background image

Release Date: 04/01/2021 

Rev:01 

TFD-1251 

INTELLIGENT ADDRESSABLE OPTICAL SMOKE DETECTOR 

WITH BUILT-IN ISOLATOR 

Installation & User Manual 

 

Critical Warnings 
General 

 

Read this manual with care before operating the device and keep it for further reference. 

 

Comply with all warnings and measures provided in the manual. Follow all respective operation and usage 
instructions. 

 

Keep the devices away from water and humidity. 

 

Ortam Şartları

 

Do not operate the device under extreme temperature conditions that fall outside the following values. 

Temperature: Between -

10°C 

and +70

°C

 

Relative Humidity: Max. 

95% RH 

 

 

Service 

Do not attempt to repair the device on your own, you may be exposed to electric shock in case you open the 
device housing.  

Contact your dealer or authorized service in case of a failure. Technical interventions to the device must be 

carried out by qualified personel of authorized service. 

 
 
 

 
 

Failures That Require Service Intervention 

Contact your authorized service or dealer in case of a failure or in following cases. 

 

If the power line or plug is damaged, 

 

If any liquid has leaked or a substance has fallen into the device, 

 

If the device is exposed to water or rain, 

 

If the device is dropped or the housing is damaged, 

 

If there is significant performance change in the device, 

 

If the device is not operating normally according to the operating instructions in the user manual 

Call the service since erroneous operations may cause further failures. 

 

What You Can Do On Your Own  

Do not attempt to repair the device on your own since you may  be exposed to electric  shock in case you 

open  the  device  housing.  Contact  your  dealer  or  authorized  service  in  case  of  a  failure.  Technical 
interventions to the device must be carried out by qualified personel of authorized service. The device must 

be cleaned with a dry cloth. No chemical must be used for cleaning purposes. 

 

Handling and Transportation 

The device must be handled with care in manner that it does not get exposed to impacts and liquid influx. 

The damages that may occur during improper handling are out of guarantee.  

 

Human and Environment Health 

This device does not contain any chemical or biological substance that may harm human health.  

 

 

General Features

 

 

 

Advanced smoke detection algorithm that minimizes false alarms 

 

Denial of temporary signals that may be perceived as alarm 

 

Adaptive protection by continuous sampling of the present environment 

 

Debris algorithm that perceives inoperability due to dirt accumulation and respective warning 

 

Easy to clean smoke chamber 

 

External notification light connection means 

 

Two LED’s used for state indication purposes

 

 

15s starting time 

 

Three different sensitivity settings that can be selected on the panel 

 

Compatible with TFA-0120 Universal Detector Base  

 

 
 

Technical Specifications

 

 

Power Input 

18V(min) 

 32V(max) 

Average (Quiescent) Current Consumption 

80uA (@32V) 

Maximum Alarm Current 

3mA (@32V) 

Maximum External Device Current 

10mA (@32V) 

 (2K2 resistance limit) 

Alarm Levels (appr.) 

H: 0.12, M: 0.15, L: 0.18 dB/m 

Operating Temperature Range 

-10

C ~ 55

C (14

F ~ 131

F) 

Humidity 

95% RH (max.) 

Size (mm) 

Ø110, h42

 

Housing Material 

White Color, ABS Plastic 

Attached Cable Cross-section 

0.4mm ² ~ 

1.5

mm ²

 

Weight (wit base / without base) 

183 gr / 125 gr 

Starting Time 

15 sec 

 

Isolator

 

Average Current Consumption (Normal Op.) @24V 

15uA 

Vmax.  

32V 

Vnom. 

28V 

Vmin. 

15V 

Vso_max. 

18V 

Vso_min. 

9V 

Vsc_max. 

5V 

Vsc_min. 

0,7V 

Ic_max. 

0,5A 

Is_max.  

3A 

IL_max. 

0,026A 

Zc_max. 

0,026Ω

 

 
 
 
 
 
 
 
 
 
 
 

 
 

Warning:

 Do not attempt to take the card out of its plastic protection. It is sealed solely for your safety. 

Users must avoid intervention. 

Отзывы: