SPYDER MODEL 5 ENGINEERING TOOL
–
USER GUIDE
65
31-00282ES-01
Manual Creation and Mapping of Reference Points (A)
Example:
Two IRM controllers and a wall module are on the MSTP bus in master-slave configuration:
•
WEB-RL6N (Master)
•
WEB-RS5N (Slave)
•
External BACnet wall module
o
The WEB-RL6N master controller:
-
reads the window contact status [EffWindow] from the slave controller via RefIn
-
reads the room temperature [ExtWmRmTemp] from the BACnet Wall Module via RefIn
-
writes the occupancy status [EffOccMd] to an external BACnet Wall Module via RefOut
o
The RS5N slave controller:
-
reads the fan output status [FanStage] of the staged fan (slow, medium, high) from the master
controller via RefIn
Reference Inputs
Based on the example above, the reference input functions of the WEB-RL6N master controller are described in the
following.
•
The WEB-RL6N master controller
-
reads the window contact status [EffWindow] from the slave controller via RefIn
-
reads the room temperature [ExtWmRmTemp] from the BACnet Wall Module via RefIn
NOTE: The read function of the WEB-RS5N slave controller is described using the automatic creation via drag &
drop
(see “
Automatic Creation and Mapping of Reference Points via Drag & drop (B)
Procedure
1.
Note the device IDs of the WEB-RL6N master and WEB-RS5N slave controllers, in this case ´5003` and ´5001`
(displayed in the Discovered and Database pane).
2.
In the
Nav
tree, expand the BACnet network and browse to the
Points
folder of the RS5N slave controller.