressure for size of orif...

Страница 9: ...e the control apart or clean it Improper cleaning or reassembly may cause gas leakage Regular preventive maintenance is important in applications that place a heavy load on system controls This include applications in commercial cooking agricultural and industrial industries where these conditions often exist Heavy cycling In commercial cooking the operation the equipment operates 100 000 to 200 0...

Страница 10: ...pliances in the house Do not touch any electrical switches Do not use the phone Leave the building and go to a neighbor s phone to call your gas supplier If you cannot reach your gas supplier call the fire department 4 Do not force or use tools to move the ignition system control switch If the switch does not operate by hand the ignition system control must be replaced by a qualified licensed if r...

Страница 11: ...eld technicians to analyze normal appliance operation Fig 13 SV9500 SV9600 SmartValveTM System Sequence of Operation APPLY 24V POWER TO SYSTEM START THERMOSTAT CALLS FOR HEAT A POWERED PILOT VALVE OPENS AND IGNITER ENERGIZES PILOT LIGHTS FLAME ROD SENSES FLAME IGNITER OFF MAIN VALVE OPENS MAIN BURNER LIGHTS ELECTRONIC FAN TIMER OUTPUT ENERGIZES THERMOSTAT CALL FOR HEAT ENDS MAIN AND PILOT VALVES C...

Страница 12: ...equence and Troubleshooting flow chart in Fig 14 and 16 for the replacement SV9501 SV9502 SV9601 SV9602 SmartValveTM NOTE The HSI element action for SV9501 SV9502 SV9601 SV9602 is different from the HSI element action for SV9500 SV9600 For SV9500 SV9600 the element is on continuously during a call for heat until shortly after the pilot flame is detected the main valve energizes and the element tur...

Страница 13: ...MEASURE VOLTAGE BETWEEN 24V HOT AND 24V COMMON LEADS TO SmartValve CONTROL MUST MEASURE AT LEAST 19 5 VAC WITH IGNITER POWERED SEE INSET A TO IDENTIFY PROPER LEAD THIS CHECK MUST BE DONE WITH THE SmartValve CONTROL CONNECTED AND IGNITER POWERED CHECK THAT PILOT FLAME MAKES GOOD CONTACT WITH PILOT BURNER FLAME ROD CHECK FOR GOOD ELECTRICAL CONNECTION THROUGH THE PILOT TUBING IF BOTH OF THE ABOVE AR...

Страница 14: ...artValve CONTROL MUST MEASURE AT LEAST 19 5 VAC WITH IGNITER POWERED SEE INSET A TO IDENTIFY PROPER LEAD THIS CHECK MUST BE DONE WITH THE SmartValve CONTROL CONNECTED AND IGNITER POWERED CHECK THAT PILOT FLAME MAKES GOOD CONTACT WITH PILOT BURNER FLAME ROD CHECK FOR GOOD ELECTRICAL CONNECTION THROUGH THE PILOT TUBING IF BOTH OF THE ABOVE ARE GOOD REPLACE IGNITER FLAME ROD ASSEMBLY CYCLE THERMOSTAT...

Страница 15: ...ting Type of Opening Prepurge Time Type of Gas Replaces in wc kPa SV9502H2522 1 2 in x 1 2 in 3 5 0 87 Slow 15 sec Natural SV9500H2609a e SV9500H2617a e SV9500H2724e SV9500H3607a d e SV9500H3615b d e SV9501H2409a e SV9501H2417e SV9501H2425b e SV9501H3415a d e SV9501H3423b d e SV9502H1706 SV9502H2522 SV9502H2704 SV9501M2528 Standard None SV9500M2603 SV9500M2629a d SV9500M2637d SV9500M2645 SV9500M26...

Страница 16: ...ce has been converted to LP gas use SV9602P4832 as the replacement e These models were field convertible to natural gas If the appliance has been converted to natural gas use SV9602P4824 as the replacement Order Number Inlet Outlet Size Pressure Regulator Setting Type of Opening Prepurge Time Type of Gas Replaces in wc kPa SV9602P4816 3 4 in x 3 4 in 3 5 0 7 Step 30 Sec 30 sec Natural SV9500P2600b...

Отзывы: