Honeywell Silent Knight IFP-2000 Module 3 Скачать руководство пользователя страница 38

IFP-2000 Installation Manual

3-12

151430

JumpStart AutoProgramming automatically selects some options for SLC devices (see “JumpStart 
AutoProgramming” section of this chart). You can change options selected by JumpStart 
AutoProgramming, if necessary and further customize input point options.

U

Program type of switch (manual pull, fire drill, and so on), if necessary. 
(JumpStart AutoProgramming assigns all switches as Manual Pull type.)

9.5

U

If the installation includes duct detectors, program detector type. 
(JumpStart AutoProgramming does not distinguish duct detectors from 
ordinary smoke detectors.)

9.5

U

Assign a name (or description) to the point.

9.5.3.1

U

Assign input points to zones, if necessary. (JumpStart AutoProgramming 
assigns all input points to Zone 1.)

9.5

Zone Configuration

U

Add the zone to the system if it does not already exist.

9.3.2

U

Program a name (or description) for the zone.

9.3.1.1

U

Select alarm delay options (detection characteristics) for zone.

9.3.1.2

U

Select heat detector trip temperature and/or smoke sensitivity level for 
photoelectric smoke detectors. (JumpStart AutoProgramming selects 150°F 
for heat detectors and Low sensitivity for smoke detectors.)

9.3.1.2

Output Point Configuration

Conventional notification circuits (circuits 1-8): 

U

Enable circuits used for notification appliances through programming, if 
necessary.

9.4.1

Conventional relay circuits (circuits 9-10):

U

Select options for relay circuits, if desired. Note: Relay circuits will always 
output continuously (constant pattern), even if assigned to an Output Group 
that uses a different output pattern.

9.4.1

Auxiliary power circuits (circuits 1-8):

U

Enable any circuit used for auxiliary power devices through programming.

9.5

U

Select type of power (door holder, constant, or resettable)

9.5

Addressable relay modules

U

Assign addressable relay modules to output groups through programming. 
(JumpStart AutoProgramming assigns all relay modules to Group 1.)

9.5

LED output points (from the 5880 LED I/O module or 5865/66 LED Annunciator)

U

Assign LED modules to output groups through programming. 

9.5.3

All output circuits (1-8):

U

Disable (set to UNUSED) any unused circuits. If you do not disable unused 
output circuits, they will cause a trouble condition (unless an EOL resistor 
is used).

9.5

U

Select a name for the point, if desired.

9.6

Output Group Configuration

U

Add the group to the system if it does not already exist.

9.4.2

U

Assign output points to the group.

9.5

U

Program a name (or description) for the group, if desired.

9.4.1.1

Select “group properties” (see below).

U

Select options for activation with system switches.

9.4.1

Task

See Sec.

(for more info.)

firealarmresources.com

Содержание Silent Knight IFP-2000 Module 3

Страница 1: ...Installation and Operations Manual MODEL IFP 2000 RPS 2000 Part Number 151430 Rev A Analog Addressable Fire System firealarmresources com ...

Страница 2: ...firealarmresources com ...

Страница 3: ...dity Therefore it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 27º C 60 80º F Verify that wire sizes are adequate for all initiating and indicating device loops Most devices cannot tolerate more than a 10 I R drop from the specified device voltage Like all solid state electronic devices this system may operate erratically o...

Страница 4: ...control panel and in rooms used by the system for the connection of alarm transmission wiring communications signaling and or power If detectors are not so located a developing fire may damage the alarm system crippling its ability to report a fire Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located...

Страница 5: ...ed Fire Alarm Systems 2 3 2 2 4 Requirements for Remote Station Protected Fire Alarm Systems Digital Alarm Communicator Transmitter DACT 2 3 Section 3 Before You Begin Installing 3 1 3 1 What s in the Box 3 1 3 2 Environmental Specifications 3 1 3 3 Electrical Specifications 3 2 3 4 Wiring Specifications 3 4 3 5 Board Assembly Diagram 3 6 3 6 Calculating Current Draw and Standby Battery 3 7 3 6 1 ...

Страница 6: ...Mounting 4 29 4 11 Vip Module Installation 4 30 4 12 Telephone Connection 4 30 4 13 Flexputs I O Circuits 4 31 4 13 1 Conventional Notification Appliance 4 31 4 13 1 1 Regulated Class B Notification Wiring 4 31 4 13 1 2 Class A Notification Wiring 4 33 4 13 2 Conventional Input Switch Circuits 4 34 4 13 2 1 Class B Inputs 4 34 4 13 2 2 Class A Inputs 4 35 4 13 3 Installing 2 Wire Smoke Detectors 4...

Страница 7: ...d Pair Repeater Wiring between Multiple Panels 5 10 5 5 Using Both Repeaters and Direct Connect Wiring on a Networked System 5 11 5 5 1 Setting the Network Terminators at Panel DIP Switches and Repeater Jumpers 5 12 5 6 Setting the Network ID for each Panel 5 13 Section 6 Network Management 6 1 6 1 Network Diagnostics 6 1 6 1 1 Ping Panel 6 1 6 1 2 Network Status 6 1 6 2 Network Programming 6 1 6 ...

Страница 8: ...tem 8 12 8 3 Programming Using the 5655 Silent Knight Software Suite 2 8 13 8 4 Programming Using an Annunciator 8 13 8 4 1 Entering Exiting Panel Programming 8 13 8 4 1 1 Moving through the Menus 8 13 8 4 1 2 Selecting Options and Entering Data 8 14 8 4 1 3 Editing Keys 8 15 8 5 Programming Menu Quick Reference 8 16 Section 9 Programming 9 1 9 1 UL 864 Programming Requirements 9 1 9 2 Modules 9 2...

Страница 9: ...liday Days 9 28 9 6 5 Miscellaneous Options 1 9 28 9 6 5 1 Water Flow Delay 9 28 9 6 5 2 Low AC Report Time 9 30 9 6 5 3 Automatic Daylight Savings Adjustment 9 30 9 6 5 4 Clock Display Format AM PM or Military 9 30 9 6 5 5 Change AC Line Frequency 9 31 9 6 6 Miscellaneous Options 2 9 32 9 6 6 1 Strobes Active when Silenced 9 32 9 6 6 2 Auto Display Oldest Event 9 32 9 6 6 3 IFP RPT Repeater Insta...

Страница 10: ...ite Annunciator and Multi Site user Access 10 14 10 7 Releasing Operations 10 15 10 7 1 Single Interlock Zone Releasing 10 16 10 7 2 Double Interlock Zone Releasing 10 17 10 8 Smoke Alarm Verification 10 18 10 9 Function Keys 10 18 10 9 1 Recording an F Key macro 10 18 10 9 2 Aborting an F Key macro recording session 10 19 10 9 3 Erasing an F Key macro 10 19 10 9 4 Using a recorded F Key macro 10 ...

Страница 11: ...3 Installation Records 13 1 13 1 Detector and Module Point Record 13 1 13 2 Conventional Output Point Record 13 6 Appendix A Compatible Devices 14 1 Appendix B Special Characters Lists B 1 Silent Knight Fire Product Warranty and Return Policy firealarmresources com ...

Страница 12: ...IFP 2000 Installation Manual viii firealarmresources com ...

Страница 13: ... to a maximum of 636 points The SLC s supports Intelligent Device Protocol IDP analog addressable sensors and modules Each SLC supports 159 IDP sensors and 159 IDP modules to a maximum of 636 points per IFP 2000 Control panel 9 0A of output power is available through 8 sets of terminals for notification and auxiliary applications Each circuit is power limited per UL 864 and can source up to 3 0A t...

Страница 14: ...ated no more than 20 feet apart and within the same room Panels separated by more than 20 feet or located in multiple buildings use IFP RPT network repeater hardware to provide up to 3000 ft of separation with twisted pair copper wire or up to 8dB loss of signal separation for fiber optic cable All 3 methods of panel connectivity can be used within the same networked system The network architectur...

Страница 15: ...panels itself and the built in power supply It also refers to any optional 5815XL SLC expansion modules Input Point An addressable sensing device such as a smoke or heat detector or a contact monitor device Input Zone A protected area made up of input points Output Point or Output Circuit A notification point or circuit for notification appliances Relay circuits and auxiliary power circuits are al...

Страница 16: ...display up to 30 LEDs 15 red and 15 yellow 5865 4 has key switches for silence and reset and a system trouble LED 5880 LED I O Module Driver for up to 40 LEDs Interfaces with customized annunciator boards In addition the 5880 has eight generic switch input points 5883 General Purpose Relay Module Provides 10 Form C relays Designed to be driven by the 5880 Up to four 5883s can be used with each 588...

Страница 17: ...n or encounter a problem not covered in this manual contact Silent Knight Technical Support at 800 328 0103 or 763 493 6455 To order parts contact Silent Knight Sales at 800 446 6444 or 763 493 6435 in Minnesota Flexput is a trademark of Silent Knight Table 1 3 Compatible Modems Manufacturer Model US Robotics 28 8 Motorola LifeStyle 28 8 3400 series Premier 33 6 MultiTech MT19321ZDX firealarmresou...

Страница 18: ...developing on another level The amount of smoke present may be insufficient to alarm smoke detectors Smoke detectors are designed to alarm at various levels of smoke density If such density levels are not created by a developing fire at the location of detectors the detectors will not go into alarm Smoke detectors even when working properly have sensing limitations Detectors that have photoelectro...

Страница 19: ...ses to make people aware of fire alarm signals and instruct on the proper reaction to alarm signals iii In rare instances the sounding of a warning device can cause temporary or permanent hearing loss Telephone lines needed to transmit alarm signals from a premises to a central station may be out of service or temporarily out of service For added protection against telephone line failure backup ra...

Страница 20: ...d that smoke detectors be located in any room where an alarm control is located or in any room where alarm control connections to an AC source or phone lines are made If detectors are not so located a fire within the room could prevent the control from reporting a fire All fire alarm systems require notification devices including sirens bells horns and or strobes In residential applications each a...

Страница 21: ... appliances shall be protected until they enter the evacuation signaling zone that they serve Any of the following methods shall be considered acceptable as meeting these requirements 1 A 2 hour rated cable or cable system 2 A 2 hour rated enclosure 3 Performance alternatives approved by Authority Having Jurisdiction firealarmresources com ...

Страница 22: ...IFP 2000 Installation Manual 1 10 151430 firealarmresources com ...

Страница 23: ...r of devices is limited The REN number is imbedded in the FCC registration number as 10B If the IFP 2000 IFP 2000HV causes harm to the telephone network the telephone company will notify you in advance that the temporarily discontinuance of service may be required But if advance notice is not practical the telephone company will notify the customer as soon as possible Also you will be advised of y...

Страница 24: ...f the manual for additional requirements The following subsections list specific requirements for each type of installation for example Central Station Fire Alarm systems Local Protected Fire Alarm systems and so on See Section 10 7 for information on releasing operation 1 All field wiring must be installed in accordance with NFPA 70 National Electric Code 2 Use the addressable smoke detectors spe...

Страница 25: ...When two count is used detector spacing shall be cut in half you shall not use the alarm verification feature and no delay shall be used P A S feature shall be used only with automatic detectors 2 2 2 Requirements for Central Station Fire Alarm Systems 1 Use both phone lines Enable phone line monitors for both lines 2 You must program a phone number and a test time so that the IFP 2000 sends an au...

Страница 26: ...IFP 2000 Installation Manual 2 4 151430 firealarmresources com ...

Страница 27: ...important to protect the IFP 2000 control panel from water To prevent water damage the following conditions should be AVOIDED when installing the units Intended for indoor use in dry locations only Do not mount directly on exterior walls especially masonry walls condensation Do not mount directly on exterior walls below grade condensation Protect from plumbing leaks Protect from splash caused by s...

Страница 28: ...n and Aux power Circuits 0Ω O 100 mA for initiation circuits X I O 4 Flexput Circuits 24 VDC 3 0 Amp Notification and Aux power Circuits 0Ω O 100 mA for initiation circuits X I O 5 Flexput Circuits 24 VDC 3 0 Amp Notification and Aux power Circuits 0Ω O 100 mA for initiation circuits X I O 6 Flexput Circuits 24 VDC 3 0 Amp Notification and Aux power Circuits 0Ω O 100 mA for initiation circuits X I...

Страница 29: ... VDC 2 5 A resistive N A C N O N C TROUBLE Trouble Relay 24 VDC 2 5 A resistive N A C N O S SLC OUT SLC terminals 32 VDC 150 mA 0Ω S SC SLC IN Used for Class A installations 0Ω SC Ring Phone Line 1 Telco Ring N A 0Ω Tip Phone Line 1 Telco Tip Ring Phone Line 1 Premises Ring Tip Phone Line 1 Premises Tip Ring Phone Line 2 Telco Ring N A 0Ω Tip Phone Line 2 Telco Tip Ring Phone Line 2 Premises Ring ...

Страница 30: ...the panel You must route high and low voltages separately Route the wiring around the inside perimeter of the cabinet It should not cross the circuit board where it could induce noise into the sensitive microelectronics or pick up unwanted RF noise from the high speed circuits See Figure 3 1 for an example High frequency noise such as that produced by the inductive reactance of a speaker or bell c...

Страница 31: ...Before You Begin Installing 151430 3 5 Figure 3 1 Wire Routing Example firealarmresources com ...

Страница 32: ...d need to remove the board assembly for repair remove the four mounting nuts which hold the assembly in the cabinet Then lift the entire assembly out of the cabinet Do not attempt to remove the circuit boards from the metal bracket Chassis Mounting Nuts On board Annunciator To AC Trouble Relay Phone lines SLC In Out Battery Connections Network Repeater USB Ethernet Port Programming Port non power ...

Страница 33: ... mentioned in the manual refer to the device manual for the current ratings 5 Make sure that the total alarm current you calculated including current for the panel itself does not exceed 9 0 A This is the maximum alarm current for the IFP 2000 control panel If the current is above 9 0 A you will need to use a notification power expander s such as the Silent Knight 5495 or the RPS 1000 intelligent ...

Страница 34: ... R with relay Aux Pwr Standby 26 mA2 mA Alarm 87 mA2 mA SLC Standby Alarm 0 27 mA mA mA IDP Acclimate Standby Alarm 0 3 mA mA mA IDP Heat ROR mA mA Addressable SLC Modules IDP Monitor 159 max loop 636 max panel 1 Standby Alarm 0 3 mA mA mA IDP Control mA mA IDP Minimon mA mA IDP Pull SA IDP Pull DA mA mA IDP Monitor 2 Standby Alarm 0 75 mA mA mA IDP Monitor 10 Standby Alarm 3 5 mA mA mA IDP Relay ...

Страница 35: ...A VIP 50 50 watt with without VIP CE4 8 max Standby 10 mA mA Alarm 10mA mA VIP RM2000 Remote Microphone 2 max Standby 50 mA mA Alarm 125mA mA IFP RPT FO IFP RPT UTP 1 max Standby 13mA mA Alarm 13mA mA A Total System Current Auxiliary Devices3 Refer to devices manual for current rating Alarm Standby mA mA mA Alarm Standby mA mA mA Alarm Standby mA mA mA B Auxiliary Devices Current Notification Appl...

Страница 36: ...Table 3 3 Maximum Battery Standby Loads for 90 Hour Standby Note For FM installations only 3 7 Installation Tasks Overview This section provides a chart listing tasks that need to be performed when installing the IFP 2000 system The chart is intended to be a handy way for you to make sure you have completed all necessary tasks Unless noted these tasks do not have to be performed in the Table 3 2 M...

Страница 37: ...nstructions JumpStart AutoProgramming JumpStart AutoProgramming searches for expanders and SLC devices connected to the panel but not programmed into the system JumpStart AutoProgramming automatically selects some options for SLC devices See Input Point Configuration section of this chart for other options JumpStart AutoProgramming makes selections for the following options You can customize optio...

Страница 38: ...l notification circuits circuits 1 8 U Enable circuits used for notification appliances through programming if necessary 9 4 1 Conventional relay circuits circuits 9 10 U Select options for relay circuits if desired Note Relay circuits will always output continuously constant pattern even if assigned to an Output Group that uses a different output pattern 9 4 1 Auxiliary power circuits circuits 1 ...

Страница 39: ...or the enclosure should be 14 75 W x 25 H x 4 D Do NOT flush mount in a wall designated as a fire break 4 1 1 Preventing Water Damage Water damage to the fire system can be caused by moisture entering the cabinet through the conduits Conduits that are installed to enter the top of the cabinet are most likely to cause water problems Installers should take reasonable precautions to prevent water fro...

Страница 40: ...2 It may be necessary for a professional electrician to make this connection The AC terminals are rated at 120 VAC 50 or 60 Hz 5A for the IFP 2000 or 240 VAC 50 or 60 Hz 2 5A for the IFP 2000HV Figure 4 1 120 VAC Power Connection for the IFP 2000 Figure 4 2 240 VAC Power Connection for the IFP 2000HV 240 VAC Models are Labeled Here firealarmresources com ...

Страница 41: ...er your standby load calculation see Section 3 6 Wire batteries in series to produce a 24 volt equivalent Do not parallel batteries to increase the AH rating It is recommended that you replace batteries every five years Figure 4 3 Battery Connection To Control Panel Red Black Battery Jumper P N 140694 Shipped With Panel UL Recognized 12V Battery UL Recognized 12V Battery firealarmresources com ...

Страница 42: ...up batteries follow these steps 1 Mount the accessory cabinet See figure Figure 4 4 for the four cabinet mounting holes If mounting onto drywall the accessory cabinet must be mounted onto 3 4 inch ply wood This is necessary because the weight of the batteries inside the accessory cabi net could cause the cabinet to pull away from the drywall When mounting on concrete especially when moisture is ex...

Страница 43: ...he wire connections can be routed However any other cabinet knock outs on either the main control panel or the RBB AB 55 cabinet that are not previously being used may be utilized to connect conduit between the two cabinets 4 Connect battery leads to the backup battery terminals See Figure 4 6 Observe the proper polarity to prevent damage to the batteries or the control panel 5 Insert the RBB or A...

Страница 44: ...ting keyhole over the cover mounting screws See Figure 4 7 Figure 4 7 Cover Plate Mounting Keyholes and Cover Mounting Screws Alignment 7 Slide the cover into place and tighten the cover mounting screws See Figure 4 7 Cover Plate Mounting Keyholes firealarmresources com ...

Страница 45: ... If a large number of accessory mod ules are required and the worst case current draw will exceed the 2 amps total then the current draw must be distributed using RPS 1000 Power Expanders Each RPS 1000 Power Expander provides an additional SBUS with an additional 1 amp of SBUS current Wiring distance calculations are done separately for each RPS 1000 and separately for each control panel SBUS Afte...

Страница 46: ...ft 6000 ft 0 200 926 ft 2344 ft 3731 ft 5906 ft 0 300 617 ft 1563 ft 2488 ft 3937 ft 0 400 463 ft 1172 ft 1866 ft 2953 ft 0 500 370 ft 938 ft 1493 ft 2362 ft 0 600 309 ft 781 ft 1244 ft 1969 ft 0 700 265 ft 670 ft 1066 ft 1687 ft 0 800 231 ft 586 ft 933 ft 1476 ft 0 900 206 ft 521 ft 829 ft 1312 ft 1 000 Max 185 ft 469 ft 746 ft 1181 ft Maximum Resistance Ohms 6 0 Volts Total Worst Case Current Dr...

Страница 47: ...e Wiring Distance table it can be found that the available options are 370 feet maximum using 22 Gauge wire 938 feet maximum using 18 Gauge wire 1493 feet maximum using 16 Gauge wire 2362 feet maximum using 14 Gauge wire 4 4 2 Wiring Configurations Figure 4 8 illustrates SBUS 1 Class A wiring configuration and Figure 4 9 illustrates SBUS1 RA 2000 Current Draw 2 x 120 amps 240 amps RPS 1000 Current...

Страница 48: ...tions are the same as SBUS1 Figure 4 8 SBUS Class A Wiring Figure 4 9 SBUS Class B Wiring Caution For proper system supervision do not use looped wire under terminals marked A B and of the SBUS device connectors Break wire runs to provide supervision of connections firealarmresources com ...

Страница 49: ...number is limited by current draw and SBUS bandwidth usage as discussed below When installing a hardware module such as 5815XL 5824 RA 2000 5496 RPS 1000 5865 3 or 5865 4 you must use the DIP switches on the module to assign an ID to the module Address zero is an invalid address and is not allowed Figure 4 10 shows all possible DIP switch positions and their correlation to a numerical ID For examp...

Страница 50: ...ndwidth usage of a given collection of devices we have created a tool available on the Farenhyt website www farenhyt com The tool will serve as a guide to help determine how heavily loaded an SBUS is with respect to bandwidth We recommend you use this tool if you plan to have more than eight SBUS devices per SBUS Remember to include devices that are on RPS 1000 SBUS repeaters in your list of devic...

Страница 51: ...on involves the following steps 1 Make sure power is off at the panel 2 Mount the RA 2000 in the desired location see Section 4 6 1 3 Connect the RA 2000 to the panel see Section 4 4 4 Use the DIP switches on the back of the RA 2000 to assign an SBUS ID to the RA 2000 see Section 4 5 1 5 The RA 2000 module must be added to the system through programming JumpStart AutoProgramming will add the modul...

Страница 52: ...h Mounting This section of the manual describes flush mounting Follow these steps to flush mount the RA 2000 1 The back box dimensions are 9 9 32 w x 8 3 8 h The minimum depth 2 The back box can be mounted prior to the complete installation of the RA 2000 using any of the mount ing holes shown in Figure 4 12 Figure 4 12 Back Box Mounting Holes Mounting Holes Mounting Holes firealarmresources com ...

Страница 53: ...re 4 13 Back Box Knockout Locations 3 Wire the Annunciator board to the main control panel See Figure 4 9 4 Attach the annunciator and door assembly to back box as shown in Figure 4 14 using the supplied screws Figure 4 14 Attaching Annunciator Door Assembly to Backbox Wire Knockouts Wire Knockouts Wire Knockouts firealarmresources com ...

Страница 54: ...shaped mounting hole Do not tighten all the way See Figure 4 15 Place a level on top of the back box with the back box level insert the rest of the mounting screws Figure 4 15 Back Box Surface Mount Holes 3 Run wires to the control panel 4 Place the trim ring over the back box as shown in Figure 4 16 Figure 4 16 Installing Trim Ring 5 Attach the Door assembly to the back box using screws provided ...

Страница 55: ... in Section 4 6 2 replace the electronic assembly in the back box Place the bezel over the back box and tighten the set screws on the bezel 4 6 2 Model RA 2000 Connection to the Panel Connect the RA 2000 to the panel as shown in Figure 4 17 Figure 4 17 Model RA 2000 Connection to the Panel firealarmresources com ...

Страница 56: ...00 Installation Instruc tions P N 151153 or 5815RMK Remote Mounting Kit Installation Instructions P N 151391 3 Connect the 5815XL to the control panel See Section 4 7 1 4 Use on board DIPswitches to select an ID See Section 4 5 1 5 The new 5815XL module must be added to the system through programming JumpStart will add the module automatically see Section 8 1 You can also add it manually see Secti...

Страница 57: ...t the 5815XL to the control panel as shown in Figure 4 19 After the 5815XL is connected to the panel it must be added to the system This programming step is described in Section 9 2 2 Figure 4 19 5815XL Connection to Main Panel Assembly Supervised Power Limited firealarmresources com ...

Страница 58: ...ion involves the following steps 1 Make sure power is off at the panel 2 Connect the 5824 to the panel as shown in Figure 4 20 Note Two 5824s per panel maximum 3 Use the DIP switches on the 5824 board to assign an ID to the 5824 see Section 4 5 1 4 Configure the 5824 device through programming See Section 4 8 1 5 Connect a printer to the 5824 as shown in Figure 4 21 Figure 4 20 5824 Connection to ...

Страница 59: ...owing steps Add the module to the system JumpStart will add the module automatically see Section 8 1 You can also add it manually see Section 9 2 2 Select a name if desired see Section 9 2 1 1 Select options for the printer and the output port See below Model 5824 with housing To Parallel Printer To Serial Printer firealarmresources com ...

Страница 60: ...een similar to the one shown in Figure 4 22 will display Figure 4 22 Selecting Printer and Output Port Options 6 Select options for the printer as needed for your installation Most printers are parallel 7 If you are using a serial printer use the next screen to select serial port options as required for your printer Refer to your printer manual if you need more information Option Choices Baud Rate...

Страница 61: ... eight inputs for dry contact monitoring The following sub sections describe hardware installation Refer to Section 6 for programming information 4 9 1 5880 Board Layout Figure 4 23 is a picture of the 5880 board showing locations of screw terminals for connection to the panel and contact monitor wiring pin connectors for connecting LEDs and the DIP switch for selecting an SBUS ID number Figure 4 ...

Страница 62: ...ects to the panel via the SBUS Make connections as shown in Figure 4 24 After the 5880 is connected to the panel it must be added to the system This programming step is described in Section 9 2 2 Figure 4 24 5880 Connection to Main Control Panel Assembly firealarmresources com ...

Страница 63: ...e mapped to output circuits See Section 9 5 3 for programming details Wire the LEDs as shown in Figure 4 25 On connector P1 Pin 12 is an open collector output for controlling a PZT If used the 5880 PZT will match the PZT pattern of the on board or RA 2000 annunciator Note The circuit connected to Open Collector Output last pin on P1 must be current limited so that no more than 100 mA of current is...

Страница 64: ...switch supported by the control panel can be used with the 5880 For example you can use a 5880 to monitor pull stations water flow tamper reset or silence switches Wire dry contacts as shown in Figure 4 26 Notice grouping of terminals power terminals are shared by two inputs Figure 4 26 Dry Contact Wiring Model 7628 Supervised firealarmresources com ...

Страница 65: ... and yellow typically used for trouble LEDs Installation of the 5865 3 and 5865 4 is identical The key switches and the trouble LED follow the behavior of other system annunciators and do not require any installation steps The following sub sections describe how to install the 5865 3 and 5865 4 hardware Refer to Section 9 for programming information Note This manual uses 5865 when referring to asp...

Страница 66: ... 5865 connects to the panel via the SBUS Make connections as shown in Figure 4 28 After the 5865 is connected to the panel it must be added to the system This programming step is described in Section 9 2 2 Figure 4 28 5865 Connection to the FACP firealarmresources com ...

Страница 67: ...ox is used as an example Figure 4 29 5865 Mounting Example The 5865 ships with a set of zone description labels that can be inserted into the 5865 board assembly These labels can be used in a typewriter or can be written on by hand Slide the labels under the plexiglass as shown in Figure 4 30 The LEDs will show through the label when illuminated Figure 4 30 Inserting Zone Description Labels fireal...

Страница 68: ...en modules on the same panel 4 12 Telephone Connection Connect the telephone lines as shown in Figure 4 31 The Model 7860 phone cord is available from Silent Knight for this purpose If you do not use the model 7860 to connect to the phone lines the wire used for the connection must be 26 AWG or larger diameter wire A number of programmable options are available for customizing telephone lines Thes...

Страница 69: ...minal is negative and O terminal is positive If the circuit is programmed as an output circuit Aux power or NAC then the X terminal is positive and the O terminal is negative This section of the manual explains how to install conventional notification appliances and initiating devices to be used with the system 4 13 1 Conventional Notification Appliance This sub section of the manual explains how ...

Страница 70: ...ring Maximum voltage drop per Class B notification circuit is 3V See Table 4 3 Table 4 3 Maximum Impedance Class B Current Maximum Impedance 1 0A 3Ω 1 5A 2Ω 2 0A 1 5Ω 2 5A 1 2Ω 3 0A 1 0Ω Alarm Polarity Shown Supervised Power Limited Notification Wiring Regulated 24 VDC 3A per Circuit 9A max Combined UL Listed EOL Model 7628 4 7 kΩ firealarmresources com ...

Страница 71: ...ure 4 33 Class A Notification Appliance Circuit Configuration Note In programming any point that uses multiple Flexput circuits the lowest Flexput circuit number is used to refer to the circuit pair For example Figure 4 33 uses both Flexput circuit 1 and 2 so in programming it would be referred to as point 1 Maximum voltage drop is 3V per Class A circuit See Table 4 4 Table 4 4 Maximum Impedance C...

Страница 72: ...ss B Inputs You can connect conventional Class B switches such as waterflow switches and pull stations directly to the Flexput circuits of the control panel To install a Class B switch 1 Wire the Class B switch as shown in Figure 4 34 2 Configure the circuit through programming see Section 9 5 Figure 4 34 Class B Input Switches Supervised Power Limited Maximum Impedance per Circuit is 50Ω UL Liste...

Страница 73: ...circuit through programming see Section 9 5 Figure 4 35 Class A initiating Switches Note In programming any point that uses multiple Flexput circuits the lowest Flexput circuit number is used to refer to the circuit pair For example Figure 4 35 uses both Flexput circuit 1 and 2 so in programming it would be referred to as point 1 Note Flexput circuit 1 and 2 used as an example Any Flexput point pa...

Страница 74: ... illustrate how to connect a UL listed 2 wire detector to the control panel 4 13 3 1 Installing 2 Wire Class B Smoke Detectors To install a Class B two wire smoke detector wire as shown in Figure 4 36 Figure 4 36 Two Wire Class B Smoke Detector Note Flexput circuit 5 used as an example Any Flexput circuit could be used UL Listed EOL Model 7628 4 7 k Ω Maximum Impedance per Circuit is 50Ω Supervise...

Страница 75: ...Note In programming any point that uses multiple Flexput circuits the lowest Flexput circuit number is used to refer to the circuit pair For example Figure 4 37 uses both Flexput circuit 5 and 6 so in programming it would be referred to as point 5 Note Flexput circuit 5 and 6 used as an example Any Flexput point pairing could be used Supervised Power Limited Maximum Impedance per Circuit is 50Ω fi...

Страница 76: ...h Class B loop input is paired with a unique power source as shown in Figure 4 38 3 Each loop gets smoke power from the even numbered Flexput circuit and the contact input is connected to the odd numbered Flexput circuit Figure 4 38 Class B 4 Wire Smoke Detector Connections Note In programming any point that uses multiple Flexput circuits the lowest Flexput circuit number is used to refer to the c...

Страница 77: ... 39 Figure 4 39 Class A 4 Wire Smoke Detector Connections Note In programming any point that uses multiple Flexput circuits are always referred to as the lowest Flexput circuit number used For example Figure 4 39 uses Flexput circuits 1 2 3 together and 4 5 6 together In programming 1 2 3 would be referred to as point 1 and 4 5 6 would be referred to as point 4 Air Products PAM 2 Model 160150 Supe...

Страница 78: ...re the auxiliary power output through programming see Section 9 5 Figure 4 40 Flexput Circuit Location 4 13 5 1 Door Holder Power Door holder power is intended for fire door applications When there are no alarms in the system and the panel has AC power door holder circuits have 24 volt power present at their terminals Any alarm will cause power to disconnect Power will be re applied when the syste...

Страница 79: ... 4 for compatible four wire smoke detectors 4 14 On Board Relays Conventional The control panel has two built in programmable relays and a built in trouble relay All relays are Form C rated at 2 5 A 24VDC Figure 4 41 Location of Conventional Relay Circuits 4 14 1 Trouble Relay The control panel has a dedicated Form C trouble relay built in The relay provides a normally open and a normally closed c...

Страница 80: ...e 4 42 2 Wire the 3158 within 20 feet of the control panel Wiring must be enclosed in conduit 3 Program control panel Relay 1 for alarm 4 Program Flexput circuit 5 for alarm 5 Program Flexput circuit 6 for supervisory non latching Table 4 5 Keltron 3158 to Control Panel Connections Terminal Connects To Terminal Connects To 3158 Term 1 To Keltron receiving equipment 3158 Term 8 Control panel Relay ...

Страница 81: ...able for remote station where separate transmission supervisory if applicable and protected premise service circuits are required for fire trouble signals Intended for connection to a polarity reversal circuit of a remote station receiving unit having compatible ratings Example firealarmresources com ...

Страница 82: ...h 2 Wire the 5220 to the control panel as shown in Figure 4 43 This drawing also shows how to connect the city box coil to terminals 3 and 4 on the 5220 Do not install an EOL resis tor in the terminals of the Flexput circuit used for this application 3 Connect earth ground wire to the 5220 chassis with mounting screw 4 Program the Flexput circuit as a notification circuit Refer to Section 9 5 2 As...

Страница 83: ...Using the IDP Relay Addressable Relay Module for City box Connection Wire the IDP Relay as shown in Figure 4 44 Figure 4 44 IDP Relay Module for City box Connection UL listed Model 7642 Must be Installed in City Box Enclosure firealarmresources com ...

Страница 84: ...ol panel using the four wire pigtail provided as shown in Figure 4 45 This diagram also shows how to connect the 5220 to the remote indicator Do not install an EOL resistor in the terminals of the flexput circuit used for this application 3 Connect earth ground wire to the 5220 chassis with mounting screw 4 Program the flexput circuit as a notification circuit Refer to Section 9 5 2 Assign this fl...

Страница 85: ...the control panel as shown in Figure 4 46 Do not install an EOL resistor on the terminals of the flexput circuit used Note Use only Flexput circuits on the control panel for reverse polarity 2 Program the Flexput circuit as a notification circuit See Section 9 5 2 3 Map the group to activate non silenceable constant on in response to a system general alarm and to disconnect in response to a system...

Страница 86: ...r to the IFP 2000 FACP dry contacts The FACP contacts must be supervised by the remote station transmitter module using end of line resistors ELRs with a value determined by the trans mitter manufacturer Power is also provided by the remote station transmitter manufacturer Refer to the remote station transmitter manufacturer s manual for details firealarmresources com ...

Страница 87: ... panels which is also the maximum panel capacity of a networked system 5 1 2 Wiring Options to Connect Networked Panels 1 Direct Connect Panels can be connected cost effectively via shielded twisted pair copper wire within conduit when the panels are located no more than 20 feet apart and in the same room 2 Repeater Connection Panels separated by more than 20 feet or are located in multiple buildi...

Страница 88: ... 20 feet of conduit run distance from each other Place the conduit for routing the direct connect networking cable between panels in a bus configuration as shown above in Figure 5 1 2 Make the network wiring connections The cable used must be shielded twisted pair 18 gauge or larger wire See Figure 5 2 for the DIP switch termination settings for Direct Connect wire option Run one of the twisted pa...

Страница 89: ... switches 8 9 and 10 set to the ON position All panels that are not at the BUS ends must have the terminators set to the OFF position See Figure 5 2 4 T Tapping is not allowed wire must be run in a BUS configuration Figure 5 2 DIP Switch terminations settings for Direct Connect Wiring option firealarmresources com ...

Страница 90: ...s the use of a network repeater with each panel Repeaters are used to travel long distances and or between buildings Figure 5 3 shows the repeater wiring connection for style 4 class B as a solid line For style 7 class A the dotted line would be used in addition to the solid lines Figure 5 3 Repeater Networking Connection Class A Wiring firealarmresources com ...

Страница 91: ...able up to a maximum signal loss of 8dB The IFP RPT FO repeater also has connections for unshielded twisted pair wiring so that either fiber optic cable or unshielded twisted pair wiring can be used for connecting panels Due to the physical size of the repeaters it is difficult to mount them directly in the IFP 2000 cabinet Accessory kits for the repeaters are available that include a small cabine...

Страница 92: ...able to reach between the repeater and the control panel Figure 5 5 Network Repeater mounted in cabinet Use the following steps to properly mount the network repeater to the IFP 2000 1 Place the network repeater cabinet within 2 of the IFP 2000 panel Use 3 4 or larger conduit between the IFP 2000 and the repeater cabinet Install the repeater PCB in the repeater cabinet using the mounting hardware ...

Страница 93: ...erminals 3 and 4 of TB1 is done at the next previous repeater due to these wiring connections being connected to terminals 1 and 2 of TB1 at the next previous repeater When no twisted pair wiring is made to terminals 1 and 2 of TB1 jumpers J2 and J3 must be left OPEN at the repeater This would be the case when using fiber optic cable or when terminals 3 and 4 of TB1 are only being used 5 On fiber ...

Страница 94: ...ectors It is important that the cable be verified to contain no more then 8dB of loss including the connectors 2 Twisted pair wiring must be UNSHIELDED twisted pair conductor cable The wire gauge must be 18 AWG or larger The maximum wire length is 3000 ft between repeaters 5 4 2 2 Unshielded Twisted Pair Wiring between Multiple Panels Unshielded twisted pair wiring between multiple panels is shown...

Страница 95: ...0 5 9 5 4 2 3 Fiber Optic Repeater Wiring Fiber optic cable between multiple panels is shown in Figure 5 8 Class A is shown with a dotted line Figure 5 8 Fiber Optic Wiring Example Class A Wiring firealarmresources com ...

Страница 96: ...ture of fiber optic cable and twisted pair wiring between multiple panels is shown in Figure 5 9 Class A cabling is shown with dotted line Figure 5 9 Twisted Pair and Fiber Optic Combination Wiring Example Class A Wiring Fiber optic ports that are not used must have their dust caps placed on the port firealarmresources com ...

Страница 97: ...example using both repeaters and direct connect wiring All repeaters in the system must be placed only on panels that are at the ends of a direct connect BUS or connected to panels with no direct connect network wiring Figure 5 10 Network Wiring Example using both Repeaters and Direct Connect Wiring Class A Wiring firealarmresources com ...

Страница 98: ...ct BUS and it does not have a repeater so its DIP switches 8 9 and 10 must be ON to provide direct connect BUS termination Panel 2 is NOT at the end of a direct connect BUS so its DIP switches 8 9 and 10 must be OFF Note A repeater would not be allowed to be connected to panel 2 in this example because it is not at the end of a direct connect BUS Panel 3 looks like it is at the end of a direct con...

Страница 99: ...er is placed ON and provides the termination Jumpers J2 and J3 for the repeater must be OFF because no wires are connected to the twisted pair terminals 1 and 2 of TB1 5 6 Setting the Network ID for each Panel Note It is important that much thought is given when choosing the network IDs for each panel It is difficult to change the IDs once panel programming has begun The network ID for each panel ...

Страница 100: ...IFP 2000 Installation Manual 5 14 151430 firealarmresources com ...

Страница 101: ... Ping Panel Menu 4 Press to enter the Network Status Menu 6 2 Network Programming This section of the manual describes how to program network options using the built in annunciator All options described in this section can be programmed using the Silent Knight Software Suite SKSS 2 6 2 1 Learn Network The Learn Network menu shows you all of the panels connected to the network Any panel that has be...

Страница 102: ...allows you to add a panel to the network edit the panel name and edit the panels site assignment To Edit Network information 1 Enter the installer code The panel will automatically go to the main menu 2 Select for Network Programming 3 Press to enter the Edit Network Menu 6 2 2 1 Edit Panel 4 Press to edit panel Information Figure 6 1 Edit Network Panel 1 6 2 1 firealarmresources com ...

Страница 103: ...nel needs to reboot in order to complete the transition After running Jumpstart Auto programming for the first time or using the Download software to program the panels the Network Panel ID will be locked from future editing The only was to change it will be to restore defaults and use this menu again To Edit the Network Panel ID 1 Enter the installer code The panel will automatically go to the ma...

Страница 104: ...ter code up to 6 digits then press 5 Enter the computer access code then press 6 Enter the phone number the panel will dial to connect to a downloading computer up to 40 digits then press 6 2 5 Access Codes Access codes provide the user access to the control panel functions Each access code can be customized for each user This allows some users the ability to access programming and other higher le...

Страница 105: ...ofile Edit Menu you can change the users name access code and the panel Type of Function Selectable Functions Panel Operations System Reset System Silence System Ack Fire Drill Key Panel Menus System Test Fire Drill Menu Indicator Test Walk Test no Report Walk Test with Report Dialer Test Clear History Buffer Point Functions Disable Enable Point Point Status Set SLC Device Address SLC Single Devic...

Страница 106: ...press to finish 6 2 5 2 Edit Access Code 9 Enter new access code minimum of 4 digits maximum of 7 digit 10 Press 11 Enter code again 12 Press 6 2 5 3 Panel Functions 13 Press the or arrow to move through the list of available functions 14 Then press to move to Y yes or N no selection column 15 Press the or arrow to select Y or N 16 Press 17 Repeat steps 14 through 17 until user profile is complete...

Страница 107: ...for this option are enable PI SIA Modifier Yes or No The default selection is Yes which will report the same as IFP 1000 version 9 panels If set to No the panel ID will be included as part of the SIA event string 6 2 6 3 Receiver Configuration The IFP 2000 network can report events to as many as four receivers Each receiver is assigned a phone number and reporting format Phone numbers can be up to...

Страница 108: ...anels into the network See Section 6 2 1 Edit Network Edit Panel Network Panel ID Edit Panel name Site member See Section 6 2 2 Edit Site Name Site Member Edit Name Edit Panel ID Change current panel ID See Section 6 2 3 Computer Accounts ComputerAccount 123456 See Section 6 2 4 Computer Access Code 0 Computer Phone Up to 40 digits firealarmresources com ...

Страница 109: ...anel functions can not be edited See Section 6 2 5 Edit Access Code Edit Panel Function System Reset System Silence System Ack Fire Drill Key System Tests Fire Drill Menu Indicator Test Walk Test no Report Walk Test w Report Dialer Test Clear History Buffer Point Functions Disable Enable Point Point Status Set SLC Device Address SLC Single Device Locator SLC Multi Device Locator I O Point Control ...

Страница 110: ...ivers Receiver Number See Section 6 2 6 3 Receiver Format Contact ID SIA500 SIA8 SIA20 Dialer Report Table Panel See Section 6 2 6 4 Report Alarms Report Supervisory Report Troubles Report Events by Point Primary Receiver Primary Account Test Primary Account Secondary Receiver Secondary Account Test Secondary Account Network Diagnostic Ping Panel See Section 6 1 1 Network Status See Section 6 1 2 ...

Страница 111: ...air speed range K200 23 00 IDP Heat Fixed temperature thermal detector 135 F Section 7 4 IDP Heat ROR Rate of rise thermal detector with 135 fixed temperature IDP Heat HT Fixed high temperature thermal detector 190 F IDP Pull SA Addressable single action pull station K200 19 00 IDP Pull DA Addressable dual action pull station K200 20 00 IDP Iso Fault isolator module K200 21 00 IDP Monitor Monitor ...

Страница 112: ...you are installing for details 7 3 1 Wiring 5815XL in Style 4 Class B Configuration No special wire is required for addressable loops The wire can be untwisted unshielded solid or stranded as long as it meets the National Electric Code 760 51 requirements for power limited fire protective signaling cables Wire distances are computed using copper wire Maximum wiring resistance is 40 ohms for IDP de...

Страница 113: ...Figure 7 1 Calculating wire run length for a simple out and back tap When using T taps the total length of all taps and the main bus must not exceed 40 000 feet This requirement must be met in addition to the maximum distance requirements for the various wire gauges Figure 7 2 Calculating Wire Run Length for a T tap firealarmresources com ...

Страница 114: ... short circuit isolator devices Note Style 7 wiring you have to have an isolator module as the first device on the in and the out loops Figure 7 3 Class A SLC Configuration Note No t taps allowed on class A SLC loops Caution For proper system supervision do not use looped wire under terminals marked SLC and of the SLC device connectors Break wire runs to provide supervision of connections firealar...

Страница 115: ...Smoke Detector with Thermal IDP Acclimate Photoelectric Smoke Detector with Thermal IDP Heat Fixed Temperature Detector IDP Heat T High Temperature Thermal Detector IDP Heat ROR Rate of Rise Thermal Detector IDP Ion Ionization Smoke Detector To wire IDP detectors 1 Wire device bases as shown in Figure 7 4 2 Set the address for each device as described in Section 7 5 Figure 7 4 Heat and Smoke Detec...

Страница 116: ... assigned any unique address from 1 to 159 There can be an IDP detector using address 1 and an IDP module using address 1 0 is an invalid address In order to set the sensor above address 99 carefully remove the stop on the upper rotary switch with thumb as shown in example 2 Example 1 To select device address 1 turn the ONES rotary dial to 5 and the TENS rotary dial to 3 as shown in Figure 7 5 Exa...

Страница 117: ...art AutoProgramming The JumpStart AutoProgramming feature allows for faster system setup When you run JumpStart AutoProgramming the panel searches for expanders and SLC devices not currently in the system The new devices are added in their default configuration At the end of the JumpStart AutoProgramming you can choose to not accept the new devices and go back to the configuration you had before d...

Страница 118: ...umpStart AutoProgramming immediately after you have addressed and connected all input devices detectors pull stations and so on and output devices notification appliances relays and so on Note If you need to install a few devices after you have run JumpStart AutoProgramming you can install them manually Follow instructions in Section 8 for configuration To run JumpStart AutoProgramming follow thes...

Страница 119: ...isplay Select for DUCT and for NonDUCT 5 Press to select the next detector Select for DUCT and for Non DUCT Continue until all duct detectors have been selected Note You can move backwards through the list with 6 When you reach the last detector on this device press 7 The system will ask you if there are more duct detectors in the system If there are select for Yes and repeat from Step 3 If there ...

Страница 120: ...concept with the control panel In general terms mapping is assigning or linking events to outputs that should activate when events occur You do this by assigning input points to input zones output points to output groups and then linking or mapping zones and output groups Figure 8 1 is a brief overview of the concept of mapping The next several pages of the manual show these subjects in detail Fig...

Страница 121: ...assigned to input zones Any input point can be assigned to any input zone Input points can be assigned to one zone only An input point can be designated as Unused which means it has not been assigned to a zone Figure 8 2 Example of Input Point Assignment firealarmresources com ...

Страница 122: ...ual 8 6 151430 8 2 2 Output Circuit Mapping Figure 8 3 is a simple example showing how to assign notification and relay output circuits to groups Figure 8 3 Example of Assigning Output Circuits to Groups firealarmresources com ...

Страница 123: ...al Pull Alarm General Alarm SBus Exp Trouble Water FLow Alarm Fire Drill SBUS Class A Trouble Detector Alarm heat or smoke detectors Aux 1 SLC loop Trouble Aux 1 and Aux 2 Alarm user specified alarm types Aux 2 AC loss Trouble Interlock alert General Super Battery Trouble Interlock Release Gen Prealarm Ground Fault Trouble Pre Alarm General Trouble Phone Line Trouble Supervisory Alarm Silenced Rep...

Страница 124: ...IFP 2000 Installation Manual 8 8 151430 Figure 8 4 Example of Zone Events Mapped to output Groups and Patterns firealarmresources com ...

Страница 125: ...Programming Overview 151430 8 9 Figure 8 5 Example of Zone Events Mapped to Output Groups and Patterns on a Single Panel firealarmresources com ...

Страница 126: ...IFP 2000 Installation Manual 8 10 151430 Figure 8 6 Example of Events Mapped to Output Groups and Patterns Within a Networked Site firealarmresources com ...

Страница 127: ...d to zones and output groups Typically you would create two output groups for each zone one for alarms and one for troubles LED points are available when models 5865 3 4 and or 5880 are used with the system Figure 8 7 Example of LED Points Mapped to Output Groups applies to Models 5865 3 4 and 5880 firealarmresources com ...

Страница 128: ...IFP 2000 Installation Manual 8 12 151430 8 2 5 Mapping LED Points for a Networked System Figure 8 8 Example of Expanding Mapping of LED Points Across Panels firealarmresources com ...

Страница 129: ...tor or a RA 2000 remote annunciator The following subsections describe programming basics including a description of editing keys available for programming and how to move through programming menus Section 9 contains specific information about individual programming options 8 4 1 Entering Exiting Panel Programming To enter Program Mode 1 Enter the Installer Code factory programmed default code is ...

Страница 130: ...o Press Select from a menu Enter the number of the option Enter numeric data Press the appropriate number on the annunciator Enter text alphanumeric data Enter each letter individually by pressing and holding any numeric key until the one you wish to select displays Then press right arrow to select the letter See Section 8 4 for complete information Select from a scrolling list Use up arrow and do...

Страница 131: ...ew 151430 8 15 8 4 1 3 Editing Keys The keys shown in Figure 8 10 are available for use when you are in the Panel Programming Menu Figure 8 10 Editing Keys Available from the Panel Programming Menu firealarmresources com ...

Страница 132: ...ED IO Dev 5865 LED Annunc VIP 50 See section 9 9 VIP Series Installation Manual P N 151286 VIP VCM VIP RM2000 Delete Module List of Modules Section 9 2 3 View Module List List of Modules Zone Edit Zone Select Zone to Edit Edit Zone Name Enter Name1 Section 9 3 1 1 Enter Number1 Enter Name2 Enter Number2 Zone Properties Verification Type 1 Count Section 9 3 1 2 2 Count Alarm Ver PAS SNGL ILOCK DBL ...

Страница 133: ...View Group Points Select Group Section 9 4 4 Point IDP Devices on Internal and External 5815XL Enter Pt SWITCH MAN_PULL Section 9 5 WATERFLOW LATCH NLATCH SUPERVSY LATCH NLATCH FIREDRILL SILENCE RESET PAS_ACK ZN_AUX1 LATCH NLATCH ZN_AUX2 LATCH NLATCH SYS_AUX1 LATCH NLATCH SYS_AUX2 LATCH NLATCH DETECT SW TAMPER LATCH NLATCH MAN REL ILOCK NOTIF OUTPUT PT Select Group Section 9 5 AUX CONST AUX RESET ...

Страница 134: ...ACK Select zone ZN_AUX1 Select zone ZN_AUX2 Select zone SYS_AUX1 SYS_AUX2 MAN REL ILOCK A SWITCH Same as B SWITCH B DETECTOR 2 WIRE SMK 4 WIRE SMK A DETECTOR 2 WIRE SMK 4 WIRE SMK Select Group or Zone Number Group or Zone selection will appear depending on the type is selected Edit Name Enter Name Section 9 5 3 5880 Enter Point NOTIF UNUSED Select Group Edit Name Enter Name 5865 Enter Point NOTIF ...

Страница 135: ... N disabled Section 9 6 2 7 No Daytime Nighttime Sensitivity Enable Disable Yes N Section 9 6 3 No Day Start enter time Night Start enter time Days of the Week Select days Holiday days Holidays 1 to 9 Enter dates Section 9 6 4 Holidays 10 to 18 Misc Options 1 Water Flow Delay 0 90 Seconds 30 sec Water Flow delay is the number of sec before water flow alarm is generated Section 9 6 5 1 Low AC Repor...

Страница 136: ...er Internal Message Edit Line 1 Section 9 6 8 Edit Voice Commands Select Command 1 6 User Message Tone Select User Message Section 9 6 9 Tone only Message 1 Message 2 Repeats 1 14 Continuous None Initial Delay 0 28 4 sec increments 12 Inter message Delay 4 32 4 sec increments 8 Allow Message Restart with new alarm Yes Y NO N No Edit Ethernet IP Address Section 4 1 3 Subnet Mask Default Gateway DCH...

Страница 137: ...confirm the integrity of the installation prior to performing any custom programming After determining that the hardware is properly installed custom programming can be performed Refer to Section 8 NOTICE TO USERS INSTALLERS AUTHORITIES HAVING JURISDICTION AND OTHER INVOLVED PARTIES This product incorporates field programmable software In order for the product to comply with the requirements in th...

Страница 138: ...me class of wiring Class A or Class B or features that are specific to the module to be edited To edit an existing module 1 Enter the installer code The panel will automatically go to the main menu 2 Select for Panel Programming Note If you are working on a networked system you will need to select which panel you want to program Display reads Initializing Please wait 3 Press enter to select SLC fa...

Страница 139: ...applies only to the 5815XL Each module has a unique set of options that specifically applies to the functionality of the module being edited 8 Choose the class of wiring you wish to use for this module Class A or Class B by press ing the or arrow then press 9 Select the option desired for the module being edited by pressing the or arrow then press firealarmresources com ...

Страница 140: ...odule if desired You must save changes when you exit the Panel Programming or the new module will not be added Note If you Add a Module that has not been physically connected the panel will go into trouble after it reinitializes when you exit the Panel Programming When the new module is attached the trouble will correct itself automatically the next time you power up the system 9 2 3 Deleting a Mo...

Страница 141: ...lete and view zone points Selections made here affect all detectors and switches in the zone Up to 999 zones can be used in each panel 9 3 1 Edit Zone Features that can be edited through the edit zone option are edit zone name zone properties which includes zone type and detector sensitivity and zone accessory options To edit a zone follow these steps 1 Enter the installer code The panel will auto...

Страница 142: ... a Zone See Appendix B for a list of available characters and their numeric designators 9 3 1 2 Edit Zone Properties Zone properties consist of alarm delay characteristics heat detector sensitivity and smoke detector sensitivity 1 Do steps 1 through 5 of Section 9 3 1 2 Press to edit the properties of the selected zone 2 Detection type also selected from this screen see Table 9 1 firealarmresource...

Страница 143: ...tput group for the prealarm event the output group will activate The prealarm will not be reported to the central station When two count is used detector spacing shall be cut in half you shall not use the alarm verification feature and no delay shall be used Alarm Ver Alarm verification is an optional false alarm prevention feature that verifies an alarm condition by resetting the smoke detector I...

Страница 144: ...er zone menu 4 Press to add a zone A zone will be added The system will assign the next available zone number Options for IMPORTANT Drift compensation is automatic for all smoke detectors photoelectric and ionization The feature is always in effect no programming is required See Section 10 4 11 for information about how to check if a detector is in UL compliance Detector Protocol Type of Smoke Det...

Страница 145: ... Press to delete a zone A warning screen will display If you want to proceed with deleting the zone select Yes To cancel select No 9 3 4 View Zone Points To view the points in a zone follow these steps 1 Enter the installer code The panel will automatically go to the main menu 2 Select for Panel Programming Display reads Initializing Please wait 3 Press to enter zone menu 4 Press to view zone poin...

Страница 146: ...n the VIP 50 and VIP CE4 can only be assigned to voice output groups Output points that are non voice circuits all other points and circuits that are on all modules except the VIP 50 and VIP CE4 are assigned to non voice output groups 9 4 1 Edit Group In the edit group option you can program the name of an output group Section 9 4 1 1 and change the properties Section 9 4 1 2 of that group To edit...

Страница 147: ...it Group Menu allows you to select options for each group for the following items VIP switch number which is used if it is a voice type group Define output group type as voice or non voice See option for Voice EVAC Only in Figure Figure 9 5 Figure 9 5 Group Properties Screen Programming Options firealarmresources com ...

Страница 148: ...IP SW16 Figure 9 6 illustrates how the numbers selected correspond to the VIP VCM and SW16 Figure 9 6 Corresponding Switch and LED for Mapping Output Groups 7 To get to this menu item repeat steps 1 through 5 of Section 9 4 1 8 To edit group properties press 9 Press the or arrows to select the desired VIP switch number or enter the number 10 Press 11 Press the or arrows to select Y yes to make thi...

Страница 149: ... 9 4 1 2 A total of 999 output groups can be defined 9 4 3 Delete Group 1 Enter the installer code The panel will automatically go to the main menu 2 Select for Panel Programming Display reads Initializing Please wait 3 Press to enter group menu 4 Press to delete a group A warning screen will display If you want to proceed with deleting the group select Yes To cancel select No 3 2 7 3 3 firealarmr...

Страница 150: ...1 Enter the installer code The panel will automatically go to the main menu 2 Select for Panel Programming Display reads Initializing Please wait 3 Press to enter group menu 4 Press to view group points 5 Enter the group number then press 7 3 4 firealarmresources com ...

Страница 151: ... or arrows to select the desired module Refer to Section 8 5 Quick Refer ence Table for available choices 5 Press 6 Select S for sensor for M for module 7 Enter the number of the point you wish to edit 8 Press 9 Select the type of device by pressing or arrows Refer to Table 9 2 under column heading Type Selection for a list of choices Table 9 2 Programming Options for 5815XL Modules Type Selection...

Страница 152: ...is an alternative way of causing a fire drill It has the same operation as the fire drill option available from the annunciator When the switch is activated a fire drill begins when the switch is de activated the fire drill ends SILENCE This system level switch is an alternative way to silence the system It has the same effect as pressing the key RESET This system level switch is an alternative wa...

Страница 153: ...xiliary power supply for door holders you would use this option See Section 4 13 5 1 for a description of how this option operates RELAY OUTPUT PT Select Group Output Point a general use relay type Use for applications requiring a relay such as fan shutdown elevator recall and so on AUX RESET Use for auxiliary power resettable applications See Section 4 13 5 3 for a description of how this option ...

Страница 154: ... point menu 4 Press the or arrows to select the desired module Refer to Section 8 5 for available choices 5 Press 6 Enter the number of the circuit or point you wish to edit Refer to Table 9 3 for available selections 7 Press 8 Select the type by pressing the or arrows 9 Press 10 Select the function by pressing the or arrows 11 Press 12 Select the zone by pressing the or arrows 13 Press 14 Edit po...

Страница 155: ...options Latch or Non latching feature only appears for waterflow supervisory tamper zone aux1 zone aux2 system aux1 and system aux2 WATERFLOW SUPERVSY TAMPER FIREDRILL SILENCE RESET PAS_ACK ZN_AUX1 ZN_AUX2 SYS_AUX1 SYS_AUX2 MAN REL ILOCK A SWITCH Same as B SWITCH B DETECTOR 2 WIRE SMK Used for Class B 2 wire detectors 4 WIRE SMK Used for Class B 4 wire detectors A DETECTOR 2 WIRE SMK Used for Clas...

Страница 156: ...Initializing Please wait 3 Press to enter point menu 4 Press the or arrows to select the desired module Refer to Section 8 5 for available choices 5 Press Figure 9 7 Programming Points Screen for 5880 and 5865 Modules 6 Enter the point number 7 Press 8 Press the or arrows to select the type Notification or unused 9 Press 10 Press the or arrows to select the desired Group 11 Press 12 Edit module na...

Страница 157: ...t ENTER if done If you wish to bypass the Edit Name field press 9 5 4 Point Programming For VIP 50 VIP CE4 To program VIP 50 or VIP CE4 module points 1 Enter the installer code The panel will automatically go to the main menu 2 Select for Panel Programming Display reads Initializing Please wait 3 Press to enter point menu 4 Press the or arrows to select the VIP 50 module or VIP CE4 5 Press 6 Enter...

Страница 158: ...IFP 2000 Installation Manual 9 22 151430 11 Press 12 Edit module name See Section 9 5 3 1 Or Press to skip module name edit 13 Repeat Steps 1 through 13 for all voice circuits firealarmresources com ...

Страница 159: ...ain menu 2 Select for Panel Programming Display reads Initializing Please wait 3 Select for System Options 4 From the next menu select for Auto Test Time 5 Enter the hour you desire the control panel to send an automatic test report or press the or arrow then press 6 Enter the minutes or press the or arrow then press 7 Select AM or PM by pressing the or arrow then press 9 6 2 Phone Lines To access...

Страница 160: ...odes a pause and so on The following special characters are available Use the number buttons on the annunciator or the up and down arrow keys to select special characters Characters begin displaying after 9 See Figure 9 8 for an example 6 Enter a dialing prefix if needed then press Or Press to bypass the dialing prefix option Pound or number key on the telephone Star key on the telephone Comma cha...

Страница 161: ...r rotary dialing option then press Options are 9 6 2 5 Line Monitor Enable the line monitor for each phone line that will be used See Figure 9 8 for location of this field on the phone lines screen When the phone line monitor has been enabled for a phone line a trouble condition will occur if the line is not connected If a phone line will not be used it must be disabled Dial Option Description PUL...

Страница 162: ...the SKSS 2 manual for more information PN 151 11 Select Y answering machine bypass enabled or N answering machine bypass disabled by pressing the or arrow then press 9 6 2 7 Phone Line Unused This option is used so that you can set unused phones lines to Yes then no autotest will be sent through that line This option is factory programmed as No 12 Select Y or N by pressing the or arrow then press ...

Страница 163: ...Programming 151430 9 27 A screen similar to the one shown in Figure 9 9 will display Figure 9 9 Changing Day Night Sensitivity Time firealarmresources com ...

Страница 164: ... Days A screen similar to that shown in 5 will display 5 Edit the holiday schedules you wish to change or add holidays as needed in the program mable holiday locations Figure 9 10 Edit Holidays Screen 6 Enter the month of the Holiday then press 7 Enter the day of the month for the Holiday then press 8 Repeat steps 6 and 7 for any remaining holidays you wish to program 9 6 5 Miscellaneous Options 1...

Страница 165: ...el will automatically go to the main menu 2 Select for Panel Programming Display reads Initializing Please wait 3 Select for System Options 4 Select for Miscellaneous Options 1 A screen similar to the one shown in Figure 9 11 will display Figure 9 11 Water Flow Delay Programming Screen 5 Enter the number of seconds 0 to 90 to delay a water flow switch alarm then press 7 5 4 Delay in seconds before...

Страница 166: ...his feature is enabled set to Yes the system clock will switch to DST on the first Sunday in April at 2 00 a m and revert to standard time on the last Sunday in October at 2 00 a m After January 2007 if this feature is enabled the system clock will start and end DST according to the settings made in Misc Options 3 see Section 9 6 7 2 If this feature is not enabled set to No the Daylight Saving Tim...

Страница 167: ...ither option can be used in areas where the AC line frequency is not dependable and you want the panel to calculate time from the internal crystal The internal crystal is not as accurate as the AC power source and either 60 Hz or 50 Hz should normally be selected The panel defaults to the 60 Hz selection To change the AC line frequency continue programming from step 8 above 9 Select 50Hz 60Hz or N...

Страница 168: ...functions with outputs that use a synchronized output pattern 5 Press the or arrow to toggle this selection between Y Yes or N No 6 Press or to make your selection and move to the next programming option 9 6 6 2 Auto Display Oldest Event When this feature is programmed Y Yes then the oldest un acknowledge event will automatically display on the control panel and remote annunciators after there has...

Страница 169: ...t and end week and month of Daylight Saving Time To edit Miscellaneous Options 3 1 Enter the installer code The panel will automatically go to the main menu 2 Select for Panel Programming 3 Enter code if prompted Display reads Initializing Please wait 4 Select for System Options 5 Select for Miscellaneous Options 3 9 6 7 1 Alarm Verification Time You can set the alarm verification time from 1 to 2...

Страница 170: ... second Sunday in March DST End The first Sunday in November To set the start and end for Daylight Saving Time 8 Press the or arrow to select the week 1st 2nd etc Daylight Saving Time starts then press to make your selection and move to the month setting 9 Press the or arrow to select the month January December Daylight Saving Time starts then press to make your selection and move to the DST End o...

Страница 171: ...em will use the internal banner You cannot change the internal banner To customizing the banner display message 1 Enter the installer code The panel will automatically go to the main menu 2 Select for Panel Programming Display reads Initializing Please wait 3 Select for System Options 4 Select for Edit Banner A screen similar to the one shown in Figure 9 13 will display Figure 9 13 Internal Banner...

Страница 172: ...ired message used for that command 7 Select the tone to be played between messages High Lo ANSI Whoop Cont Whoop ANSI March Code California Steady or Alert Tone 8 Select how many times you wish the message to repeat None 1 14 or Continuous 9 Select the initial delay time 0 to 28 seconds in 4 second increments 10 Select the inter message delay time 4 to 32 seconds in 4 second increments 11 Enable D...

Страница 173: ...ted to confirm the locking of the current Network Panel ID If it is incorrect change the DIP switches to match 7 Press to confirm 9 8 Restore Defaults This option allows you to restore the panel back to factory defaults All programming will be lost 1 Enter the installer code The panel will automatically go to the main menu 2 Select for Panel Programming Display reads Initializing Please wait 3 Sel...

Страница 174: ...editing user message through the 7780 SKE Voice Evacuation Software 4 Connect the computer to the VIP VCM via the serial ports 5 Run the 7780 software 6 Select 7 Through the 7780 software add or edit the system messages 9 9 2 Local Recording Select this option if you wish to record the user message with the VIP VCM microphone or through the sound card of your PC Refer to Section 4 of the VIP Serie...

Страница 175: ...this entire section carefully before operating the panel Press to view Main Menu Select the desired menu option Enter your access code if prompted Note See Section 6 2 5 or information on how to modify user access code profiles 10 1 User and Installer Default Codes User Code factory programmed as 1111 Installer Code factory programmed as 123456 Multi site Installer Code factory programmed as 65432...

Страница 176: ...00 Installation Manual 10 2 151430 10 2 Annunciator Description Figure 10 1 shows the annunciator that is part of the control panel board assembly Figure 10 1 Control Panel Annunciator firealarmresources com ...

Страница 177: ...ur lines of 40 characters each Annunciator keys beep when they are pressed 10 2 2 Banner The banner is the message that displays on the control panel when the system is in normal mode no alarm or trouble condition exists and menus are not in use You can create a customized message that will display instead of the internal default message See Section 9 6 8 for information on editing the banner Figu...

Страница 178: ...ons Description System Tests From here both menus can access Fire Drill and Indicator Test Point Functions From here both menus can enable disable points Event History Display event history on the LCD See Section 10 4 4 for more information Set Time and Date Set time and date for the system Network Diagnostics Ping Panel and Network Status screen Network Programming From here menus can access Lear...

Страница 179: ...e is located A description of the point should display The fourth line of the screen should show NORMAL meaning that the point is currently enabled or DISABLED the point is currently disabled Press to toggle between NORMAL and DISABLE 10 4 3 Disable Enable NACs by Group 1 From the Main Menu select for point functions 2 Select to Disable NACs by group or to Enable NACs by group 3 Use and to move th...

Страница 180: ...d the drill If you do not press any key to end the fire drill manually it will time out automatically after ten minutes If a fire drill switch has been installed activating the switch will begin the drill deactivating the switch will end the drill 10 4 6 Conduct an Indicator Test The indicator test checks the annunciator LEDs PZT and LCD display 1 From the Main Menu press for System Tests 2 Press ...

Страница 181: ...le condition All zones respond as 1 Count zones respond when a single detector is in alarm during a walk test Each alarm initiated during the walk test will be reported and stored in the event history buffer 3 Press to end the walk test The system will reset The panel will send a TEST RESTORE report to the central station If you do not end the walk test manually within four hours it will end autom...

Страница 182: ...ty Through Point Status The control panel constantly monitors smoke detectors to ensure that sensitivity levels are in compliance with NFPA 72 Detectors are sampled every three hours If sensitivity for a detector is not in compliance the panel goes into trouble generating a CAL TRBLE condition A detector enters a CAL MAINT state to indicate that it is approaching an out of compliance condition but...

Страница 183: ...creen that displays will show you if the point has a trouble and will provide sensitiv ity compliance information See Section 10 4 11 for complete information about detector sensitivity compliance 10 4 13 View Alarms or Troubles When the system is in alarm or trouble you can press to view the location of an alarm or trouble See Section 10 4 13 for more information 10 4 14 View System Information P...

Страница 184: ...number is not needed and this step will be skipped If the phone number you will be calling is already displayed press Continue with Step four If the phone number you will be calling is not already displayed enter the number and press A phone number can be up to 40 digits long and can contain the following special characters Use the number buttons on the annunciator or the up and down arrow keys to...

Страница 185: ...larm or trouble condition exists and menus are not in use SYSTEM POWER LED is on The All Systems Normal display indicates that the system is in normal mode The current date and time display on the last line of the LCD Enter the appropriate code to activate the User or Installer Menu Alarm A smoke detector goes into alarm or a pull station is activated The dialer seizes control of the phone line an...

Страница 186: ...control of the phone line and calls the central station The on board annunciator sounds a loud pulsing beep in the sequence one second on nine seconds off SYSTEM TROUBLE LED is on The LCD displays a screen similar to this one Press down arrow to view the trouble A screen similar to this one displays Press to silence the annunciator Once the trouble condition has been fixed the system will restore ...

Страница 187: ... but still exists To silence alarms and troubles press followed by the Installer or User Code or rotate the key SYSTEM SILENCE LED is on SYSTEM TROUBLE SUPERVISORY or GENERAL ALARM LED depending on condition is on The annunciator and any notification devices attached to the system will be silenced Press down arrow to view the location of the alarm or trouble When the condition no longer exists the...

Страница 188: ... is enabled on a multi site annunciator it will be indicated by a blinking Silenced LED If any new troubles supervisory pre alarms or alarms are triggered in any assigned sites Locally Silenced will become disabled If a multi site annunciator is locally silenced for 24 hours the locally silenced feature will be disabled 3 The IFP 2000 menu system is disabled on a multi site annunciator Pressing th...

Страница 189: ...leasing zones NAC 98 001 is assigned to Output Group 2 Output Group 3 is created Output Group 3 will be defaulted as an Pre Alert output group for all releasing zones NAC 98 002 is assigned to Output Group 3 Output Group 4 is created Output Group 4 will be defaulted as a Release output group for all releasing zones NAC circuit 98 003 is assigned to Output Group 4 Note The installer must define whi...

Страница 190: ... General Alarm and Release Output Activation If two or more addressable detectors or a manual release switch activate the Alarm and the Release outputs will activate Also refer to Table 10 3 Table 10 3 Single Interlock Zone Operation Important Only addressable detectors can be used No conventional detectors can be used Each Single Interlock Zone input requires at least one manual release switch In...

Страница 191: ...s the activation of an interlock switch and either a manual release switch or 2 activated addressable detectors When these conditions are met the Release and General Alarm outputs will activate and the Alert outputs will deactivate Table 10 4 Double Interlock Zone Operation Important Only addressable detectors can be used No conventional detectors can be used Each Single Interlock Zone input requi...

Страница 192: ...ke to utilize 2 Enter a PIN with F Key macro recording privileges 10 9 1 Recording an F Key macro 1 Access the F Key Recording Menu and select the Start FKEY Recording option 2 This will exit you from the menu 3 Any Disabling or Activating of points or output groups from the site at this point will be programmed into the macro Do this by going to any annunciator within the site and enter ing Main ...

Страница 193: ...his will exit you from the menu 10 9 3 Erasing an F Key macro 1 If an F Key macro has already been recorded you can erase it by accessing the F Key Recording Menu and selecting the Erase FKEY Macro option 2 This will exit you from the menu 10 9 4 Using a recorded F Key macro 1 From the idle screen or any annunciator in the site press the F Key you want to activate 2 When you are finished to de act...

Страница 194: ...IFP 2000 Installation Manual 10 20 151430 firealarmresources com ...

Страница 195: ...either Report by Point or Report by Zone is selected AC power low trouble AT 0 ATNN000000 1 301 00 000 AC power low trouble restore AR 0 ARNN000000 3 301 00 000 Auto dialer test communications trouble line 1 YC 1 YCNN000001 1 350 00 001 Auto dialer test communications trouble line 1 restore YK 2 YKNN000001 3 350 00 002 Auto dialer test communications trouble line 2 YC 1 YCNN000002 1 350 00 001 Aut...

Страница 196: ...vision lost ET Exp ID ETNNXX0000 1 333 Exp ID 000 SBUS Class A supervision restore ER Exp ID ERNNXX0000 3 333 Exp ID 000 SBUS expander trouble ET Exp ID ETNNXX0000 1 333 Exp ID 000 SBUS expander trouble restore ER Exp ID ERNNXX0000 3 333 Exp ID 000 SLC class A supervision trouble ET Exp ID ETNNXX0000 1 331 Exp ID 000 SLC class A supervision trouble restore ER Exp ID ERNNXX0000 3 331 Exp ID 000 SLC...

Страница 197: ...d AUX2 switch trouble UT Zone UTNN000ZZZ 1 373 02 000 System based AUX2 switch trouble restore UJ Zone UJNN000ZZZ 3 373 02 000 Water flow switch alarm SA Zone SANN000ZZZ 1 113 00 Zone Water flow switch alarm restore SH Zone SHNN000ZZZ 3 113 00 Zone Water flow switch trouble ST Zone STNN000ZZZ 1 373 00 Zone Water flow switch trouble restore SJ Zone SJNN000ZZZ 3 373 00 Zone Zone based acknowledge sw...

Страница 198: ...larm restore Water Release Zone pi Exp ID FH Point FHNNXXPPPP 3 110 Exp ID Point Manual release switch disabled pi Exp ID FB Point FBNNXXPPPP 1 571 Exp ID Point Manual release switch enabled pi Exp ID FU Point FUNNXXPPPP 3 571 Exp ID Point Manual release switch trouble Water Release Zone pi Exp ID FT Point FTNNXXPPPP 1 373 Exp ID Point Manual release switch trouble restore Water Release Zone pi Ex...

Страница 199: ...ter flow switch trouble restore pi Exp ID SJ Point SJNNXXPPPP 3 373 Exp ID Point Zone based AUX1 switch alarm pi Exp ID UA Point UANNXXPPPP 1 140 Exp ID Point Zone based AUX1 switch alarm restore pi Exp ID UH Point UHNNXXPPPP 3 140 Exp ID Point Zone based AUX1 switch disabled pi Exp ID UB Point UBNNXXPPPP 1 571 Exp ID Point Zone based AUX1 switch enabled pi Exp ID UU Point UUNNXXPPPP 3 571 Exp ID ...

Страница 200: ...ier Reporting Examples Event Report Zone Point Panel ID Module Zone ZZZZ Point ZZZZ Fields Sent SIA Event Data Fire Alarm Zone Zone n a n a97 15 n a EE ZZ FA15 Fire Alarm Zone Zone n a n a 05 n a EE Z FA5 Fire Alarm Point Point n a 01 n a 123 EE ZZ EE ZZZ pi01 FA123 Fire Alarm Point Point n a 33 n a 203 EE ZZ EE ZZZ pi11 FA203 Expander Trouble n a n a 11 n a n a EE ZZ ET11 Auto Test n a n a n a n ...

Страница 201: ...mation 1 The Event field will contain 10 digits including the 2 digit event code EE 2 digit panel ID PP 2 digit Module Number MM and a 4 digit Event Parameter ZZZZ 2 Based on the actual Event Code the Module Number or Event Parameter fields might not contain pertinent information In that case the field will contain zeros 3 The account number is sent using an account block that is separate from the...

Страница 202: ...2 n a n a n a EE PP MM ZZZZ RP32000000 Battery Trouble Panel 32 n a 32 98 n a n a EE PP MM ZZZZ YT32980000 Battery Trouble Expander 18 n a 32 18 n a n a EE PP MM ZZZZ YT32180000 SLC Loop Shorted n a 01 44 n a n a EE PP MM ZZZZ ET01440000 Program Begin n a 32 n a n a n a EE PP MM ZZZZ LB32000000 Program Begin n a 22 n a n a n a EE PP MM ZZZZ LB22000000 AC Power Loss Panel 22 n a 22 98 n a n a EE PP...

Страница 203: ...L module Do not connect devices to terminals labeled SLC IN Make sure SLC devices have been addressed properly following the procedure described in Section 7 5 if using IDP devices Make sure correct polarity has been observed for SLC device wiring See Section 7 4 SLC devices are not being recognized trouble message Missing displays on the annunciator Check that SLC loop impedance is within the req...

Страница 204: ... hours before completing this step Remove AC power activate initiating device and check that the ALARM indicator lights all active Notification Appliances sound Measure battery voltage while the Notification Appliances are sounding Replace any battery with terminal voltage less than 85 of rating Reapply AC power and RESET system 5815XL module that has been physically connected to the panel but is ...

Страница 205: ...ocate a particular SLC device 1 Select Point Functions from the Main Menu 2 Select SLC Single Device Locator A message similar to the one shown in Figure 12 1 will display Figure 12 1 Shut Down Warning 3 Press the or arrow to toggle NO to YES then press If NO is chosen you will exit back to the Point Function menu If Yes is chosen the system will cease normal operation leaving the premise unprotec...

Страница 206: ... shown in Figure 12 2 will display Figure 12 2 Shut Down Warning 3 Press the or arrow to toggle NO to YES then press If NO is chosen you will exit back to the Point Function menu If Yes is chosen the system will cease normal operation leaving the premise unprotected 4 Select the SLC loop 5 Enter up to 8 SLC addresses for the devices you wish to locate The LEDs on the selected devices will start fl...

Страница 207: ...t s output mapping Follow these steps to control a I O point 1 Select Point Functions from the Main Menu 2 Select I O Point Control 3 Select the Module the point is on 4 Enter the zone number or press the or arrow to select the point you wish to test then press 5 Press to generate an alarm for an input point or activate an output point 6 To exit press 2 6 firealarmresources com ...

Страница 208: ...Function Terminal Label Low Biased High Biased Values in Ohms High Trip High Restore Low Trip Low Restore Flexput Notification Circuits X I O 8 0 0 O 0 0 X I O 7 0 0 O 0 0 X I O 6 0 0 O 0 0 X I O 5 0 0 O 0 0 X I O 4 0 0 O 0 0 X I O 3 0 0 O 0 0 X I O 2 0 0 O 0 0 X I O 1 0 0 O 0 0 SBUS Communication B SBUS1 OUT 0 0 A 0 0 SBUS Power 0 0 0 0 SBUS Communication B SBUS1 IN 0 0 A 0 0 SBUS Power 0 0 0 0 f...

Страница 209: ... OUT 0 0 A 0 0 SBUS Power 0 0 0 0 SBUS Communication B SBUS 2 IN 0 0 A 0 0 SBUS Power 0 0 0 0 SLC Terminals SLC OUT 0 0 0 0 SLC IN 0 0 0 0 Function Terminal Label Low Biased High Biased Values in Ohms High Trip High Restore Low Trip Low Restore firealarmresources com ...

Страница 210: ...IFP 2000 Installation Manual 12 8 151430 firealarmresources com ...

Страница 211: ...one Group Description On board 1 On board 30 On board 2 On board 31 On board 3 On board 32 On board 4 On board 33 On board 5 On board 34 On board 6 On board 35 On board 7 On board 36 On board 8 On board 37 On board 9 On board 38 On board 10 On board 39 On board 11 On board 40 On board 12 On board 41 On board 13 On board 42 On board 14 On board 43 On board 15 On board 44 On board 16 On board 45 On ...

Страница 212: ...n board 78 On board 122 On board 79 On board 123 On board 80 On board 124 On board 81 On board 125 On board 82 On board 126 On board 83 On board 127 On board 84 On board 128 On board 85 On board 129 On board 86 On board 130 On board 87 On board 131 On board 88 On board 132 On board 89 On board 133 On board 90 On board 134 On board 91 On board 135 On board 92 On board 136 On board 93 On board 137 O...

Страница 213: ...On board 154 On board 148 On board 155 On board 149 On board 156 On board 150 On board 157 On board 151 On board 158 On board 152 On board 159 On board 153 Module Addr Zone Group Description Module Addr Zone Group Description firealarmresources com ...

Страница 214: ... table below to record devices installed on additional 5815XLs Make a copy of this page if additional pages are needed Table 13 2 Installation Record of Devices Installed on 5815XL Module Addr Zone Group Description Module Addr Zone Group Description firealarmresources com ...

Страница 215: ...Installation Records 151430 13 5 Module Addr Zone Group Description Module Addr Zone Group Description firealarmresources com ...

Страница 216: ...nual 13 6 151430 13 2 Conventional Output Point Record This chart can be used to keep track of how conventional output points circuits have been configured Point Circuit Group Description 1 2 3 4 5 6 7 8 firealarmresources com ...

Страница 217: ...nces compatible with the fire alarm control panel Appliances which can be synchronized indicate the type of snyc available in the columns marked Audio and or Visual Table A 1 Compatible Notification Appliances Manufacturer Model Audio Visual Type AMSECO SH24W 153075 Horn Strobe SAD24 153075 Strobe SAD24 75110 Strobe SL24W 75110 Strobe SL24C 3075110 Strobe SLB24 75 Strobe RSD24 153075 Strobe RSD24 ...

Страница 218: ...e P241575W FC Horn Strobe P241575F FC Horn Strobe P241575K FC Horn Strobe P2430 FC Horn Strobe P2430W FC Horn Strobe P2430K FC Horn Strobe P2475 FC Horn Strobe P2475W FC Horn Strobe P2475K FC Horn Strobe P24110 FC Horn Strobe P24110W FC Horn Strobe P24110K FC Horn Strobe S2430W FC Strobe S2430K FC Strobe S2475 FC Strobe S2475W FC Strobe S2475K FC Strobe S24110 FC Strobe S24110W FC Strobe S24110K F...

Страница 219: ... Strobe GCC24 Multi Candella Horn Strobe Ceiling Mount GCCR24 Multi Candella Horn Strobe Ceiling Mount GCS24 Multi Candella Strobe Ceiling Mount GCSR24 Multi Candella Strobe Ceiling Mount GECR 24 Multi Candella Horn Strobe GES24 15 Strobes GES24 30 Strobes GES24 60 Strobes GES24 75 Strobes GES24 110 Strobes GES24 15 75 Strobes GES24 177 Strobes GES3 24 Multi Candella Strobe GESR 24 Multi Candella ...

Страница 220: ...2 Wire Horn Strobe High Candela P2RH P 2 Wire Horn Strobe High Candela PC2RH 2 Wire Horn Strobe High Candela PC2RH P 2 Wire Horn Strobe High Candela P2W 2 Wire Horn Strobe P2W P 2 Wire Horn Strobe PC2W 2 Wire Horn Strobe PC2W P 2 Wire Horn Strobe P2WH 2 Wire Horn Strobe High Candela P2WH P 2 Wire Horn Strobe High Candela PC2WH 2 Wire Horn Strobe High Candela PC2WH P 2 Wire Horn Strobe High Candela...

Страница 221: ...4 Wire Horn Strobe High Candela PC4RH 4 Wire Horn Strobe High Candela SR Strobe SR P Strobe SCR Strobe SCR P Strobe SRH Strobe High Candela SRH P Strobe High Candela SCRH Strobe High Candela SCRH P Strobe High Candela SW Strobe SW P Strobe SCW Strobe SCW P Strobe SWH Strobe High Candela SWH P Strobe High Candela SCWH Strobe High Candela SCWH P Strobe High Candela SRK Strobe SCRK Strobe SRHK Strobe...

Страница 222: ...n Strobe AS 24MCWH Horn Strobe ASWP 2475W Horn Strobe Weatherproof ASWP 2475C Horn Strobe Weatherproof ASWP 24MCWH Horn Strobe ASWP 24MCCH Horn Strobe CH 70 Chime CH 90 Chime CH70 241575W Chime Strobe CH70 24MCW Chime Strobe CH70 24MCWH Chime Strobe CH90 24MCC Chime Strobe CH90 24MCCH Chime Strobe HS 24 Horn HS4 241575W Horn Strobe HS4 24MCW Horn Strobe HS4 24MCWH Horn Strobe HS4 24MCC Horn Strobe...

Страница 223: ...e Horn Strobe ZNH Horn NS 121575W Horn Strobe NS 241575W Horn Strobe NS 24MCW Horn Strobe NS 24MCC Horn Strobe NS 24MCCH Horn Strobe ZNS MCW Horn Strobe ZNS MCWH Horn Strobe ZNS 24MCC Horn Strobe ZNS 24MCCH Horn Strobe RSS 121575W Strobe RSS 241575W Strobe RSS 24MCC Strobe RSS 24MCCR Strobe RSS 24MCCH Strobe RSS 24MCCHR Strobe RSS 24MCW Strobe RSS 24MCWH Strobe RSSP 121575W Strobe RSSP 241575W Str...

Страница 224: ...RSSWPG 24MCCH Strobe Weatherproof RSSWPR 24MCCH Strobe Weatherproof RSSWP 2475W Strobe Weatherproof RSSWP 2475C Strobe Weatherproof RSSWP 24MCWH Strobe Weatherproof ZRS MCWH Strobe ZRS 24MCC Strobe ZRS 24MCCH Strobe MB G6 24 Motor Bell MB G10 24 Motor Bell MB G6 12 Motor Bell MB G10 12 Motor Bell MIZ 24 R Mini Horn MT 12 24 R Multitone Horn MT4 12 24 Multitone Horn ZRS MCW Strobe MTWPR 24MCCH Mult...

Страница 225: ...r greater than or equal to the maximum reset time of the smoke detector IFP 2000 Identifier 24H Operating voltage Range 17 1 27 3 VDC Table A 2 Compatible Two Wire Smoke Detectors Style B Manufacturer Model Name or Number Base model name or number in parentheses Compatibility ID per Loop Head Base Apollo 55000 350 45681 200 55000 350 45681 200 15 loop 55000 250 45681 200 55000 250 45681 200 24 loo...

Страница 226: ... 2451TH B401B A N A 16 loop Table A 3 Compatible Two Wire Smoke Detectors Style B or Style D Manufacturer Model Name or Number Compatibility ID per Loop Head Base System Sensor 2W B A N A 20 loop 2WT B A N A 20 loop 2WTA B A N A 1 loop 2WTR B A N A 1 loop Table A 2 Compatible Two Wire Smoke Detectors Style B Manufacturer Model Name or Number Base model name or number in parentheses Compatibility I...

Страница 227: ...on 0 05 50 System Sensor 1424 Ionization 0 10 41 System Sensor 1451 w B402B Base Ionization 0 10 39 System Sensor 2112 24ATR Photoelectric 0 50 60 70 System Sensor 2112 24AITR Photoelectric 0 50 60 70 System Sensor 2112 24 D Photoelectric 0 05 50 System Sensor 2112 24R Photoelectric 0 50 60 70 System Sensor 2112 24TR Photoelectric 0 50 60 70 System Sensor 2112 24T D Photoelectric w 135 Thermal 0 0...

Страница 228: ...4 Volt I3 Photo w IsolatedTherm Sounder Relay 05 50 System Sensor 2W MOD2 I3 Loop Test Maintence Mod 05 System Sensor RRS MOD I3 Reversing Relay Sync Module 05 System Sensor 64241 Projected Beam 10 28 4 System Sensor Beam 1224 S Projected Beam 17 38 5 Notes Contact manufacturer for current draws Smoke Detector Base Detector Type Max Standby Current mA Alarm Current mA firealarmresources com ...

Страница 229: ...PE Current mA Edwards DH150A Floor Mount 96 Edwards DH154A Flush Mount 96 Edwards DH158A Surface Mount 96 Rixon Firemark FM 980 Floor Mount single 68 Rixon Firemark FM 996 Surface Wiring 68 Rixon Firemark FM 998 Concealed Wiring 68 MANUFACTURER MODEL Current mA Air Products Controls LTD MR 101 C MR 201 C PAM 1 PAM 2 PAM SD 15 35 15 15 15 System Sensor A77 716B PR 1 PR 2 PR 3 EOLR 1 R 10T R 14T R 2...

Страница 230: ...IFP 2000 Installation Manual A 14 firealarmresources com ...

Страница 231: ...hort cut to using the up or down arrow keys to select characters when naming a point or zone Table B 1 Character Table 000 A 001 B 002 C 003 D 004 E 005 F 006 G 007 H 008 I 009 J 010 K 011 L 012 M 013 N 014 O 015 P 016 Q 017 R 018 S 019 T 020 U 021 V 022 W 023 X 024 Y 025 Z 026 a 027 b 028 c 029 d 030 e 031 f 032 g 033 h 034 i 035 j 036 k 037 l 038 m 039 n 040 o 041 p 042 q 043 r 044 s 045 t 046 u...

Страница 232: ...IFP 2000 Installation Manual B 2 151430 firealarmresources com ...

Страница 233: ...g slip that has the RA number a content list and a detailed description of the problem should be included with each return All products returned to Silent Knight must be sent freight pre paid After product is pro cessed Silent Knight will pay for shipping product back to customer via UPS ground Return the Silent Knight product circuit board only Products that are returned in cabinets will be charg...

Страница 234: ... guidelines described under General Terms and Conditions The defective board must be returned within 30 days of shipment of replacement board for customer to receive credit No credit will be issued if the returned board was damaged due to misuse or abuse Repairs and returns should be sent to Silent Knight Honeywell Attn Repair Department 7550 Meridian Circle N Suite 100 Maple Grove MN 55369 4927 R...

Страница 235: ...ILENT KNIGHT or its authorized distributors This warranty is also void if there is a failure to maintain the products and systems in which they operate in a proper and workable manner In case of defect secure a Return Material Authorization form from our Return Authorization Department This writing constitutes the only warranty made by SILENT KNIGHT with respect to its products SILENT KNIGHT does ...

Страница 236: ...firealarmresources com ...

Страница 237: ...firealarmresources com ...

Страница 238: ...50 Meridian Circle Suite 100 Maple Grove MN 55369 4927 763 493 6455 or 800 328 0103 Fax 763 493 6475 www silentknight com 2008 Honeywell International Inc SILENT KNIGHT by Honeywell firealarmresources com ...

Отзывы: