10. Specifications
WARNING
Do not disconnect terminals or remove modules when energised.
(Class 1 Div.2, Class 1 Zone 2, and Zone 2 [ATEX])
AVERTISSEMENT
Ne pas déconnecter les terminaux ou supprimer les modules lorsque l’appareil est
sous tension.
(Classe 1 Div.2, Classe 1 Zone 2, et Zone 2 [ATEX])
This wall mounted enclosure is certified for use in hazardous areas / locations (Class 1 Div.2, Class 1
Zone 2, and Zone 2 [ATEX]). This enclosure can only be used as a remote unit due to its classification,
and no User Interface option is available.
This unit is IP 66 Type 4 & 4X, Class 1 (grounded), and can be installed indoors or outdoors in a Pollution
Degree 4 environment, and can be exposed to rain, snow and direct sunlight.
The upper T
a
may be reduced dependent on internal power dissipation. See Rating Plate for details.
Part Number
TPPR-V-1241
Material
Stainless Steel
Dimensions (H x W x D)
780 x 510 x 300 mm
Weight
42 Kg (Basic Unit)
Operating Conditions
-40 to +65 °C (T
a
), 0 – 100 %RH (condensing)
Power Supplies
24 VDC Nominal (18 – 32 VDC), 0 – 20 A max.
Pmax
See Rating Plate
10.3 Floor Standing Enclosures
WARNING
Protect from direct exposure to precipitation and sunlight.
AVERTISSEMENT
Protéger des expositions directes au soleil et de la pluie.
Ventilated enclosures are IP20, Type 1, Class 1 (grounded), installation category 2, and must only be
installed in a place that provides a Pollution Degree 2 environment. I.e. places that afford protection from
rain, snow and direct sunlight. Such an environment would include laboratories, offices and Control rooms.
Non-ventilated (sealed) enclosures are IP56, Type 4 & 12, Class 1 (grounded), installation category 2, and
can be installed indoors or outdoors in a Pollution Degree 3 environment that affords total protection from
rain, snow and direct sunlight.
The upper T
a
may be reduced dependent on internal power dissipation. See Rating Plates for details.