IFP-2000 Installation Manual
9-26
151430
10. Select Y (monitor line) or N (don’t monitor line) by pressing the
or
arrow, then
press .
9.6.2.6 Answering Machine Bypass
This option is used in conjunction with the SKSS-2. This feature ensures that an answering
machine will not interfere with communication between the panel and the computer. If an
answering machine is used at the panel site, enable this feature; if an answering machine is not
used, disable the feature.
This option is factory-programmed as Yes (enabled).
The selection made here must match the programming for this option in the Communication
Configuration dialog box of the SKSS-2. See the SKSS-2 manual for more information (PN
151...).
11. Select Y (answering machine bypass enabled) or N (answering machine bypass disabled)
by pressing the
or
arrow, then press
.
9.6.2.7 Phone Line Unused
This option is used so that you can set unused phones lines to “Yes”, then no autotest will be
sent through that line.
This option is factory programmed as No.
12. Select Y or N by pressing the
or
arrow, then press
.
9.6.3
Daytime/Nighttime Sensitivity
If you need to change the time that sensitivity levels take effect (that is, the time that “Day”
and “Night” begin), follow these steps.
1. Enter the installer code. The panel will automatically go to the main menu.
2. Select
for Panel Programming.
Display reads:
Initializing
Please wait . . .
3. Select
for System Options.
4. From the System Options Menu, select
for Daytime/Nighttime Sensitivity.
7
5
2
firealarmresources.com
Содержание Silent Knight IFP-2000 Module 3
Страница 2: ...firealarmresources com ...
Страница 12: ...IFP 2000 Installation Manual viii firealarmresources com ...
Страница 22: ...IFP 2000 Installation Manual 1 10 151430 firealarmresources com ...
Страница 26: ...IFP 2000 Installation Manual 2 4 151430 firealarmresources com ...
Страница 31: ...Before You Begin Installing 151430 3 5 Figure 3 1 Wire Routing Example firealarmresources com ...
Страница 100: ...IFP 2000 Installation Manual 5 14 151430 firealarmresources com ...
Страница 194: ...IFP 2000 Installation Manual 10 20 151430 firealarmresources com ...
Страница 210: ...IFP 2000 Installation Manual 12 8 151430 firealarmresources com ...
Страница 230: ...IFP 2000 Installation Manual A 14 firealarmresources com ...
Страница 232: ...IFP 2000 Installation Manual B 2 151430 firealarmresources com ...
Страница 236: ...firealarmresources com ...
Страница 237: ...firealarmresources com ...