2. Overview / Introduction
2.6.1 Available Modules
Analogue Input Module 4–20 mA (AIM mA)
4-channel Analogue Input Module for 2 or 3 wire 4-20mA detector
signals
Analogue Input Module mV Bridge (AIM mV)
4-channel Analogue Input Module for mV-Bridge signals; powers up to 4
catalytic flammable gas detectors
Digital Input Module (DIM)
4-channel Digital Input Module for switched input devices such as
manually operated push buttons. Can also be used for remote alarm
acknowledge, reset and output inhibit
Relay Output Module (ROM)
4-channel Relay Output Module incorporating 4 SPCO relays; suitable to
activate field mounted annunciators
Note: Communication/Power Rails may be included in the system without any I/O Modules, however there is
a limit of 5 such Communication/Power Rails within the full 3 km loop of the system.
2.7 System Interaction
The User Interface consists of:
•
Interface software with three ways to access:
Touchscreen for normal system operation, maintenance and configuration
Web Server for remote access to view normal system operation
PC Configuration Software (optional) for convenient system configuration
•
Accept and reset buttons on the front panel of the Touchpoint Pro Controller
•
Power, Alarm, Fault and Inhibit LEDs on the front panel of the Touchpoint Pro Controller
•
Buzzer on the Touchpoint Pro Controller
Further System Interfaces consist of:
•
Two master relays, System Failure and System Fault
•
Connections for SD Card and USB memory device
•
10/100 Mbps Ethernet connection
•
Optional digital bus interface