6.3.2. Troubleshooting with HART communicator
Troubleshooting the STT700 HART transmitter loop is greatly simplified by connecting a HART
Communicator in the termination area near the receiving instrument. Also connect a digital volt
meter (DVM), at the termination area for the receiving instrument, to confirm a similar signal is
coming from the field and power is available on the two wires of the 4-20 mA loop. This isolates
the problem to either field loop or receiving instrument/power supply/wiring/safety barriers etc. If
the original symptom was an unstable input, it could be a loose connection on the receiving side.
Assuming the above confirms a field loop problem, the likely causes/actions are given below.
Condition
Analysis
Recommended Corrective Action
Diagnostics Failure.
A critical failure has been
detected on the HART
Electronics.
Use a HART device
communicator to read the
detailed status information from
the transmitter. Refer to the
appropriate manual for more
details about the possible failure
causes.
Power cycle the transmitter and if problem
persists replace the transmitter.
DAC Failure.
A critical failure has been
detected on the HART
Electronics.
Use a HART device
communicator to read the
detailed status information from
the transmitter. Refer to the
appropriate manual for more
details about the possible failure
causes.
Power cycle the transmitter and if problem
persists replace the transmitter.
Sensor Input Failure.
A critical failure has been
detected on the HART
Sensor Inputs.
Use a HART device
communicator to read the
detailed status information from
the transmitter. Refer to the
appropriate manual for more
details about the possible failure
causes.
If detail status indicate input fault (open,
short...), correct the root error by checking
the input connection to the transmitter and
sensor type configuration.
If problem persists even after verifying the
input connection and sensor input type
configuration, replace the transmitter.
Configuration Corrupt.
A critical failure has been
detected on the HART
Electronics.
Use a HART device
communicator to read the
detailed status information from
the transmitter. Refer to the
appropriate manual for more
details about the possible failure
causes.
Power cycle the transmitter and if problem
persists replace the transmitter.
For DE please refer to STT700 HART/DE option manual, #34-TT-25-18.
Содержание STT700 STT700
Страница 41: ...Revision 1 STT700 Temperature Transmitter User s Manual Page 33 ...
Страница 45: ...Revision 1 STT700 Temperature Transmitter User s Manual Page 37 ...
Страница 46: ...Page 38 STT700 Temperature Transmitter User s Manual Revision 1 ...
Страница 47: ...Revision 1 STT700 Temperature Transmitter User s Manual Page 39 ...
Страница 48: ...Page 40 STT700 Temperature Transmitter User s Manual Revision 1 ...
Страница 56: ...Page 48 STT700 Temperature Transmitter User s Manual Revision 1 A 6 Control Drawing ...
Страница 57: ...Revision 1 STT700 Temperature Transmitter User s Manual Page 49 ...
Страница 58: ...Page 50 STT700 Temperature Transmitter User s Manual Revision 1 ...
Страница 59: ...Revision 1 STT700 Temperature Transmitter User s Manual Page 51 ...