STT700 Temperature Transmitter
User’s Manual
Revision 1
Input2 Out Of Range
Measured value of Sensor2
is out of range
Input 2 temperature is greater than Sensor 2
URL or less than Sensor 2 LRL.
Set when the input at second sensor is either
under range or over range
Watchdog reset
Watchdog has reset (it may
be due to FW failure or HW
failure)
Controller Watchdog has reset
Supply Voltage Fault
MCU or DAC reference
voltages are beyond limits
This is set when one of the supply voltages
(DAC loop / MCU) in the device is outside its
specification limits. Check the transmitter
supply voltage
SIL Diagnostics
RAM / NVM database
corrupt
Advance diagnostics data is corrupted. Power
cycle the device