Page 42
STT700 Temperature Transmitter
User’s Manual
Revision 1
A4. Hazardous Locations Certifications
MSG
CODE
AGENCY
TYPE OF PROTECTION
Electrical
Parameters
Ambient
Temperature
F1
FM
Approvals
TM
(USA)
Intrinsically Safe
Certificate: 17US0112X
Class I Division 1, Groups A, B, C, D; T6 .. T4
Class I Zone 0 AEx ia IIC T6.. T4 Ga
Note 2
T6: -40
o
C to +40
o
C
T5: -40
o
C to +55
o
C
T4: -40
o
C to +70
o
C
Non-Incendive and Zone 2 Intrinsically Safe
Certificate: 17US0112X
Class I, Division 2, Groups A, B, C, D; T6.. T4
Class I Zone 2 AEx nA IIC T6.. T4 Gc
Class I Zone 2 AEx ic IIC T6.. T4 Gc
Note 1
T6: -40
o
C to +40
o
C
T5: -40
o
C to +55
o
C
T4: -40
o
C to +85
o
C
F2
(No EU
Meter)
FM
Approvals
TM
(USA)
Explosion proof
Certificate: 17US0112X
Class I, Division 1, Groups A, B, C, D; T6.. T5
Dust Ignition Proof:
Class II, III, Division 1, Groups E, F, G; T6.. T5
Class 1, Zone 1, AEx db IIC T6.. T5 Gb
Zone 21, AEx tb IIIC T 95
o
C Db
Note 1
T6: -40
o
C to +65
o
C
T95
o
C/T5: -40
o
C to +85
o
C
Intrinsically Safe
Certificate: 17US0112X
Class I, II, III, Division 1, Groups A, B, C, D,
E, F, G; T6.. T4
Class I Zone 0 AEx ia IIC T6.. T4 Ga
Class I Zone 2 AEx ic IIC T6.. T4 Gc
Note 2
T6: -40
o
C to +40
o
C
T5: -40
o
C to +55
o
C
T4: -40
o
C to +70
o
C
Non-Incendive and Zone 2 Intrinsically Safe
Certificate: 17US0112X
Class I, Division 2, Groups A, B, C, D; T6.. T4
Class I Zone 2 AEx ic IIC T6.. T4 Gc
Note 1
T6: -40
o
C to +40
o
C
T5: -40
o
C to +55
o
C
T4: -40
o
C to +85
o
C
Enclosure:
Type 4X/ IP66/ IP67
F2
(W/ EU
Meter)
FM
Approvals
TM
(USA)
Explosion proof
Certificate: 17US0112X
Class I, Division 1, Groups A, B, C, D; T6.. T5
Dust Ignition Proof:
Class II, III, Division 1, Groups E, F, G; T6.. T5
Class I, Zone 1, AEx db IIC T6.. T5 Gb
Zone 21, AEx tb IIIC T 95
o
C Db
Note 1
T6: -40
o
C to +65
o
C
T95
o
C/T5: -40
o
C to
+85
o
C
Intrinsically Safe
Certificate: 17US0112X
Class I, II, III, Division 1, Groups A, B, C, D,
E, F, G; T4
Class I Zone 0 AEx ia IIC T4 Ga
Note 2
T4: -40
o
C to +70
o
C
Non-Incendive and Zone 2 Intrinsically Safe
Certificate: 17US0112X
Class I, Division 2, Groups A, B, C, D; T4
Class I Zone 2 AEx ic IIC T4 Gc
Note 1
T4: -40
o
C to +85
o
C
Enclosure:
Type 4X/ IP66/ IP67
Содержание STT700 STT700
Страница 41: ...Revision 1 STT700 Temperature Transmitter User s Manual Page 33 ...
Страница 45: ...Revision 1 STT700 Temperature Transmitter User s Manual Page 37 ...
Страница 46: ...Page 38 STT700 Temperature Transmitter User s Manual Revision 1 ...
Страница 47: ...Revision 1 STT700 Temperature Transmitter User s Manual Page 39 ...
Страница 48: ...Page 40 STT700 Temperature Transmitter User s Manual Revision 1 ...
Страница 56: ...Page 48 STT700 Temperature Transmitter User s Manual Revision 1 A 6 Control Drawing ...
Страница 57: ...Revision 1 STT700 Temperature Transmitter User s Manual Page 49 ...
Страница 58: ...Page 50 STT700 Temperature Transmitter User s Manual Revision 1 ...
Страница 59: ...Revision 1 STT700 Temperature Transmitter User s Manual Page 51 ...