SDC / DHC
Operation
EN2H-0221GE51 R0808
75
5.2.3.3.2 Individualised
night-time room temperature for each heating
circuit
►
Press
¦
button.
►
Select desired heating circuit (HC, MC-1 or MC-2) by turning
the input button
î
.
►
Confirm selected circuit by pressing the input button
î
.
►
Set flashing room temperature specification to the desired
value by turning the input button
î
.
►
Confirm set value by pressing the
¦
button.
Alternative: Automatic acceptance of the value after the set
information time (see 5.1.2.7 "System information" button, pg. 35).
5 ... 30 °C
16 °C
5.2.3.3.3 Individualised
operating
mode for each heating circuit
Each heating circuit can be assigned an individualised operating
mode.
►
Press
button.
►
Select desired heating circuit (HC, MC-1 or MC-2) by turning
the input button
î
.
►
Confirm selected circuit by pressing the input button
î
.
►
Select flashing operating mode by turning the input button
î
.
►
Confirm set operating mode by pressing the
button or the
input button
î
.
►
With short-term operating modes (ABSENT, PARTY), set
desired target value by turning the input button
î
and confirm
set value by pressing the input button
î
.
Alternative: Automatic acceptance of the value after the set
information time (see 5.1.2.7 "System information" button, pg. 35).
This parameter specifies the end of heating operation depending
on the outside temperature based on the following criteria:
Setting
C
Setting range
Factory setting
Setting
C