![Honeywell Touchpoint Plus Скачать руководство пользователя страница 101](http://html.mh-extra.com/html/honeywell/touchpoint-plus/touchpoint-plus_technical-handbook_150867101.webp)
Touchpoint Plus User Guide
MAN0984_Iss 4_01/19
Touchpoint Plus
Pt. No. 3011M5001
101
Technical Handbook
7.17
Monitoring TPPL via the Optional Web Interface
The Web Interface is an optional external PC interface tool that provides remote web clients with TPPL data in real
time.
The following browsers are currently supported:
•
Chrome
•
Internet Explorer 10, Internet Explorer 11
•
Internet Explorer 8, Internet Explorer 9 (Trend / Plot is not available)
•
Safari
•
Other browsers may work but their performance may vary.
Note:
Contact Honeywell Support (refer to back page of this manual) if a browser security update causes
performance issues.
7.17.1
Web Interface Configuration
The Web Interface supports two concurrent web clients. Further users may connect, but performance may be
degraded.
The TPPL Default IP address is
192.168.0.100
. To change the IP address refer to Ch.6.11 Network Settings for WEB
and MODBUS TCP.
The Web Interface shows the current TPPL status as follows:
•
Channel List View
shows up to six inputs and events with automatic scrolling
•
Channel Summary View
shows total counts for alarm 1, alarm 2, alarm 3, fault, warning and inhibits
•
Channel Output View
shows up to eight outputs and events
Key to examples below:
•
Channel marking in red one or more input channels are in
Alarm
•
Channel marking in yellow one or more channels are in
Fault
•
Channel marking in orange one or more channels are in
Inhibit
•
Channel marking in blue one or more channels are in
Warning
CAUTION
Windows XP has known security issues and should not be used with TPPL.
WARNING
The data from Touchpoint Plus web interface should not be used for safety relevant purposes