Honeywell R4140G Скачать руководство пользователя страница 17

R4140G, L AND M FLAME SAFEGUARD PROGRAMMING CONTROLS

60-0770—2

17

(Burn a solid instead of a liquid, or a liquid instead of a gas.)
When the maximum refractory temperature is reached, close
all manual fuel shutoff valves, or open the electrical circuits of
all automatic fuel valves. Visually observe when the burner
flame goes out. After the flame goes out, measure the time it
takes for the flame relay 2K to drop out. (Watch or listen to the
flame relay to determine when it drops out.) If the flame relay
fails to drop out within four seconds, the infrared detector is
sensing hot refractory. Immediately terminate the firing cycle.
(Lower the setpoint of the burner controller, or set the fuel
selector switch to OFF. Do not open the master switch.)

NOTE:

Some burners continue to purge their oil lines
between the valve(s) and nozzle(s) even though the
fuel valve(s) is closed. Terminating the firing cycle
(instead of opening the master switch) allows
purging the combustion chamber, if available. This
reduces a buildup of fuel vapors in the combustion
chamber caused by oil line purging.

If the detector is sensing hot refractory, the condition must be
corrected. Add an orifice plate ahead of the cell to restrict the
viewing area of the detector. If this does not work, resight the
detector at a cooler, more distant part of the combustion
chamber. While resighting the detector, remember that it must
also properly sight the flame. For an infrared detector, you
can also try lengthening the sight pipe or decreasing the pipe
size (diameter). For details, refer to the C7015A Instructions,
form 60-2306. Continue adjustments until hot refractory hold-
in is eliminated.

Ultraviolet Response Tests (All Ultraviolet
Detectors) Ignition Spark Response Test

Test to be sure that ignition spark is not actuating flame
relay 2K.

���

Close the pilot and main burner manual fuel shut-off
valves.

���

Start the burner and run through the ignition period.
Ignition spark should occur, but relay 2K must not pull in.
The flame signal should not be more than 1/4 microamp.

���

If relay 2K does pull in, resight the detector farther out
from the spark, or away from possible reflection. It may
be necessary to construct a barrier to block the ignition
spark from the detector’s view. Continue adjustments
until the flame signal due to ignition spark is less than
1/4 microamp.

NOTE:

Honeywell Q624A Solid State Spark Generator
prevents detection of ignition spark when properly
applied with flame detection systems using C7027,
C7035, or C7044 Minipeeper Ultraviolet Flame
Detectors. The Q624A is for use only with gas pilots.

Response to Other Ultraviolet Sources

Some sources of artificial light produce small amounts of
ultraviolet radiation. Under certain conditions, an ultraviolet
detector responds to them as if sensing a flame. Do not use
an artificial light source to check the response of an ultraviolet
detector. To check for proper detector operation, conduct flame
failure response tests (Safety Shutdown Tests 1, 2, and 3)
under all operating conditions.

Flame Signal with Hot Combustion Chamber
(All Installations)

With all initial startup tests and burner adjustments completed,
operate the burner until the combustion chamber is at
maximum expected temperature. (Observe the burner
manufacturer warmup instructions.) Recycle the burner under
these hot conditions and measure the flame signal. Check the
pilot alone, the main burner flame alone, and both together
(unless monitoring only the pilot flame when using an
intermittent pilot, or only the main burner flame when using
direct spark ignition). Check the signal at both the high and the
low firing rate positions and while modulating, if applicable.

Also check the flame failure response time. Lower the
setpoint of the burner controller and observe the time it takes
flame relay 2K to drop out after the burner flame goes out (2K
should drop out within four seconds).

If the flame signal is too low or unsteady, check the flame
detector temperature. Relocate the detector if the
temperature is too high. If necessary, realign the sighting to
obtain the proper signal and response time. If the response
time continues to be too slow, replace the plug-in flame signal
amplifier. If the detector is relocated or resighted, or the
amplifier is replaced, repeat all required checkout tests.

IMPORTANT

Repeat all required Checkout tests after all
adjustments are complete. All tests must be satisfied
with the flame detector(s) in its FINAL position.

Safety Shutdown Tests (All Installations)

Perform these tests at the end of Checkout after all other
tests are complete.

For all R4140 Programmers, safety shutdown should occur
on: (1) failure to ignite the pilot (or first stage burner when
using direct spark ignition), (2) failure to light the main burner
(unless monitoring an intermittent pilot), and (3) loss of flame
during the Run period. (If a self-checking flame detection
system is used, safety shutdown should also occur on a
failure in the detection system. However, because the
programmer acts the same if a flame failure has occurred, no
separate test is necessary.)

For an R4140L, safety shutdown should also occur upon (1)
detection of a flame (or a condition simulating a flame) before
or during prepurge, (2) opening of a preignition interlock
during prepurge, and (3) opening of a lockout interlock after
14 seconds.

On safety shutdown, the lockout switch should trip (pop out)
and lock out the programmer. The ignition and fuel valve
terminals should be de-energized. If used, the external alarm
should turn on. The timer should complete its revolution and
lock up at the start position. The lockout switch must be
manually reset to restart the system.

���

Failure to Ignite Pilot (or First Stage Burner if Using
Direct Spark Ignition).

a.

Close all manual fuel shutoff valves; this includes
the manual pilot shutoff valve and all manual
main burner shutoff valves.

b.

Make sure all interlocks are closed.

Содержание R4140G

Страница 1: ...tion 27 Testing and Maintenance 28 Fig 2 Components of R4140L Programmers RESET BUTTON RELAY TIMER COVER FLAME SIGNAL METER JACK TIMER DIAL TIMER RELAY 2K RELAY 3K RELAY 1K RELAY 4K TIMER MOTOR HINGE BRACKET 2 CHASSIS SAFETY SWITCH BUTTON CHASSIS RETAINING SCREW HANDLE TIP JACK PLUG IN FLAME SIGNAL AMPLIFIER M7959 OPTIONAL HEAVY DUTY COVER PART NO 202050C OR 139695C RESET BUTTON OPTIONAL 202050C C...

Страница 2: ...tarting Vibration Do not install the R4140 where it could be subjected to excessive vibration Vibration shortens the life of the electronic components Weather The R4140 is not designed to be weather tight If it is installed outdoors it must be protected Mounting the Wiring Subbase NOTE For installation dimensions see Fig 1 and 2 in the Specifications for the R4140G L or M The subbase can be mounte...

Страница 3: ...40 to a circuit that is subjected to line voltage variations such as would occur with on off switching of heavy loads A separate power supply circuit can be required for the flame safeguard control Add required disconnect means and overload protection Check all wiring circuits and complete the Static Checkout in Table 2 before installing the R4140 Installing the Flame Detector NOTE Table 1 lists t...

Страница 4: ...rrectly and that the external controllers limits interlocks actuators valves transformers motors and other devices are operating properly Equipment Required 1 Voltmeter W136A or equivalent set on 0 to 300 Vac scale 2 Jumper wires 2 of No 14 wire insulated 12 in 304 8 mm long with alligator clips at both ends General Instructions Perform all applicable tests in Table 2 in the order listed Make sure...

Страница 5: ... opens if connected to terminal 5 NOTE Refer to wiring diagram of the programmer being tested 1 Watch for spark or listen for buzz a Ignition electrodes are clean b ignition transformer is OK 2 Listen for click or feel head of valve for activation a Actuator if used is OK b Pilot valve is OK 7 All models L1 6 Same as test no 6 for connections to terminal 6 If using direct spark ignition check the ...

Страница 6: ...osed line voltage at terminal 13 after motor closes 1 Low Fire switch is connected between terminals 8 and 13 If not proceed to test no 14 2 Low Fire switch is closed 3 Firing rate motor and transformer are OK 14 All R4140L models L1 15 and 14 11 13 L2 Firing rate motor drives closed line voltage at terminal 13 after motor closes 1 Low Fire switch is connected between terminals 15 and 13 If not pr...

Страница 7: ...s with the two scribe marks alongside the receptacle on the programmer Push in the amplifier until the circuit board is fully inserted into the receptacle Make sure the amplifier is firmly in place then replace the relay timer cover Make sure the spring clip on the cover fits over the amplifier NOTE For further information about a self checking amplifier refer to the Instructions packed with the a...

Страница 8: ...ons a Firing rate motor must close by itself spring return when power is removed FM Factory Mutual requirements IRl Industrial Risk Insurers formerly FlA requirements UL Underwriters Laboratories Inc requirements IMPORTANT Before replacing an R4140 make sure the replacement model has the required prepurge time pilot ignition timing on terminal 6 5 second ignition on terminal 18 if required interlo...

Страница 9: ...R C7027A C7035A OR C7044A ULTRAVIOLET FLAME DETECTOR C7012A C E F OR C7076A ULTRAVIOLET FLAME DETECTOR RECTIFYING FLAME ROD RECTIFYING PHOTOCELL OR INFRA RED LEAD SULFIDE FLAME DETECTOR LOW FIRE SWITCH 1 LIMITS C8347 1 2 3 4 7 8 9 5 6 LEAVE INTERLOCKS CONNECTED BETWEEN TERMINALS 4 AND 16 IF INTERLOCKS ARE NOT USED INSTALL A JUMPER WIRE BETWEEN TERMINALS 4 AND 16 IF THE R4140G REPLACEMENT MODEL HAS...

Страница 10: ... FLAME ROD RECTIFYING PHOTOCELL OR INFRA RED LEAD SULFIDE FLAME DETECTOR LOW FIRE SWITCH 10 HIGH FIRE SWITCH 2 LIMITS C8349 1 BURNER MOTOR BLOWER ALTERNATE LOW FIRE SWITCH 9 C7012A C E F OR C7076A ULTRAVIOLET FLAME DETECTOR 1 2 3 4 7 8 9 5 6 LEAVE INTERLOCKS CONNECTED BETWEEN TERMINALS 3 AND 16 LEAVE INTERLOCKS CONNECTED BETWEEN TERMINALS 4 AND 16 IF THERE IS A JUMPER WIRE BETWEEN TERMINALS 14 AND...

Страница 11: ...couple to measure temperature at the flame detector s 8 Orifice plates aperture disks or filters as necessary to adjust sensitivity of flame detector s Checkout Summary The following list summarizes the checkout tests required for each type of installation Instructions for each test are included in this section also consult the burner installation instructions Preliminary Inspection all installati...

Страница 12: ...master switch is closed connections are correct and the power supply is of the correct voltage and frequency Check the detector wiring for defects including incorrect connections wrong type or size of wire deteriorated wire open circuits short circuits leakage paths caused by moisture soot or accumulated dirt For a flame rod make sure there is enough ground area the flame rod is properly located i...

Страница 13: ...blished in ten seconds safety shutdown occurs in about one half minute Let the timer complete its revolution and stop Wait about one minute reset the lockout switch and let the system recycle once If the pilot still does not ignite make the following ignition pilot adjustments a Open the master switch and remove the programmer from the subbase a This minimum or stronger signal is easily obtained w...

Страница 14: ...equired to purge the lines and bring sufficient fuel to the burner NOTE This step requires two people one to open the manual valve s and one to watch for ignition 씈 If the main burner flame is not established within five sec onds or within the normal lightoff time specified by the burner manufacturer close the manual main fuel shutoff valve s and open the master switch Check all burner adjustments...

Страница 15: ...ame is established during IGN within the normal lightoff time specified by the burner manufacturer 씏 Measure the flame signal Continue to check for the proper signal Table 4 through the MAIN part of the timer dial and into the Run period after the timer stops Check the signal at both the high and the low firing rate positions and while modulating if applicable Any pulsating or unsteady readings re...

Страница 16: ...adiation from hot refractory does not mask the flickering radiation of the flame itself Start the burner and monitor the flame signal during the warmup period A decrease in signal strength as the refractory heats up indicates hot refractory saturation If saturation is extreme the flame relay 2K drops out and the system shuts down as though a flame failure occurred If hot refractory saturation occu...

Страница 17: ...ponse of an ultraviolet detector To check for proper detector operation conduct flame failure response tests Safety Shutdown Tests 1 2 and 3 under all operating conditions Flame Signal with Hot Combustion Chamber All Installations With all initial startup tests and burner adjustments completed operate the burner until the combustion chamber is at maximum expected temperature Observe the burner man...

Страница 18: ...erlocks are closed b Reset the Lockout switch c Start the system d After about 30 seconds open a preignition interlock e Relay 3K should drop out and there should be no ignition f Safety shutdown should occur about one half minute after 3K drops out Opening of a Lockout Interlock R4140L Only a Make sure all manual fuel shutoff valves are open this includes the manual pilot shutoff valve if using a...

Страница 19: ...fer to Table 5 and follow the troubleshooting procedure s outlined Refer to Fig 15 16 and 17 for location of relay and timer contacts Access to the contacts can be gained by removing the relay timer cover Fig 4 Fig 11 Adjusting spring connectors IMPORTANT a Blackened M4A M6B M8B M9B or M11B timer contacts are due to normal deposits of impurities caused by breaking an inductive load ignition transf...

Страница 20: ...ll in replace programmer B Relay 1K pulls in but 1 Check manual switch for burner motor 1 Make sure switch is closed burner motor does not start 2 Check external burner motor circuits 2 Make sure circuits are wired correctly replace deteriorated leadwires 3 Check motor power supply motor overload protection and motor starter 3 Replace devices if not operating properly 4 Check burner motor 4 Replac...

Страница 21: ... ignition transformer 5 Check operation of automatic pilot valve or first stage valve open master switch and jumper terminals L1 5 or L1 6 on subbase Refer to appropriate wiring diagram to determine proper terminals Close master switch and listen for click or feel head of valve for activation 5 If valve or actuator is not operating properly replace it 6 Open master switch remove test jumpers from ...

Страница 22: ...t end of main burner flame establishing period 1 Close all manual fuel shutoff valves open master switch and remove programmer from subbase 1 Make sure that external circuits are wired correctly replace deteriorated leadwires Applicable only if using an interrupted pilot 2 If programmer has provisions for extending the main burner flame establishing period MBFEP at terminal 6 check back of program...

Страница 23: ...s b If a running interlock is open determine cause s and correct condition s Make sure that there is airflow If not check burner motor replace if necessary check Airflow switch replace if necessary 3 If the Lockout switch has tripped if the reset button has popped out a For an R4140L only check that all lockout interlocks including the Airflow switch are closed b If using an infrared lead sulfide ...

Страница 24: ...t or first stage burner ignites measure the flame signal as described in Flame Signal Measurement in the Checkout section If the signal is unstable or weak check the flame detector installation and circuitry as instructed Recycle the programmer and measure the flame signal again to obtain a good reading If the flame signal is unstable or less than the minimum acceptable value listed in Table 4 pro...

Страница 25: ...Remove the flame detector leadwire from terminal F on the subbase Be sure the leadwire does not touch anything after removal 5 Reinstall the programmer on the subbase and reset the Lockout switch if popped out 6 Set the Timer switch to the TEST position 7 Proceed to the following instructions for the appropriate amplifier c R7247A Rectification Amplifier green used with rectifying flame rods recti...

Страница 26: ... except substitute a 123514B Flame Simulator in step 3 Restore the programmer to operating condition as follows a Let the timer complete its revolution and set the timer switch to the NORM position b Open the master switch and remove the programmer from the subbase c Reconnect the flame detector Ieadwire to terminal F on the subbase d Reinstall the programmer on the subbase and reset the Lockout s...

Страница 27: ...hese tubes with commercial substitutes Contact Cleaning Field cleaning of relay or timer contacts is not recommended IMPORTANT 1 Do not clean contacts 2 Use extreme care to avoid bending the contacts or changing the specifications or configuration in any way 3 Do not use an abrasive or a burnishing tool to clean contacts 4 Do not use hard paper such as a business card to clean contacts Do not use ...

Страница 28: ...1 M9 M7 M5 M3 M1 MOTOR B B A INSIDE CONTACTS B OUTSIDE CONTACTS A A B A B A DIAL MANY PROGRAMMERS HAVE ONLY 8 OR 10 SETS OF CONTACTS 1 1 C8348 Fig 17 Location of timer contacts front view TESTING AND MAINTENANCE Periodic tests of all boiler controls and safety devices are required to determine that they are operating as designed to provide a measure of safety Because the operation of all control a...

Страница 29: ...Refractory Hold In As required Annual Service Technician See Pilot Turn Down Test Low Water Fuel Cutoff and Alarm Daily Weekly Operator Refer to manufacturer s instruction High Limit Safety Control Annual Service Technician Refer to manufacturer s instructions Operating Control Annual Service Technician Refer to manufacturer s instructions Low Draft Fan and Air Pressure Interlocks Monthly Operator...

Страница 30: ...R4140G L AND M FLAME SAFEGUARD PROGRAMMING CONTROLS 60 0770 2 30 ...

Страница 31: ...R4140G L AND M FLAME SAFEGUARD PROGRAMMING CONTROLS 60 0770 2 31 ...

Страница 32: ...n Hung Kai Centre No 30 Harbour Road Wanchai Hong Kong Honeywell Limited Honeywell Limitée 35 Dynamic Drive Scarborough Ontario M1V 4Z9 Honeywell Latin American Division Miami Lakes Headquarters 14505 Commerce Way Suite 500 Miami Lakes FL 33016 60 0770 2 E C Rev 7 96 Automation and Control Solutions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 ...

Отзывы: