IFP-2000 Installation Manual
5-6
151430
5.4.2
Network Repeater Installation
The network repeater mounts in its own cabinet. The cabinet must be placed within 2 feet of
the main control panel cabinet in order for the 5 foot ribbon cable to reach between the
repeater and the control panel.
Figure 5-5 Network Repeater mounted in cabinet
Use the following steps to properly mount the network repeater to the IFP-2000.
1. Place the network repeater cabinet within 2’ of the IFP-2000 panel. Use 3/4”or larger
conduit between the IFP-2000 and the repeater cabinet. Install the repeater PCB in the
repeater cabinet using the mounting hardware provided.