Repairs, Replacements and Upgrades
MAN0984_Iss 4_01/19
Touchpoint Plus
Pt. No. 3011M5001
118
Technical Handbook
11)
Touch
Menu>Maintenance>Power-off>Yes
.
12)
Switch off and isolate the TPPL power supplies.
13)
Open the TPPL enclosure door.
14)
Replace the backup SD Card with the original or a spare card.
15)
Close and secure the enclosure door and return the system to normal operation.
16)
See and touch the SD Card Icon to confirm it has sufficient space to record events.
9.6
How to Update Firmware
Firmware and software updates should normally be carried out only by a Honeywell trained Engineer or a qualified
Engineer trained in accordance with this Technical Manual.
9.6.1
How to Check Firmware Compatibility
1)
Touch
Menu>Information>System information
.
2)
Note down the Serial Number from screen one and the Software Information from screen two. Touch Next to tab
through screens.
3)
Contact your local service representative and relay the information above. They can check compatibility and offer
upgrade advice and download information (see next chapter).
CAUTION
Gas Detection will be inoperative during this procedure so alternative site safety arrangements should be
made.
CAUTION
Before starting the firmware update, confirm that the new firmware is compatible with both the installed I/O
Module firmware and the Main module (see below).