background image

  

I56-3433-004 

 

 04-12

In a room with a smooth ceiling, detectors should be spaced between 30 and 
60 feet (9.1 to 18.3 m). One-half that spacing between the beam and the side-
wall may be used as a guide. See Figure 1. The beam detector can be mounted 
with the transmitter/receiver on one wall and the reflector on the opposite 
wall, or both suspended from the ceiling, or any wall/ceiling combination. 
In the case of the ceiling mount, the distance from the end walls should not 
exceed one-quarter of the selected spacing (7.5 ft. [2.3 m] maximum if the 
spacing is 30 ft. [9.1 m] ). See Figure 2.

FIGURE 1. SPACING FOR SMOOTH CEILING (SIDE VIEW):

1

/

2

 S

S

12 - 18 IN.

(0.3 - 0.46M)

WALL

C0254-00

FIGURE 2. SPACING FOR SMOOTH CEILING (TOP VIEW):

16 FT. (5M) MINIMUM

328 FT. (100M) MAXIMUM

Tx/Rx

REFLECTOR

S

Tx/Rx

REFLECTOR

1

/

2

 S MAXIMUM

1

/

4

 S

MAX.

C0255-00

In the case of peaked or sloped ceilings, codes may specify spacing of detec-
tors by using horizontal spacing from the peak of the roof or ceiling. Figures 
3 and 4 show the spacing for both the shed type and peaked type sloped 
ceilings.

On smooth ceilings, beam smoke detectors should generally be mounted be-
tween 12 and 18 inches (0.3 to 0.46 m) from the ceiling. In many cases, how-
ever, the location and sensitivity of the detectors shall be the result of an 
engineering evaluation that includes the following: structural features, size 
and shape of the room and bays, occupancy and uses of the area, ceiling 
height, ceiling shape, surface and obstructions, ventilation, ambient environ-
ment, burning characteristics of the combustible materials present, and the 
configuration of the contents in the area to be protected. As a general rule, 
reflective objects such as ductwork or windows should be a minimum of 15 
inches (38.1 cm) from the path of the beam.

FIGURE 3. SLOPED CEILING (SHED TYPE):

S

3 FT.

(0.9M)MAX.

S

1

/

2

 S MAX.

Tx/Rx

REFLECTOR

C0256-00

FIGURE 4. SLOPED CEILING (PEAKED TYPE):

1

/

2

 S

S

S

1

/

2

 S

3 FT. (0.9M)

MAX.

3 FT. (0.9M)

MAX.

MOUNT SPOT DETECTOR 

ANYWHERE IN THIS 

AREA  AT LEAST 4 IN. (100 mm) 

VERTICALLY FROM PEAK

Tx/Rx

REFLECTOR

C0257-04

MOUNTING LOCATIONS

Beam detectors require a stable mounting surface for proper operation. A sur-
face that moves, shifts, vibrates, or warps over time will cause false alarm or 
trouble conditions. Initial selection of a proper mounting surface will elimi-
nate false alarms and nuisance trouble signals.

Mount the detector on a stable mounting surface, such as brick, concrete, 
a sturdy load-bearing wall, support column, structural beam, or other sur-
face that is not expected to experience vibration or movement over time. DO 
NOT MOUNT the beam detector on corrugated metal walls, sheet metal walls, 
external building sheathing, external siding, suspended ceilings, steel web 
trusses, rafters, nonstructural beam, joists, or other such surfaces.

In cases where only one stable mounting surface as defined above can be 
used, the transmitter/receiver unit should be mounted to the stable surface 
and the reflector should be mounted to the less stable surface. The reflec-
tor has a much greater tolerance for the unstable mounting locations defined 
above.

MOUNTING INSTRUCTIONS

The transmitter/receiver unit may be mounted over a recessed junction box. 
The cavity behind the detector is then used for routing of the wiring from the 
junction box to the terminal blocks on the detector. The transmitter/receiver 
unit should be mounted to the wall such that unit covers the recessed junc-
tion box in the wall completely. If the junction box is not recessed then you 
may use the surface mount kit (BEAMSMK). See the BEAMSMK installation 
instructions for surface mounting instructions. The transmitter/receiver unit 
can be mounted to the wall using the supplied drilling template (see Appendix 
II). The detector base has 4 primary mounting keyholes, one in each corner of 
the base. All four hole locations should be used to provide a secure mounting. 
The outer housing of the beam detector is held to the base using four screws. 
In order to mount the detector you must remove the outer housing first.

The reflector can be mounted to the wall using the supplied drilling template 
(see Appendix III). The reflector has 4 mounting holes, one in each corner. 
All four hole locations should be used to provide a secure mounting. The 
reflector must be mounted such that it is within 10° in both the X and Y 
planes of the transmitter/receiver unit. See Figure 5a. The reflector must also 
be mounted such that the plane of the reflector is perpendicular to the optical 

Содержание SK-Beam

Страница 1: ...ication every 5 sec LED flashing SLC 24 V Max Alarm LED on 8 5 mA Max Max Trouble LED on 4 5 mA Max Max Alignment 20 mA Max External Supply SK Beam T only VOLTAGE 15 to 32 VDC CURRENT 0 5 A Max Remote Output alarm VOLTAGE 15 to 32 VDC NOTE Output voltage same as device input voltage CURRENT 15 mA maximum 6 mA minimum NOTE Output current is limited by 2 2 kΩ resistor GENERAL DESCRIPTION Model SK Be...

Страница 2: ... with the long range reflector kit BEAMLRK BEAMSMK The BEAMSMK allows reflected beam detectors to be mounted when surface wiring is used This kit must be used when mounting the transmitter receiver unit with the multi mount kit BEAMMMK 6500 MMK The 6500 MMK provides a heavy duty multi mount bracket for installations prone to building movement or vibration It offers similar tilt and swivel flex ibi...

Страница 3: ... A sur face that moves shifts vibrates or warps over time will cause false alarm or trouble conditions Initial selection of a proper mounting surface will elimi nate false alarms and nuisance trouble signals Mount the detector on a stable mounting surface such as brick concrete a sturdy load bearing wall support column structural beam or other sur face that is not expected to experience vibration ...

Страница 4: ...lector In cases where operation through panes of glass cannot be avoided some spe cific installation practices can help to minimize the effects of the glass These practices include avoid penetration of multiple panes of glass position the glass so that it is not perpendicular to the line of sight between the detector and the reflector A minimum of 10 off perpendicular should be considered and make...

Страница 5: ... to ensure a successful installa tion Proper application mounting alignment and set up will minimize false alarms and nuisance trouble signals PRE ALIGNMENT CHECKLIST Insure that both the detector and reflector are mounted securely to stable surfaces Insure that all wiring is correct Insure that terminal blocks are fully seated into their receptacles on the detector Complete any wiring dressing to...

Страница 6: ...ment process The display will continue to read Lo until the detector receives enough light from the reflector to function properly 3 With the display indicating a numeric value begin adjusting the horizon tal adjustment wheel in the direction that increases the number on the display When the number starts decreasing continue rotating the knob 3 4 revolutions past the peak value to confirm that you...

Страница 7: ... the outer housing 4 Press the reset button making sure to avoid blocking the line of sight between the detector and reflector The yellow LED will begin to blink for about 20 seconds At this time the detector is making its final gain adjustment to compensate for the effects of installing the outer housing When the gain adjustment is complete the yellow LED will turn off and the green LED will begi...

Страница 8: ... perform a complete reflector blockage test as in step 4 of the Instal lation Alignment procedure to insure that the pathway between the detector and reflector is clear NOTE For the SK Beam this test does not satisfy the requirements of NFPA72 for periodic maintenance and sensitivity verification of beam type detectors For the SK Beam T this test in conjunction with the complete reflector block ag...

Страница 9: ...onse Off 4 Quick Blinks Blink Blink Off Beam Blockage Remove blockage Faulty unit Initialization Power on Off Blink until complete Blink Blink Off Apply Power from discharged state Initialization alignment exit Off Blink until complete Blink Blink Off Depressing RESET switch after alignment Local Test SK Beam T Pass Result On Blinking the amount of drift used Off On Off Panel or RTS451 RTS451KEY R...

Страница 10: ...10 I56 3433 004 04 12 ...

Страница 11: ...11 I56 3433 004 04 12 APPENDIX II DETECTOR DRILLING TEMPLATE 4 345 6 190 157 mm 110 mm Scale 1 1 C0278 00 ...

Страница 12: ...12 I56 3433 004 04 12 ...

Страница 13: ...13 I56 3433 004 04 12 APPENDIX III REFLECTOR DRILLING TEMPLATE 5 512 140mm 8 465 215mm Scale 1 1 C0279 00 ...

Страница 14: ...erence when the equip ment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to corr...

Отзывы: