SDC / DHC
Operation
EN2H-0221GE51 R0808
99
Para-
meter
Designation
Setting range / Setting values
Factory
setting
Setting
Heat-
ing
circuit
name
Heating circuit
name
00000 ... ZZZZZ
–
* OEM
5.4.6 "Heat generator" menu (HEAT GENER.
The parameters in this menu refer to the type of the respective
heat generator and the associated specific control functions.
Para-
meter
Designation
Setting range / Setting values
Factory
setting
Setting
OFF
Without heat generator
1
1
Oil/gas - one stage
2
Oil/gas - two stages
3
Oil/gas - 2 x one stage
4 Modulating
burner
01 Design
5 Open
Therm
OFF
No start-up protection
1
1 Unlimited
start-up
protection
2 Start-up
protection
controlled by weather
conditions
02 Start-up
protection
(not if parameter
01 = OFF)
3 Start-up
protection
disconnected
03 Minimum
tem-
perature limit (not
if parameter 01 =
OFF)
5°C to setting value of parameter
04
38 (5 with
automatic
operation)
04 Maximal
temperature limit
(not if parameter
01 = OFF)
Setting value of parameter 03 to
setting value of parameter 30
(OEM maximum limit)
80