
Programming
151430
9-7
Alarm Delay Characteristics
3. Select the alarm delay characteristics (see Table 9-1) by pressing the
or
arrow.
Table 9-1Alarm Delay Characteristics
4. Press .
Heat Detector Sensitivity
Use this feature to set the temperature at which high temperature detectors will respond. All
detectors in the zone will respond in the same way. The range for IDP-Heat-HT heat detector
is from 135°F to 190°F
The high temperature IDP heat detectors are absolute temperature devices. This means that
they respond to an alarm immediately if the temperature in the zone goes above the
programmed temperature.
5. Enter the temperature at which the heat detector will respond.
Or
Use the
or
keys to scroll through the range or enter directly from the number keys
on the annunciator, then press
.
Type of Delay
Description
1-Count
One Count (No Delay). When this option is enabled, an alarm occurs immediately when a single device
of any of the following types goes into alarm: detector, manual pull, water flow, Aux1 or Aux2. This is
considered the most typical operation and is the default for all zones.
2-Count
When this type of alarm delay is used, two or more detectors within the zone must go into alarm in order
for the zone to report an alarm. Switches of type manual pull, water flow, Aux1 and Aux2 are an
exception; they will cause an alarm when only one switch is in alarm.
When a single detector is in alarm in a 2-Count zone, the system enters a prealarm condition. In a
prealarm condition, the touchpad PZT beeps and the annunciator display indicates that a prealarm has
occurred. If the zone has been mapped to an output group for the prealarm event, the output group will
activate. The prealarm will not be reported to the central station.
When two count is used detector spacing shall be cut in half, you shall not use the alarm verification
feature, and no delay shall be used.
Alarm Ver.
Alarm verification is an optional false alarm prevention feature that verifies an alarm condition by
resetting the smoke detector. If the alarm condition still exists by the time the reset cycle has completed,
the detector will go into alarm. If the detector is no longer in alarm, no report will go to the central
station. The alarm verification sequence is ignored if the zone is already in alarm.
PAS
This option is intended to be used with an acknowledge switch. An alarm is delayed for 15 seconds,
giving on-site personnel a chance to investigate the alarm. If the acknowledge switch is not activated
within 15 seconds, an alarm occurs automatically.
If this option is enabled for a zone, the zone will respond to an alarm condition as follows:
• The zone will not go into alarm for 15 seconds to allow an on-site operator to activate the acknowl-
edge switch.
• If the operator does not press the acknowledge switch within 15 seconds, the zone will go into
alarm.
• If the operator presses the acknowledge switch within 15 seconds, a 180-second time-frame will
begin counting down. This time-frame allows the operator to investigate the cause of the alarm.
If the operator performs a reset within 180 seconds, the alarm will not occur. If the operator does not
perform a reset within 180 seconds, an alarm will occur automatically.
• The P.A.S. feature will be overridden if another alarm occurs.
SNGL ILOCK
See Section 10.7.1 for single interlock releasing operation.
DBL ILOCK
See Section 10.7.2 for double interlock releasing operation.
firealarmresources.com
Содержание Silent Knight IFP-2000 Module 3
Страница 2: ...firealarmresources com ...
Страница 12: ...IFP 2000 Installation Manual viii firealarmresources com ...
Страница 22: ...IFP 2000 Installation Manual 1 10 151430 firealarmresources com ...
Страница 26: ...IFP 2000 Installation Manual 2 4 151430 firealarmresources com ...
Страница 31: ...Before You Begin Installing 151430 3 5 Figure 3 1 Wire Routing Example firealarmresources com ...
Страница 100: ...IFP 2000 Installation Manual 5 14 151430 firealarmresources com ...
Страница 194: ...IFP 2000 Installation Manual 10 20 151430 firealarmresources com ...
Страница 210: ...IFP 2000 Installation Manual 12 8 151430 firealarmresources com ...
Страница 230: ...IFP 2000 Installation Manual A 14 firealarmresources com ...
Страница 232: ...IFP 2000 Installation Manual B 2 151430 firealarmresources com ...
Страница 236: ...firealarmresources com ...
Страница 237: ...firealarmresources com ...