SDC / DHC
Operation
EN2H-0221GE51 R0808
105
Para-
meter
Designation
Setting range / Setting values
Factory
setting
Setting
0 Temperature
(parameters 12 through
15 are not displayed)
0
1
Volume flow and
temperature (parameters
12 through 14 are not
displayed)
11*
Return limit of
district heating
valve
2
Heat output and
temperature (parameters
13 through 15 are not
displayed)
12* Calibration
of
heat
output
1 ... 9999
1
13* Calibration
of
volume flow
1 ... 9999
1
14* Maximum
heat
output
1 ... 9999 kW
9999
15* Maximum
volume
flow
0,01 ... 99.99 m
3
/h 99.99
* OEM
5.4.8 "Return increase" menu (RETURN CONTR)
The parameters in this menu refer to special settings with regard
to the increase in return temperature with heat generators.
Enabling occurs only with corresponding activation in the
"Hydraulics" menu.
Para-
meter
Designation
Setting range / Setting values
Factory
setting
Setting
01 Return
temperature
setpoint
10 ... 95°C
20
02 Switch-off
differential
1 ... 20 K
2
03
Follow-up time of
pump
0 ... 60 min
1