IFP-2000 Installation Manual
9-10
151430
9.4
Group
An output group is made up of output points that have been programmed to respond in the
same way. Output groups simplify programming because you have to program the output
characteristics that are common to all of the group points once, instead of programming each
individual point. Once you have defined the characteristics of output groups, you can assign
each point to the appropriate group. All valid output points are assigned to only one output
group. Unused points are not assigned to any output group. Up to 999 output groups can be
defined per panel.
Each output group is defined as either a voice output group or a non-voice output group.
Output points that are audio circuits (all circuits on the VIP-50 and VIP-CE4) can only be
assigned to voice output groups. Output points that are non-voice circuits (all other points and
circuits that are on all modules except the VIP-50 and VIP-CE4) are assigned to non-voice
output groups.
9.4.1
Edit Group
In the edit group option you can program the name of an output group (Section 9.4.1.1) and
change the properties (Section 9.4.1.2) of that group.
To edit a group, follow these steps:
1. Enter the installer code. The panel will automatically go to the main menu.
2. Select
for Panel Programming.
Display reads:
Initializing
Please wait. . .
3. Press
to enter group menu.
4. Press
to edit group.
5. Enter the number of the group you wish to edit, then press
.
9.4.1.1 Edit Group Name
6. To edit the group name, press
.
A screen similar to the one in Figure 9-4 will display. Select a one-or two word descriptive
name as shown in the diagram. Refer to Appendix B for a list of available characters.
7
3
1
1
firealarmresources.com
Содержание Silent Knight IFP-2000 Module 3
Страница 2: ...firealarmresources com ...
Страница 12: ...IFP 2000 Installation Manual viii firealarmresources com ...
Страница 22: ...IFP 2000 Installation Manual 1 10 151430 firealarmresources com ...
Страница 26: ...IFP 2000 Installation Manual 2 4 151430 firealarmresources com ...
Страница 31: ...Before You Begin Installing 151430 3 5 Figure 3 1 Wire Routing Example firealarmresources com ...
Страница 100: ...IFP 2000 Installation Manual 5 14 151430 firealarmresources com ...
Страница 194: ...IFP 2000 Installation Manual 10 20 151430 firealarmresources com ...
Страница 210: ...IFP 2000 Installation Manual 12 8 151430 firealarmresources com ...
Страница 230: ...IFP 2000 Installation Manual A 14 firealarmresources com ...
Страница 232: ...IFP 2000 Installation Manual B 2 151430 firealarmresources com ...
Страница 236: ...firealarmresources com ...
Страница 237: ...firealarmresources com ...