IFP-2000 Installation Manual
5-8
151430
combination of both repeater types can be used. See Figure 5-7, Figure 5-8, Figure 5-9,
and Figure 5-10 for repeater wiring examples.
5.4.2.1 Network Repeater Cable Requirements
Cable requirements for wire runs between repeaters.
1. All fiber cable must be multimode 62.5/125 micron cable with ST type connectors. It is
important that the cable be verified to contain no more then 8dB of loss including the
connectors.
2. Twisted pair wiring must be UNSHIELDED twisted pair conductor cable. The wire gauge
must be 18 AWG or larger. The maximum wire length is 3000 ft. between repeaters.
5.4.2.2 Unshielded Twisted Pair Wiring between Multiple Panels
Unshielded twisted pair wiring between multiple panels is shown in Figure 5-7. Class A
wiring is shown with a dotted line.
Figure 5-7 Twisted Pair Wiring Configuration
Class A
Wiring
firealarmresources.com
Содержание Silent Knight IFP-2000 Module 3
Страница 2: ...firealarmresources com ...
Страница 12: ...IFP 2000 Installation Manual viii firealarmresources com ...
Страница 22: ...IFP 2000 Installation Manual 1 10 151430 firealarmresources com ...
Страница 26: ...IFP 2000 Installation Manual 2 4 151430 firealarmresources com ...
Страница 31: ...Before You Begin Installing 151430 3 5 Figure 3 1 Wire Routing Example firealarmresources com ...
Страница 100: ...IFP 2000 Installation Manual 5 14 151430 firealarmresources com ...
Страница 194: ...IFP 2000 Installation Manual 10 20 151430 firealarmresources com ...
Страница 210: ...IFP 2000 Installation Manual 12 8 151430 firealarmresources com ...
Страница 230: ...IFP 2000 Installation Manual A 14 firealarmresources com ...
Страница 232: ...IFP 2000 Installation Manual B 2 151430 firealarmresources com ...
Страница 236: ...firealarmresources com ...
Страница 237: ...firealarmresources com ...