background image

SV9501/SV9502/SV9601/SV9602 SMARTVALVE

TM 

SYSTEM CONTROL

69-1270—3

2

demands on the controls. Special steps are 
recommended to prevent nuisance shutdowns and control 
failures due to frequent cycling, or severe environmental 
conditions such as exposure to moisture, corrosive 
chemicals, dust, or excessive heat. Following are the 
possible causes of shutdown and the preventative 
solutions.

Frequent Cycling

These controls are designed to cycle three to four times 
each hour during the heating season. Year around 
applications and applications with more frequent cycling 
rates can wear out controls more quickly than normal 
operation. Perform monthly system checks to make sure 
the system operates properly.

Water or Steam Cleaning

Replace any electronic control that gets wet. If the 
appliance is likely to be cleaned with water or steam, 
cover the control and wiring to protect them from water or 
steam flow. Mount the control high enough above the 
cabinet bottom to avoid getting it wet during cleaning 
procedures.

High Humidity or Dripping Water

Dripping water can cause the control to fail. Never install 
an appliance where water can drip on the control. High 
humidity around the control can cause the control to 
corrode and fail. If the appliance is located in a humid 
atmosphere, make sure the air circulation around the 
control is adequate to prevent water condensing on the 
control. Check the system regularly for signs of 
condensation and corrosion.

Corrosive Chemicals

Corrosive chemicals can erode the control, eventually 
causing a failure. If chemicals are used for routine 
cleaning, make sure they do not touch the control. Where 
chemicals are suspended in air, for example, in some 
industrial or agricultural applications, protect the control 
with an enclosure.

Dust or Grease Accumulation

Heavy accumulations of dust or grease can cause the 
control to malfunction. Where dust or grease are 
problems, cover the control to limit contamination.

Heat

Excessively high (above 175°F [79°C]) temperatures can 
damage the control. Make sure the ambient temperature 
at the control does not exceed the control rating. If the 
appliance operates at very high temperatures, use 
insulation, shielding and proper air circulation as 
necessary to protect the control. The appliance 
manufacturer should provide proper insulation or 
shielding. Make sure there is proper air circulation when 
installing the appliance.

Installation

WARNING

Fire or Explosion Hazard.
Can cause severe injury, death or property 
damage.

Follow these warnings exactly as written.

1. Disconnect the power supply before wiring to 

prevent electrical shock and equipment 
damage.

2. Turn of the gas supply at the appliance service 

valve before starting installation to avoid 
dangerous accumulation of fuel gas.

3. Perform gas leak test after completing 

installation.

4. Do not bend pilot tubing at ignition system 

control or pilot burner after tightening the 
compression fitting. Bending can cause gas 
leakage at the connection.

5. Always install a sediment trap in the gas supply 

line to prevent contamination of the ignition 
system.

WARNING

Fire or Explosion Hazard.
Can cause severe injury, death or property 
damage.

Follow this warning exactly as written.

• Always change the main and pilot burner 

orifices when converting between LP and 
natural gas. Follow appliance manufacturer 
specifications and instructions.

CAUTION

Equipment Damage Hazard.
Improper device replacement will damage the 
equipment.

The SV9501, SV9502, SV9602, and SV9601 
provide direct replacement only as shown in Table 
4 or Table 5 of this manual. Use the Y8610 to 
convert standing pilot systems to electronic 
ignition systems.

CAUTION

Equipment Damage Hazard.
Can Burn Out Heat Anticipator in Thermostat.

1. Never apply a jumper across or short the 

terminals in the SV9501, SV9502, SV9602, or 
SV9601 connectors or appliance wiring 
harnesses.

2. Never short the electric fan timer (EFT) output. 

Shorting the output can damage the EFT drive 
circuitry.

IMPORTANT

These ignition system controls are shipped with 
protective seals over inlet and outlet tappings. 
Do not remove seals until ready to connect 
piping.

Follow the appliance manufacturer’s instructions if 
available. Otherwise, use these instructions as a guide.

Содержание TRADELINE SV9501

Страница 1: ...ed step outlet pressure at the start of each heating cycle to allow main burner ignition at reduced outlet pressure Reducer bushings are provided with the SV9602 and SV9601 models for adapting to smaller pipe sizes IMPORTANT Carefully determine the full Honeywell model number of the existing control Use Table 4 or Table 5 to make sure the replacement control model is suitable for replacing the ori...

Страница 2: ...ge the control Make sure the ambient temperature at the control does not exceed the control rating If the appliance operates at very high temperatures use insulation shielding and proper air circulation as necessary to protect the control The appliance manufacturer should provide proper insulation or shielding Make sure there is proper air circulation when installing the appliance Installation WAR...

Страница 3: ...ine in place of the gas control by following the same precautions and instructions that are used for installing the gas control After the pipe adapter is installed attach the gas control to the adapter NOTE Using a pipe adapter increases the overall length of the gas control Install Pipe Adapter to Gas Control Install adapter to gas control as follows Bushings 1 Remove seal over gas control inlet ...

Страница 4: ...system control connect the pipe to the ignition system control inlet and outlet Fig 3 Sediment trap installation Fig 4 Mount so gas flows in the direction of the arrows NOTE If the control has a flange place the wrench on the flange instead of on the ignition system con trol as shown in Fig 6 Table 1 Threading the Pipe M17142 VALVE OUTLET FLANGE 9 64 INCH HEX SCREWS 4 Pipe Size Thread Pipe this Am...

Страница 5: ...50 or Q3480 pilot hardware Wiring Follow the wiring instructions supplied by the appliance manufacturer if available Otherwise use the following general instructions NOTE 1 In most cases connect the wiring by plugging the appliance wiring harness connector into the SmartValveTM Use the supplied exten sion harness if necessary 2 Where the general instructions are different from the appliance manufa...

Страница 6: ...ERMOSTAT OR PRESSURE SWITCH PILOT BURNER GROUND THROUGH PILOT TUBING L1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 1 1 M7935C UNUSED M7937D G W C Y R FUSE AIR CLEANER LO ML MH HI CIRCULATING FAN STARTING CAP ROLL OUT SWITCH LIMIT CONTROL PRESSURE SWITCH TRANS FORMER 115 230 VAC 24 VAC DENOTES STANDARD TERMINAL DENOTES OPTIONAL TERMINAL THERMOSTAT L2 N L1 H TO 115 230...

Страница 7: ...ccurs normally ON Allows gas to flow through the control valve The thermostat controls the gas flow to the pilot and main burners Fig 11 SV9501 SV9502 SV9602 SV9601 typical wiring diagram in induced draft boiler application THERMOSTAT L2 L1 120 VAC POWER SUPPLY W G C R Y COIL RED BLACK RED D892 VENT DAMPER 4 3 2 1 BLACK CIRCULATOR PUMP AQUASTAT CONTROL ROLLOUT SWITCH SPILL SWITCH M7936C BLACK PILO...

Страница 8: ... gas leakage NOTE Controls are provided with adjustment screws set at the maximum pilot flow position Fig 12 Proper flame adjustment Check and Adjust Gas Input and Burner Ignition IMPORTANT Many replacement valves require outlet pressure adjustment Do not exceed the input rating stamped on the appliance nameplate Do not exceed the manufacturer s recommended burner orifice pressure for size of orif...

Страница 9: ...e the control apart or clean it Improper cleaning or reassembly may cause gas leakage Regular preventive maintenance is important in applications that place a heavy load on system controls This include applications in commercial cooking agricultural and industrial industries where these conditions often exist Heavy cycling In commercial cooking the operation the equipment operates 100 000 to 200 0...

Страница 10: ...pliances in the house Do not touch any electrical switches Do not use the phone Leave the building and go to a neighbor s phone to call your gas supplier If you cannot reach your gas supplier call the fire department 4 Do not force or use tools to move the ignition system control switch If the switch does not operate by hand the ignition system control must be replaced by a qualified licensed if r...

Страница 11: ...eld technicians to analyze normal appliance operation Fig 13 SV9500 SV9600 SmartValveTM System Sequence of Operation APPLY 24V POWER TO SYSTEM START THERMOSTAT CALLS FOR HEAT A POWERED PILOT VALVE OPENS AND IGNITER ENERGIZES PILOT LIGHTS FLAME ROD SENSES FLAME IGNITER OFF MAIN VALVE OPENS MAIN BURNER LIGHTS ELECTRONIC FAN TIMER OUTPUT ENERGIZES THERMOSTAT CALL FOR HEAT ENDS MAIN AND PILOT VALVES C...

Страница 12: ...equence and Troubleshooting flow chart in Fig 14 and 16 for the replacement SV9501 SV9502 SV9601 SV9602 SmartValveTM NOTE The HSI element action for SV9501 SV9502 SV9601 SV9602 is different from the HSI element action for SV9500 SV9600 For SV9500 SV9600 the element is on continuously during a call for heat until shortly after the pilot flame is detected the main valve energizes and the element tur...

Страница 13: ...MEASURE VOLTAGE BETWEEN 24V HOT AND 24V COMMON LEADS TO SmartValve CONTROL MUST MEASURE AT LEAST 19 5 VAC WITH IGNITER POWERED SEE INSET A TO IDENTIFY PROPER LEAD THIS CHECK MUST BE DONE WITH THE SmartValve CONTROL CONNECTED AND IGNITER POWERED CHECK THAT PILOT FLAME MAKES GOOD CONTACT WITH PILOT BURNER FLAME ROD CHECK FOR GOOD ELECTRICAL CONNECTION THROUGH THE PILOT TUBING IF BOTH OF THE ABOVE AR...

Страница 14: ...artValve CONTROL MUST MEASURE AT LEAST 19 5 VAC WITH IGNITER POWERED SEE INSET A TO IDENTIFY PROPER LEAD THIS CHECK MUST BE DONE WITH THE SmartValve CONTROL CONNECTED AND IGNITER POWERED CHECK THAT PILOT FLAME MAKES GOOD CONTACT WITH PILOT BURNER FLAME ROD CHECK FOR GOOD ELECTRICAL CONNECTION THROUGH THE PILOT TUBING IF BOTH OF THE ABOVE ARE GOOD REPLACE IGNITER FLAME ROD ASSEMBLY CYCLE THERMOSTAT...

Страница 15: ...ting Type of Opening Prepurge Time Type of Gas Replaces in wc kPa SV9502H2522 1 2 in x 1 2 in 3 5 0 87 Slow 15 sec Natural SV9500H2609a e SV9500H2617a e SV9500H2724e SV9500H3607a d e SV9500H3615b d e SV9501H2409a e SV9501H2417e SV9501H2425b e SV9501H3415a d e SV9501H3423b d e SV9502H1706 SV9502H2522 SV9502H2704 SV9501M2528 Standard None SV9500M2603 SV9500M2629a d SV9500M2637d SV9500M2645 SV9500M26...

Страница 16: ...ce has been converted to LP gas use SV9602P4832 as the replacement e These models were field convertible to natural gas If the appliance has been converted to natural gas use SV9602P4824 as the replacement Order Number Inlet Outlet Size Pressure Regulator Setting Type of Opening Prepurge Time Type of Gas Replaces in wc kPa SV9602P4816 3 4 in x 3 4 in 3 5 0 7 Step 30 Sec 30 sec Natural SV9500P2600b...

Отзывы: