Page 24
STT700 Temperature Transmitter
User’s Manual
Revision 1
4. Startup
4.1.1. Overview
This section identifies typical startup tasks the STT700 temperature transmitter and includes the
procedure for running an optional analog output check.
4.1.2. Startup Tasks
After completing the installation and configuration tasks for a transmitter, you are ready to startup the
process loop. Startup usually includes:
Setting initial resistance, based on actual temperature (RTD sensor types only)
Reading inputs and outputs
Applying process inputs to the transmitter.
You can also run an optional output check to
wring out
an analog loop and check out individual
Process Variable (PV) outputs in Digitally Enhanced (DE) mode before startup.
The actual steps in a startup procedure vary based on the type of transmitter and the measurement
application. In general, the procedures in this section are based on using Honeywell MC Toolkit, with
a HART or DE variant, to check the transmitter input and output under static process conditions, and
make adjustments as required initiating full operation with the running process.
4.1.3. Output Check Procedures
The Output Check comprises the following procedures:
The Loop Test procedure checks for continuity and the condition of components in the output
current loop.
The Trim DAC Current procedure calibrates the output of the Digital-to-Analog converter for
minimum (0%) and maximum (100%) values of 4 mA and 20 mA, respectively. This
procedure is used for transmitters operating online in analog mode to ensure proper operation
with associated circuit components (for example, wiring, power supply, control equipment).
Precision test equipment (an ammeter or a voltmeter in parallel with precision resistor) is
required for the Trim DAC Current procedure.
The Apply Values
procedure uses actual Process Variable (PV) input levels for calibrating
the range of a transmitter. The PV is carefully adjusted to stable minimum and maximum
levels, and the Lower Range Limit Value (LRV) and Upper Range Limit Value (URV) are
then set by commands from the MC Toolkit.
The transmitter does not measure the given PV input or update the PV output
while it operates in the Output mode.
Содержание STT700 STT700
Страница 41: ...Revision 1 STT700 Temperature Transmitter User s Manual Page 33 ...
Страница 45: ...Revision 1 STT700 Temperature Transmitter User s Manual Page 37 ...
Страница 46: ...Page 38 STT700 Temperature Transmitter User s Manual Revision 1 ...
Страница 47: ...Revision 1 STT700 Temperature Transmitter User s Manual Page 39 ...
Страница 48: ...Page 40 STT700 Temperature Transmitter User s Manual Revision 1 ...
Страница 56: ...Page 48 STT700 Temperature Transmitter User s Manual Revision 1 A 6 Control Drawing ...
Страница 57: ...Revision 1 STT700 Temperature Transmitter User s Manual Page 49 ...
Страница 58: ...Page 50 STT700 Temperature Transmitter User s Manual Revision 1 ...
Страница 59: ...Revision 1 STT700 Temperature Transmitter User s Manual Page 51 ...