Operation
SDC / DHC
108 EN2H-0221GE51
R0808
5.4.11 "Buffer" menu (BUFFER)
The parameters in this menu refer to special settings with regard
to solids regulation.
Enabling occurs only with corresponding activation in the
"Hydraulics" menu.
Para-
meter
Designation
Setting range / Setting values
Factory
setting
Setting
01 Minimum
temperature
5 °C to setting value of parameter
02
20
02 Maximum
temperature
Setting value of parameter
01 to 95 °C
80
03 Boiler
temperature
increase
–10 to 80 K
0
04 Buffer
switching
differential
1 to 70 K
2
05 Forced
discharge
OFF
OFF
1
In process water tank
2
In heating circuits
06 Follow-up
switch-
on differential
OFF, (setting value of parameter
07 + 2 K) to 50 K
10
07 Follow-up
switch-
off differential
1 K to (setting value of parameter
06 – 2 K)
5
OFF No
start-up
protection
ON
08 Buffer
start-up
protection
ON Start-up
protection
active
OFF No
discharge
protection
ON
09 Buffer
discharge
protection
ON Discharge
protection
active