Configurable Parameter Reference Guide
MAN0984_Iss 4_01/19
Touchpoint Plus
Pt. No. 3011M5001
139
Technical Handbook
Parameter Name
Parameter
Description
Applies
to
Read/
Write
Range
Default Value
Remark
Signal Fault Max.
maximum fault current from mA output
sensor
mA Input R/W
0~24
1.1 mA
Signal Warning Min.
minimum warning current from mA output
sensor
mA Input R/W
0~24
2.9 mA
if min/max is set to zero, mA
input board will not detect
warning condition.
Signal Warning Max.
maximum warning current from mA output
sensor
mA Input R/W
0~24
3.1 mA
Alarm 1 Function
Threshold, STEL, TWA
mA Input R/W
0~2
Threshold
Threshold=0, STEL=1,
TWA=2
Alarm 2 Function
Threshold, STEL, TWA
mA Input R/W
0~2
Threshold
Threshold=0, STEL=1,
TWA=2
Alarm 3 Function
Threshold, STEL, TWA
mA Input R/W
0~2
Threshold
Threshold=0, STEL=1,
TWA=2
Target Zero Range
Number
mA Input R/W
0~100000
0
Write available when:
Detector Name- User
Detector.
Channel Enable
Channel Enable/Disable
mV Input R/W
Disable/Enable
Disable
Channel Number
Channel designate Number
mV Input R/W
1~16
-
An unique number
(Auto assigning 1~16 LED )
Channel ID will be
automatically assigned
Channel Tag
Channel description tag (25 characters)
mV Input R/W
Alphanumeric
Character
Range
50 chars
Detector Name
20 characters
mV Input R/W
Alphanumeric
Character
Range
40 chars
Write available when:
Detector Name- User
Detector