R4140G, L AND M FLAME SAFEGUARD PROGRAMMING CONTROLS
60-0770—2
6
Table 2. Static Tests of External Devices
(Continued).
Installing the Programmer (Fig. 3)
���
Open the master switch.
���
Make sure no subbase wiring is projecting out beyond
the terminal blocks. Tuck in wiring against the back of
the subbase so it does not interfere with the contacts.
���
Grasp the handle of the programmer chassis and
engage the chassis hinge brackets with the pivot pins
at the bottom of the subbase.
���
Swing the chassis inward until the spring connectors
engage the knife-blade contacts. Push in until the
contacts are fully engaged.
���
Tighten the chassis retaining screw securely.
Removing the Programmer
���
Open the master switch.
���
Loosen the chassis retaining screw.
���
Pull outward on the handle.
���
Disengage the chassis hinge brackets from the
subbase pivot pins.
HANDLE
CHASSIS
RETAINING
SCREW
SPRING
CONNECTORS
KNIFE-BLADE
CONTACTS (20)
WIRING
SUBBASE
PIVOT PIN (2)
HINGE
BRACKET (2)
PROGRAMMER
CHASSIS
M7965
Fig. 3. Mounting the programmer on the subbase.
Test
No.
R4140
Models
Test
Jumpers Voltmeter
Normal
Operation
If Operation is Abnormal,
Check the Items Listed Below
13
All R4140L
modeIs
L18 and
14-11
13-L2
Firing rate motor drives closed;
line voltage at terminal 13 after
motor closes.
1. Low Fire switch is connected between
terminals 8 and 13. If not, proceed to test
no. 14.
2. Low Fire switch is closed.
3. Firing rate motor and transformer are OK.
14
All R4140L
models
L1-15
and
14-11
13-L2
Firing rate motor drives closed;
line voltage at terminal 13 after
motor closes.
1. Low Fire switch is connected between
terminals 15 and 13. If not, proceed to test
no. 15.
2. Low Fire switch is closed.
3. Firing rate motor and transformer are OK.
15
All R4140G
and R4140L
models
12-11
—
1. Raise setpoint of Series 90
Controller—firing rate motor
should drive toward open.
2. Lower setpoint of Series 90
Controller—firing rate motor
should drive toward closed.
1. Series 90 Controller is OK.
2. Firing rate motor and transformer are OK.
16
R4140M
models with
open damper
contacts
L1-10
—
If damper control is used,
actuator drives damper open.
1. Jumper wire is installed between
terminals 11 and 12.
2. Damper actuator is OK.
17
R4140M
models with
open damper
contacts
L1-8
13-L2
If damper control is used,
spring return drives actuator
and damper closed; line
voltage at terminal 13 after
actuator closes.
1. Low Fire switch is closed.
2. Damper actuator is OK.
Final
All models
CAUTION
After completing these tests, open the master switch and remove all test jumpers from the
subbase terminals. Also remove bypass jumpers from the low fuel pressure limits (if used).